13

Ductless recirculation is intended for applications where an exhaust duct work is not possible to be installed. 
When converted, the hood functions as a recirculating hood rather than an exhaust hood. Fumes and exhaust 
from cooking are drawn and fi ltered by an optional charcoal fi lter. The air is then purifi ed and recirculated back 
within the home.

We recommend to ALWAYS exhaust air outside of the home by employing existing or installing new duct 
work, if possible. The hood is most effective and effi cient as an exhaust hood. Only when the exhaust option 
is not possible should you recourse to converting the hood into a recirculating hood.

When converted to be a recirculating hood, a charcoal fi lter is required on top of the decorative mesh fi lter. 
Order according to its part number below. The decorative mesh fi lter is intended to capture residue from 
cooking and the optional charcoal fi lter helps to purify fumes exhausted from cooking for recirculation.

RECIRCULATING KIT (REQUIRED IF NOT DUCTED OUTSIDE THE HOME)

Kit includes charcoal fi lter, brackets and return air vent.

Hood Model 

       Part No. 

       Filters in Pkg.

ZGE (all models)       ZRC-00GE  

          1

1.   Purchase recirculating kit per the part number above.

2.  Remove decorative mesh fi lter from  hood  and  place  charcoal  fi lter  on  top  of                                                                                                                 

mesh fi lter.  Secure charcoal fi lter to mesh fi lter by using the supplied wire                                                            
brackets as shown in Fig.13.

3.   Reinstall decorative mesh fi lter.

Charcoal Filter Replacement

Hood Model 

      Part No. 

  Qty to Order

ZGE (all models        Z0F-C0GE 

          1

Installation – 

Ductless Recirculation

4.  In order to recirculate the air properly, a return air vent must be installed to 

allow recycled air to be returned to the kitchen, Fig. 14.  Ducting must be run 
from the blower to the return air vent. The return air vent can be positioned 
on top of the cabinet or in a soffi t/ceiling.                      

5.  Enable Charcoal Filter Change indicator on control panel. See page 15.

6.  Charcoal fi lter must be replaced after every 120 hours of use or approximately 

every 3 to 4 months based on an average daily use of 1 hour of cooking time) 
The microprocessor in the controls, when set, will elapse and count usage 
time and indicate when charcoal fi lter replacement is required every 120 hrs.

Fig.13

Fig.14

Summary of Contents for Genova ZGE-E36AS290

Page 1: ...Use Care and Installation Guide www zephyronline com Model number Serial Number JUL11 0301 Zephyr Corporation Genova ZGE E30AS ZGE E36AS ZGE E30AS290 ZGE E36AS290...

Page 2: ...www zephyronline com...

Page 3: ...ng Options 7 Hood Speci cations 8 Preparing the Cabinet 9 Installing the Hood 10 12 Ductless Recirculation 13 FEATURES CONTROLS Touch Controls 14 15 Remote Control Optional 16 MAINTENANCE Hood and Fil...

Page 4: ...te for the type of and amount of food being prepared WARNING TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP FIRE OBSERVE THE FOLLOWING a SMOTHER FLAMES with a close tting lid cook...

Page 5: ...the electrical installation is adequate and in conformance with National Electrical Code ANSI NFPA 70 latest edition or CSA standards C22 1 94 Canadian Electrical Code Part 1 and C22 2 No 0 M91 latest...

Page 6: ...nel pre installed 1 hardware package MODELS ZGE E30AS ZGE E30AS290 ZGE E36AS ZGE E36AS290 PARTS SUPPLIED HARDWARE PACKAGE CONTENTS PARTS NOT SUPPLIED Ducting conduit and all installation tools Cable c...

Page 7: ...ent number length x used 6 8 Round wall cap with damper 30 Ft x Ft Round wall cap with damper 30 Ft x Ft 7 or 8 Round 900 elbow 15 Ft x Ft 7 or 8 7 or 8 Round 450 elbow 9 Ft x Ft Ft Ft Ft 6 8 Round ro...

Page 8: ...32 It is important to install the hood at the proper mounting height Hoods mounted too low could result in heat damage and re hazard while hoods mounted too high will be hard to reach and will lose pe...

Page 9: ...unless using the recirculating option Use single wall rigid Metal ductwork only Fasten all connections with sheet metal screws and tape all joints w certi ed Silver Tape or Duct Tape Ducting Options...

Page 10: ...od side of hood top of hood 500mm 19 11 16 76mm 3 280mm 11 912mm 35 7 8 760mm 29 15 16 242mm 9 1 2 1 5 3 m m 6 197mm 7 3 4 180mm 7 1 16 16mm 5 8 445mm 17 1 2 473mm to 18 5 8 286mm 11 1 4 6mm 1 to 4 1...

Page 11: ...alled to ensure proper alignment of the hood with the cabinet bottom Wood blocking should be ush within cabinet bottom 3 Follow the dimensions in Fig 1 and cut out the bottom of your cabinet to create...

Page 12: ...have access to the interrior of the range hood Fig 3 Fig 4 3 Open cabinet doors Lift range hood and slide it through the opening located in the bottom of the cabinet Fig 4 Make sure opening matches t...

Page 13: ...the captive nuts of each upper installation bracket Tighten screws to adjust the height of range hood until there is no gap between the cabinet bottom and front edge of hood Fig 9 After hood is posit...

Page 14: ...d codes purchase and install appropriate connector if necessary Make sure no packing material is inside hood Power up hood check for leaks around duct tape and verify all functions Fig 11 Fig 12A 11 S...

Page 15: ...OUTSIDE THE HOME Kit includes charcoal lter brackets and return air vent Hood Model Part No Filters in Pkg ZGE all models ZRC 00GE 1 1 Purchase recirculating kit per the part number above 2 Remove de...

Page 16: ...to Normal by pressing once again to Dim and again to switch Off 1 2 3 4 Display Displays blower speed level delay off status mesh filter clean and charcoal filter replace notification 5 Lights Normal...

Page 17: ...coal filter if installed When your hood is installed as a recirculating unit it must be fitted with a charcoal filter to purify exhaust and fumes from cooking and then recirculate the air within the h...

Page 18: ...3 4 Blower On Power Off 2 5 Min Delay Off 3 Lights On Dim Off 4 By pressing the blower and lights will enter Delay Off mode A dot will appear in the lower right corner of the power pack display indica...

Page 19: ...stalled by the factory is intended to lter out residue and grease from cooking It need not be replaced on a regular basis but is required to be kept clean Filter should be cleaned after every 30 hours...

Page 20: ...ing bulb counter clockwise Note Bulb does not unscrew it turns 60 degrees stops and falls out If bulbs are dif cult to turn due to prolonged use rmly attach a glass suction cup approximately the diame...

Page 21: ...19 Maintenance Wiring Diagram 370W 270W...

Page 22: ...blower 3 The hood is not secured in place 3 Check the installation of the hood The motor is working but the lights are not 1 Defective halogen bulb 1 Change the halogen bulb 2 The light bulb is loose...

Page 23: ...Decorative Mesh Filter 50200036 Optional Accessories Recirculating Kit ZRC 00GE Replacement Charcoal Filter each Z0F C0GE RF Remote Control 14000005 To order parts visit us online at http store zephy...

Page 24: ...all labor costs associated with this warranty Limitations of Warranty OUR OBLIGATION TO REPAIR OR REPLACE AT OUR OPTION SHALL BE YOUR SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY WE SHALL NOT BE LIA...

Page 25: ...Guide d utilisation d entretien et d installation www zephyronline com Num ro de mod le Num ro de s rie JUL11 0301 Zephyr Corporation Genova ZGE E30AS ZGE E36AS ZGE E30AS290 ZGE E36AS290...

Page 26: ...www zephyronline com...

Page 27: ...n pour le conduit 7 Sp ci cations de la hotte 8 Pr paration de l armoire 9 Installation de la hotte 10 12 Reprise d air sans conduit 13 COMMANDES Commandes ef eurement 14 16 Commande distance optionne...

Page 28: ...s surveillance lorsque vous cuisinez h Utilisez toujours une batterie de cuisine et des ustensiles convenant au type et la quantit de nourriture que vous pr parez AVERTISSEMENT POUR R DUIRE LES RISQUE...

Page 29: ...en quali S assurer que l installation lectrique est ad quate et qu elle respecte le Code national de l lectricit la plus r cente dition du ANSI NFPA 70 ou des normes du CSA C22 1 94 le Code canadien d...

Page 30: ...Liste du mat riel 4 www zephyronline com 2 M4 x 1...

Page 31: ...pi x pi embout mural circ registre 30 pi x pi 7 or 10 circ coude 90 15 pi x pi 7 or 10 7 or 10 circ coude 45 9 pi x pi pi pi pi 6 chapeau de toiture circ 30 pi x pi 7 or 10 circ chapeau de toiture 30...

Page 32: ...es install es trop basses pourraient tre endommag es par la chaleur en plus de pr senter des risques d incendie plus lev s tandis que les hottes install es trop hautes seront dif ciles atteindre et ve...

Page 33: ...pements doivent tre dirig s l ext rieur de la maison moins que l option de reprise d air ne soit utilis e N utilisez que des conduits en m tal pour cloison simple Fixez toutes les pi ces du conduit av...

Page 34: ...8 www zephyronline com Installation Sp ci cations de la hotte LC...

Page 35: ...e l armoire avec la hotte Les blocs de bois devraient arriver ras du bas de l armoire 3 Respectez les dimensions de la Fig 1 et coupez le bas de l armoire pour cr er une ouverture permettant l install...

Page 36: ...uverture situ e au bas de l armoire Fig 4 Assurez vous que l ouverture correspond aux dimensions indiqu es la page 9 Fig 1 4 Des attaches ressort sont situ es sur les c t s gauche et droit du bo tier...

Page 37: ...n sup rieur Serrez les vis pour ajuster la hauteur de la hotte jusqu ce qu il n y ait plus d espace entre le bas de l armoire et le rebord avant de la hotte Fig 9 Une fois que la hotte est en place se...

Page 38: ...Achetez et installez le connecteur appropri si n cessaire Assurez vous qu aucun mat riel d emballage ne se trouve l int rieur de la hotte Allumez la hotte assurez vous qu il n y a pas de fuites o il y...

Page 39: ...SI AUCUN CONDUIT N EST UTILIS L ensemble comprend un ltre charbon et un d ecteur d air Mod le de hotte Num ro de pi ce Filtres par paquet ZGE tous les mod les ZRC 00GE 1 1 Procurez vous l ensemble de...

Page 40: ...14 www zephyronline com Commandes Commandes ef eurement...

Page 41: ...15 Commandes Indicateur de changement des ltres charbon...

Page 42: ...16 www zephyronline com COMMANDES Indicateur de nettoyage des ltres tamis m talliques...

Page 43: ...ttoyez la commande distance avec des d tergents non abrasifs Suivez les instructions ci dessous pour remplacer la pile Enlevez le couvercle du compartiment pile A l aide d un tournevis plat pour avoir...

Page 44: ...ratifs Le ltre tamis install par le fabricant a pour fonction de ltrer les r sidus et la graisse de cuisson Il ne n cessite aucun remplacement sur une base r guli re mais doit tre gard propre Le ltre...

Page 45: ...dans le sens contraire des aiguilles d une montre Note les ampoules ne se d vissent pas apr s une rotation de 60 degr s elles s arr tent et tombent de la douille Lorsqu il est dif cile de retirer les...

Page 46: ...20 www zephyronline com Entretien Sch ma de c blage...

Page 47: ...x e en place 3 V ri ez l installation de la hotte Le moteur fonctionne mais pas les lumi res 1 L ampoule halog ne est d fectueuse 1 Remplacez l ampoule halog ne 2 L ampoule est desserr e 2 Serrez l am...

Page 48: ...haque Z0B 0020S Filtre tamis d coratif 50200036 Accessoires optionnels Ensemble de reprise d air ZRC 00GE Filtres charbon de remplacement chaque Z0F C0GE Commande distance radio lectrique 14000005 Pou...

Page 49: ...main d uvre associ s la pr sente garantie Restrictions de la garantie NOTRE OBLIGATION DE R PARER OU DE REMPLACER NOTRE GR LE PRODUIT CONSTITUE VOTRE SEUL ET UNIQUE RECOURS SOUS LA PR SENTE GARANTIE...

Reviews: