MINiBOX 0-10V X3 

3 fold 0-10V analog input/output multifunction module 

ZIO3X010 

TECHNICAL DOCUMENTATION 

 

FEATURES 

 

3 connections than can be configured as 0-10V output, 0-10V input or 
4-20mA input 

 

Manual operation of the 0-10VDC outputs 

 

1 fan coil module 

 

3 thermostats 

 

10 logic functions 

 

Total data saving on power failure 

 

Integrated KNX BCU 

 

Dimensions 67 x 90 x 36mm (2 DIN units) 

 

DIN rail mounting according to IEC 60715 TH35, with fixing clamp 

 

Conformity with the CE directives (CE-mark on the right side) 

 

 

 

1. Multifunction inputs/outputs 

2.  0-10V output status LED 

3.  0-10V output control button 

4.  Programming/Test button 

5.  Programming/Test LED 

6.  KNX connector 

7.   Fixing clamp 

Figure 1: MINiBOX 0-10V X3 

Programming/Test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe 
mode. If this button is held for more than 3 seconds, the device enters the test mode. 
 
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual mode 
is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash. 

GENERAL SPECIFICATIONS 

CONCEPT 

DESCRIPTION 

Type of device 

Electric operation control device 

KNX supply 

Voltage (typical) 

29VDC SELV 

Voltage range 

21..31VDC 

Maximum 
consumption 

Voltage 

mA 

mW 

29VDC (typical) 

18.5 

536.5 

24VDC¹ 

25 

600 

Connection type 

Typical TP1 bus connector for 0.80mm Ø rigid cable 

External power supply 

Not required 

Operation temperature 

0°C .. +55°C 

Storage temperature 

-20°C .. +55°C 

Operation humidity 

5 .. 95% 

Storage humidity 

5 .. 95% 

Complementary characteristics 

Class B 

Protection class 

III 

Operation type 

Continuous operation 

Device action type 

Type 1 

Electrical stress period 

Long 

Degree of protection 

IP20, clean environment 

Installation 

Independent device to be mounted inside electrical panels with DIN rail (IEC 
60715) 

Minimum clearances 

Not required 

Response on KNX bus failure 

Data saving according to parameterization 

Response on KNX bus restart 

Data recovery according to parameterization 

Operation indicator 

The programming LED indicates programming mode (red) and  test mode 
(green). Each output LED indicates its status 

Weight 

80g 

PCB CTI index 

175V 

Housing material 

PC FR V0 halogen free 

¹ Maximum consumption in the worst-case scenario (KNX Fan-In model). 