Installation – 

Mounting Height & Clearance

6

www.zephyronline.com

DUCTING

A minimum of 6” round duct must be used to 
maintain maximum air fl ow effi ciency.

Always use rigid type metal ducts only. Flexible 
ducts could restrict air fl ow by up to 50%.

Use calculation worksheet to compute total duct 
work (Page 5).

ALWAYS, when possible, reduce the number of 
transitions and turns. If a long duct run is required, 
increase duct size from 6” to 7” or 8”.

If turns or transitions are required: Install as far 
away from duct opening and as far apart between 
the two transitions as possible.

Minimum mount height between range top to hood 
bottom should be no less than 26”.

Maximum mount height should be no higher than 
34”.

It is important to install the hood at the proper 
mounting height. Hoods mounted too low could 
result in heat damage and fi re hazard; while hoods 
mounted too high will be hard to reach and will 
loose performance and effi ciency.

If available, also refer to range manufacturer’s 
height clearance requirements and recommended 
hood mounting height above range. Always check 
your local codes for any differences.

Duct cover extension kit available for ceiling 
heights up to 12 feet. Turn to page 19 for part 
number and ordering information.

D

DAMAGE-SHIPMENT / INSTALLATION:

•  Please fully inspect unit for damage before 

installation.

•  If the unit is damaged in shipment, return the 

unit to the store in which it was bought for 
repair or replacement.

•  If the unit is damaged by the customer, repair 

or replacement is the responsibility of the 
customer.

•  If the unit is damaged by the installer (if other 

than the customer), repair of replacement must 
be made by arrangement between customer 
and installer.

26” min.

34” max.

min.  A
min.  B
max. C

min.  D
min.  E
max. F

    

 

 

 

Standard  

Extension

Hood Heights  

 

Duct Cover 

Duct Cove

r

            minimum ducted (A)  27” 

 

42“

 minimum recirculating (B)  31” 

 

46“

                          maximum (C)  50” 

 

80”

Ceiling Heights

           minimum ducted (D)  89” (7’ 5”) 

104“ (8’ 8”)

 minimum recirculating (E)  93” (7’ 9”) 

108“ (9’)

                          maximum (F)  120” (10’)         150” (12’ 6”)

36”

Summary of Contents for ACT Roma Wall ZRO-E30CS

Page 1: ...Use Care and Installation Guide Model number Serial Number www zephyronline com Roma Wall ZRO E30CS ZRO M90CS SEP13 0101 Zephyr Corporation...

Page 2: ...www zephyronline com...

Page 3: ...ce 6 Ducting Options 7 Hood Specifications 8 Mounting the Hood 9 Ductless Recirculating 10 FEATURES CONTROLS ICON Touch Controls 11 12 MAINTENANCE Hood and Filter Cleaning 13 Light Bulbs 14 TROUBLESHO...

Page 4: ...the type of and amount of food being prepared WARNING TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP FIRE OBSERVE THE FOLLOWING a SMOTHER FLAMES with a close fitting lid cookie s...

Page 5: ...ctrical installer To assure that the electrical installation is adequate and in conformance with National Electrical Code ANSI NFPA 70 latest edition or CSA standards C22 1 94 Canadian Electrical Code...

Page 6: ...ccessory Z1C 00RO Recirculating kit accessory ZRC 01RO HARDWARE PACKAGE CONTENTS 1 Light Bulb Removal Suction Cup PARTS SUPPLIED MODELS ZRO E30CS ZRO M90CS 1 Hood with internal blower 1 Duct cover wal...

Page 7: ...ent number length x used 6 8 Round wall cap with damper 30 Ft x Ft Round wall cap with damper 30 Ft x Ft 7 or 8 Round 900 elbow 15 Ft x Ft 7 or 8 7 or 8 Round 450 elbow 9 Ft x Ft Ft Ft Ft 6 8 Round ro...

Page 8: ...will loose performance and efficiency If available also refer to range manufacturer s height clearance requirements and recommended hood mounting height above range Always check your local codes for...

Page 9: ...e unless using the recirculating option Use single wall rigid metal ductwork only Fasten all connections with sheet metal screws and tape all joints w certified Silver Tape or Duct Tape Some Ducting O...

Page 10: ...zephyronline com Installation Hood Specifi cation 4 6 CL 29 15 16 35 7 16 14 1 8 3 15 16 22 1 16 STANDARD min ducted 27 min recirc 31 max 50 Z1C 00RO EXTENSION min ducted 42 min recirc 46 max 80 11 1...

Page 11: ...uct work Seal duct work with aluminum duct tape 10 Power up hood and check for leaks around duct tape 11 Place telescopic duct covers onto hood and extend inner top duct cover upwards and secure to du...

Page 12: ...coal filters help to purify fumes exhausted from cooking for recirculation RECIRCULATING KIT REQUIRED IF NO DUCTING IS USED Kit includes charcoal filters and air diverter plate Hood Models Part No Fil...

Page 13: ...ction is enabled will turn the hood off and cancel the Delay Off Function ACT Verification Airflow Control Technology ACT allows the installer to set the maximum fan CFM to align with local codes and...

Page 14: ...bled if recirculating hood To enable Charcoal Filter Replacement Reminder With hood off hold button and button simultaneously for two seconds All LED indicators will illuminate for three seconds confi...

Page 15: ...with the grain Do not use any product containing chlorine bleach Do not use orange cleaners Aluminum Mesh Filters The aluminum mesh filters installed by the factory are intended to filter out residue...

Page 16: ...ot Remove by turning bulb counter clockwise Note Bulb does not unscrew it turns 60 degrees stops and falls out If bulbs are difficult to turn due to prolonged use firmly attach the included glass suct...

Page 17: ...place 2 Damaged blower wheel 2 Replace the blower 3 The hood is not secured in place 3 Check the installation of the hood The blower is working but the lights are not 1 Defective halogen bulb 1 Change...

Page 18: ...OLTS HZ MAX AMPS 120 60 3 5 USE ONLY TYPE MR16 GU10 50 W MAX HALOGEN LIGHT BULBS ZRO E30CS ZRO M90CS CIRCUIT DIAGRAM ACT 390 CFM Fan Max 320W 2 6A ACT 290 CFM Fan Max 303W 2 5A Power consumption shown...

Page 19: ...CFM The usage of ACT may not be necessary for your installation Please check your local codes for CFM restrictions By default the maximum blower CFM is set to 600 To verify if your installer enabled A...

Page 20: ...18 www zephyronline com Fan Curve Diagrams...

Page 21: ...er each 50200053 Optional Accessories Recirculating Kit ZRC 01RO Replacement Charcoal Filter each Z0F C002 Extension Duct Cover Z1C 00RO Universal Make Up Air Damper MUA006A To order parts visit us on...

Page 22: ...rst year from the date of your original purchase you are also responsible for all labor costs associated with this warranty Limitations of Warranty OUR OBLIGATION TO REPAIR OR REPLACE AT OUR OPTION SH...

Page 23: ...Guide d utilisation d entretien et d installation www zephyronline com Num ro de mod le Num ro de s rie SEP13 0101 2013 Zephyr Corporation Roma Wall ZRO E30CS ZRO M90CS...

Page 24: ...www zephyronline com...

Page 25: ...tallation pour le conduit 7 Sp cifications de la hotte 8 Montage de la hotte 9 Reprise d air sans conduit 10 COMMANDES ICON Commandes lectroniques 11 12 ENTRETIEN Nettoyage des filtres et de la hotte...

Page 26: ...ns surveillance lorsque vous cuisinez h Utilisez toujours une batterie de cuisine et des ustensiles convenant au type et la quantit de nourriture que vous pr parez AVERTISSEMENT POUR R DUIRE LES RISQU...

Page 27: ...Communiquer avec un installateur lectricien qualifi S assurer que l installation lectrique est ad quate et qu elle respecte le Code national de l lectricit la plus r cente dition du ANSI NFPA 70 ou de...

Page 28: ...Liste du mat riel 4 www zephyronline com ZRO E30CS ZRO M90CS ZRC 01RO...

Page 29: ...pi x pi embout mural circ registre 30 pi x pi 7 or 10 circ coude 90 15 pi x pi 7 or 10 7 or 10 circ coude 45 9 pi x pi pi pi pi 6 chapeau de toiture circ 30 pi x pi 7 or 10 circ chapeau de toiture 30...

Page 30: ...r senter des risques d incendie plus lev s tandis que les hottes install es trop hautes seront difficiles atteindre et verront leur efficacit et leur rendement r duits Si elles sont disponibles consul...

Page 31: ...ements doivent tre dirig s l ext rieur de la maison moins que l option de reprise d air ne soit utilis e N utilisez que des conduits en m tal pour cloison simple Fixez toutes les pi ces du conduit ave...

Page 32: ...hyronline com Installation Sp cifi cations de la hotte 4 6 CL 29 15 16 35 7 16 14 1 8 3 15 16 22 1 16 STANDARD min ducted 27 min recirc 31 max 50 Z1C 00RO EXTENSION min ducted 42 min recirc 46 max 80...

Page 33: ...is pourraient derri re la cloison s che si aucune poutre n est pr sente Des dispositifs d ancrage au mur peuvent galement tre utilis s mais v rifiez d abord les r glementations locales avant d utilise...

Page 34: ...ident la purification des vapeurs et fum es de la cuisson lors de la reprise d air ENSEMBLE DE REPRISE D AIR REQUIS SI AUCUN CONDUIT N EST UTILIS L ensemble comprend des filtres charbon et un d flecte...

Page 35: ...d utilisation pour teindre la hotte et annuler la fonction d arr t retardement V rification de la ACT La technologie de contr le du d bit d air permet l installeur d ajuster la quantit maximale d vacu...

Page 36: ...ar d faut doit tre activ lors de l utilisation du mode de recirculation d air Pour activer le rappel de remplacement des filtres charbon Lorsque la hotte est teinte tenez les touches et enfonc es simu...

Page 37: ...s le sens du grain N utilisez pas de produits blanchir au chlore ou d agents nettoyants orange Filtres tamis en aluminium Les filtres tamis en aluminium install s par le fabricant ont pour fonction de...

Page 38: ...d vissant dans le sens contraire des aiguilles d une montre Note les ampoules ne se d vissent pas apr s une rotation de 60 degr s elles s arr tent et tombent de la douille Lorsqu il est difficile de r...

Page 39: ...pareil vibre 1 Le moteur n est pas bien fix en place 1 Fixez solidement le moteur en place 2 La roue du ventilateur est endommag e 2 Remplacez le ventilateur 3 La hotte n est pas bien fix e en place 3...

Page 40: ...0CS SCHEMA DE CIRCUIT ROUGE ROUGE JUANE JUANE JUANE GRIS BRUN BRUN ROUGE BLEU BLEU VERT VERT BLANC BLANC BLANC BLANC NOIR NOIR NOIR NOIR BLANC Sch ma de c blage Consommation nerg tique avec la configu...

Page 41: ...na tre les restrictions en mati re de pieds cubes par minute Par d faut le nombre maximal de pi3 min du ventilateur est de 600 Pour v rifier si votre installateur a activ la ACT appuyez sur la touche...

Page 42: ...18 www zephyronline com Diagrammes des courbes caract ristiques des ventilateurs...

Page 43: ...ssoires optionnels Ensemble de reprise d air ZRC 01RO Filtres charbon de remplacement chaque Z0F C002 Ensemble de prolongement de recouvrement de conduit Z1C 00RO Pour commander des pi ces visitez nou...

Page 44: ...responsable de tous les frais de main d uvre associ s la pr sente garantie Restrictions de la garantie NOTRE OBLIGATION DE R PARER OU DE REMPLACER NOTRE GR LE PRODUIT CONSTITUE VOTRE SEUL ET UNIQUE R...

Reviews: