MAXinBOX SHUTTER 4CH / 8CH v2
Technical Support:
13
As described previously if the device is in Test On mode, any command sent from the
KNX bus to the actuator will not affect the channel and no status objects will be sent
(only periodically timed objects such as Heartbeat or logic functions will continue to be
sent to the bus) while Test ON mode is active. However, in the case of the "Alarm" and
"Block" objects, although in Test ON mode the actions received by each object are not
taken into account, the evaluation of their status is carried out when exiting this mode,
so that any change in the alarm status or blocking of the outputs while Test ON mode
is active is taken into account when exiting this mode and is updated with the last
status detected.
Important
:
the device is delivered from factory with the channel disabled, and with both
manual modes (Test Off and Test On) enabled by default
.
ETS PARAMETERISATION
The
manual control
is configured from the Configuration tab, under Manual Control.
The only two parameters are:
Figure 7.
Manual Control
Manual Control
[
Disabled / Only Test Off Mode / Only Test On Mode /
Test
Off Mode + Test On Mode
]. Depending on the selection, the device will permit
using the manual control under the Test Off, the Test On, or both modes.
Note that, as stated before, using the Test Off mode does not require any
special action, while switching to the Test On mode does require long-
pressing the Prog/Test button.
Manual Control Lock
[
enabled/
disabled
]: unless the above parameter has
been “Disabled”, the Lock Manual Control parameter provides an optional
procedure for locking the manual control in runtime. When this checkbox is
enabled, object “
Manual Control Lock
” turns visible, as well as two more
parameters: