MAXinBOX SHUTTER 4CH / 8CH v2

 

http://www.zennio.com

 

                 

Technical Support:

 

http://support.zennio.com

 

 

13 

As described previously if the device is in Test On mode, any command sent from the 

KNX  bus to  the  actuator  will not affect  the  channel  and no  status  objects  will be  sent 

(only periodically timed objects such as Heartbeat or logic functions will continue to be 

sent to the bus) while Test ON mode is active. However, in the case of the "Alarm" and 

"Block" objects, although in Test ON mode the actions received by each object are not 

taken into account, the evaluation of their status is carried out when exiting this mode, 

so that any change in the alarm status or blocking of the outputs while Test ON mode 

is  active  is  taken  into  account  when  exiting  this  mode  and  is  updated  with  the  last 

status detected. 

Important

the device is delivered from factory with the channel disabled, and with both 

manual modes (Test Off and Test On) enabled by default

ETS PARAMETERISATION 

The 

manual control 

is configured from the Configuration tab, under Manual Control.  

The only two parameters are: 

 

Figure 7. 

Manual Control

 

 

Manual Control

 [

Disabled / Only Test Off Mode / Only Test On Mode / 

Test 

Off Mode + Test On Mode

]. Depending on the selection, the device will permit 

using  the  manual  control  under  the  Test  Off,  the  Test  On,  or  both  modes. 

Note  that,  as  stated  before,  using  the  Test  Off  mode  does  not  require  any 

special  action,  while  switching  to  the  Test  On  mode  does  require  long-

pressing the Prog/Test button. 

 

Manual  Control  Lock 

[

enabled/

disabled

]:  unless  the  above  parameter  has 

been  “Disabled”,  the  Lock  Manual  Control  parameter  provides  an  optional 

procedure  for  locking  the  manual  control  in  runtime. When  this  checkbox  is 

enabled,  object  “

Manual  Control  Lock

”  turns  visible,  as  well  as  two  more 

parameters: 

Summary of Contents for MAXinBOX SHUTTER 4CH

Page 1: ...MAXinBOX SHUTTER 4CH 8CH v2 4 Channel 8 Channel Shutter Actuator USER MANUAL ZIOMBSH4V2 ZIOMBSH8V2 Application program version 1 2 User manual edition 1 2 _a www zennio com...

Page 2: ...ennio com 2 CONTENTS Contents 2 1 Introduction 3 1 1 MAXinBOX SHUTTER 4CH 8CH v2 3 1 2 Installation 4 1 3 Start Up and Power Loss 5 2 Configuration 6 2 1 General 6 2 2 Outputs 8 2 3 Logic Functions 8...

Page 3: ...for controlling motorised shutter blind systems The most outstanding features are 8 16 relay outputs configurable as up to 4 8 independent shutter channels with or without slats 20 customisable multi...

Page 4: ...MAXinBOX SHUTTER 4CH v2 The main elements of the device are described next Test Prog Pushbutton 5 a short press on this button sets the device into the programming mode making the associated LED 3 lig...

Page 5: ...ink in blue colour for a few seconds before the device is ready External orders will not be executed during this time but afterwards Depending on the configuration some specific actions will also be p...

Page 6: ...om this screen it is possible to activate deactivate all the required functionality Figure 2 General screen Outputs disabled enabled 1 enables o disables the Outputs tab on the left menu See section 2...

Page 7: ...ending of Indication objects on bus voltage recovery Heartbeat Periodic Alive Notification disabled enabled this parameter lets the integrator incorporate a one bit object to the project Heartbeat Obj...

Page 8: ...cts specifically enabled for this purpose MAXinBOX SHUTTER 4CH 8CH v2 can implement up to 20 different and independent functions each of them entirely customisable and consisting in up to 4 consecutiv...

Page 9: ...annel the channel will interrupt such temporisation will be interrupted and only the delay and the action of the new scene will be executed ETS PARAMETERISATION Prior to setting the scene temporisatio...

Page 10: ...channel Note In the configuration of a scene of a shutter channel it is possible to parameterize several scenes with the same scene number This means that several delay parameters associated with the...

Page 11: ...user presses from the start On the contrary switching to the Test On mode unless disabled by parameter needs to be done by long pressing the Prog Test button for at least three seconds until the LED i...

Page 12: ...ing the Test On mode it will only be possible to control the shutters through the on board pushbuttons Orders received through communication objects will be ignored with independence of the channel th...

Page 13: ...tus detected Important the device is delivered from factory with the channel disabled and with both manual modes Test Off and Test On enabled by default ETS PARAMETERISATION The manual control is conf...

Page 14: ...ck unlock should take place respectively upon the reception through the aforementioned object of values 0 and 1 or the opposite Initialization Unlocked Locked Last Value sets how the lock state of the...

Page 15: ...1 Heartbeat Object to Send 1 Sending of 1 Periodically 5 16 27 38 49 60 71 82 93 104 115 126 137 148 159 170 181 192 203 214 225 236 247 258 1 Byte I C W DPT_SceneControl 0 63 128 191 Ox Scenes 0 63...

Page 16: ...410 438 466 494 522 550 578 1 Bit I C W DPT_UpDown 0 1 Cx Move 0 Raise 1 Lower 271 299 327 355 383 411 439 467 495 523 551 579 1 Bit I C W DPT_Step 0 1 Cx Stop Step 0 Stop StepUp 1 Stop StepDown 1 Bit...

Page 17: ...569 597 1 Bit I C T W U DPT_Occupancy 0 1 Cx Presence No Presence 0 Presence 1 No Presence 1 Bit I C T W U DPT_Occupancy 0 1 Cx Presence No Presence 0 No Presence 1 Presence 290 318 346 374 402 430 4...

Page 18: ...T_Switch 0 1 FCx Fan Speed 2 Status 0 Off 1 On 621 654 687 720 753 786 1 Bit O C T R DPT_Switch 0 1 FCx Fan Speed 3 Status 0 Off 1 On 622 655 688 721 754 787 1 Byte I C W U DPT_Value_1_Ucount 0 255 FC...

Page 19: ...atus 0 Open 1 Closed 1 Bit O C T R DPT_Switch 0 1 FCx Heating Valve Status 0 Closed 1 Open 632 665 698 731 764 797 1 Bit O C T R DPT_Switch 0 1 FCx Cooling Valve Anti Seize Protection Status 0 Not Act...

Page 20: ...57 958 959 960 961 962 963 964 965 966 967 968 969 970 971 972 973 974 975 976 977 978 1 Bit O C T R DPT_Bool 0 1 LF Function x Result 1 Bit Boolean 1 Byte O C T R DPT_Value_1_Ucount 0 255 LF Function...

Page 21: ...n and send us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio c...

Reviews: