MINiBOX 25 v2
Multifunction actuator with 2 outputs and 5 inputs
ZIOMN25V2
TECHNICAL DOCUMENTATION
FEATURES
•
2 different configurable outputs: shutter channel (up to 1) and individual
outputs (up to 2)
•
Outputs suitable for capacitive loads, maximum 140 µF.
•
5 analog/digital inputs.
•
Manual output operation with push button and LED Status indicator.
•
10 logic functions.
•
Output timing.
•
4 thermostats.
•
Total data saving on KNX bus failure.
•
Integrated KNX BCU.
•
Dimensions 67 x 90 x 35 mm (2 DIN units).
•
DIN rail mounting (EN 50022), with fixing clamp.
•
Possibility of connecting different phases in adjacent outputs.
•
Conformity with the CE directives (CE-mark on the right side).
1. Analog/Digital inputs
2. Outputs
3. Output status LED indicator
4. Output control button
5. Programming/test LED
6. Programming/test button
7. KNX Connector
A1
A2
M
N
L
A1
A2
N
L
L1
L2
C IN
C IN
C I
C IN
A1
A2
N
L1
L1
L2
L2
4
1
7
6
3
5
2
Figure 1: MINiBOX 25 v2
Programming/Test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe
mode. If this button is held for more than 3 seconds, the device enters the test mode.
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual mode
is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it starts a blue blinking sequence.
GENERAL SPECIFICATIONS
CONCEPT
DESCRIPTION
Type of device
Electric operation control device
KNX supply
Voltage (typical)
29VDC SELV
Voltage range
21..31VDC
Maximum
consumption
Voltage
mA
mW
29VDC (typical)
4.6
133.4
24VDC¹
10
240
Connection type
Typical TP1 bus connector for 0.80mm Ø rigid cable
External power supply
Not required
Operation temperature
0°C .. +55°C
Storage temperature
-20°C .. +55°C
Operation humidity
5 .. 95%
Storage humidity
5 .. 95%
Complementary characteristics
Class B
Protection class / Overvoltage category
II / III (4000V)
Operation type
Continuous operation
Device action type
Type 1
Electrical stress period
Long
Degree of protection / Pollution degree
IP20 / 2 (clean environment)
Installation
Independent device to be mounted inside electrical panels with DIN rail (EN
50022)
Minimum clearances
Not required
Response on KNX bus failure
Data saving according to parameterization
Response on KNX bus restart
Data recovery according to parameterization
Operation indicator
The programming LED indicates programming mode (red) and test mode
(green). Each output LED indicates its status
Weight
78g
PCB CTI index
175V
Housing material / Ball pressure test temperature
PC FR V0 halogen free / 75ºC (housing) - 125ºC (connectors)
¹ Maximum consumption in the worst-case scenario (KNX Fan-In model)