background image

© Zennio Avance y Tecnología S.L. 

Edition 4 

Futher information 

www.zennio.com

 

Page 2/2 

 

 

SAFETY INSTRUCTIONS 

 Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country. 

 Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for th e entire 

KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other 
accessories, in case of being installed. 

 Once the device is installed (in the panel or box), it must not be accessible from outside. 

 Keep the device away from water and do not cover it with clothes, paper or any other material while in use. 

 The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructi ons at 

http://zennio.com/weee-regulation. 

OUTPUTS SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of outputs 

Output type 

Potential-free  outputs  through  bistable  relays 
with tungsten pre-contact / Micro-disconnection 

Rated current per output 

AC 16(6)A @ 250VAC (4000VA) 
DC 7A @ 30VDC (210W) 

Maximum load 
per output 

Resistive 

4000W 

Inductive 

1500VA 

Maximum inrush current 

800A/200μs 
165A/20ms 

Different phases connection  

Possibility  of  connecting  different  phases  in 
adjoining outputs  

Maximum current per block 

40A 

Connection method 

Screw terminal block 

Cable cross-section 

1.5-4mm² (IEC) / 26-10AWG (UL) 

Outputs per common 

Maximum response time 

10ms 

Mechanical lifetime (min. cycles) 

3 000 000 

 

0-10V OUPUT SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Número de salidas 

Ouput type 

0-10VDC 

Maximum load per output 

1.5mA 

Connection method 

Screw terminal block  

Cable cross-section 

0.5-2.5mm² (IEC) / 26-12AWG (UL) 

Output per common 

 

INPUTS SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of inputs 

Inputs per common 

Operation voltage 

+3.3VDC in the common 

Operation current 

1mA @ 3.3VDC (per input) 

Switching type 

Dry  voltage  contacts  between  input  and 
common 

Connection method 

Screw terminal block 

Cable cross-section 

0.5-2.5mm² (IEC) / 26-12AWG (UL) 

Maximum cable length 

30m 

NTC probe length 

1.5m (up to 30m) 

NTC accuracy (@ 25°C) 

±0.5°C 

Temperature resolution 

0.1°C 

Maximum response time 

10ms 

 

 In order  to ensure the  expected  status of  the relays, 

please check that the device is connected to the KNX bus 
before energizing the power circuit. 
 

WIRING DIAGRAMS 

Figure 2: wiring example for 4-pipe fan coil with 4-

speed fan (up) and for 2-pipe fan coil with 3-speed 

fan (down). 

Attaching MAXinBOX FC 0-10V VALVE to DIN rail: 

Removing MAXinBOX FC 0-10V VALVE from DIN rail:

 

* The micro switch number 2 in the ZN1IO-DETEC-P must be in 

Type B position

 to work properly.

 

INPUTS CONNECTION 

Any combination of the next 

accessories

 is allowed on the inputs: 

Zennio  temperature 
probe.

 

 

 

Up  to  two  motion  sensors 
can  be  plugged  into  the 
same  device  input  (parallel 
wiring)

 

 

 

Motion 

sensor 

screw 

terminal.

 

Motion sensor references:

 

ZN1IO-DETEC-X

 

ZN1IO-DETEC-P

*

 

Temperature Probe

 

Motion Sensor

 

 

 

Switch/Sensor/ 

Push button

 

 

 

G/L 

G0/N 

G/L 

G0/N 

G/L 

G0/N 

G/L 

G0/N 

0-10V  outputs 

according  to  the  number  of  fan 

coil pipes

:

 

Fan Coil 

0-10V output 

Valve function 

4 pipes 

V1 

Cooling valve 

V2 

Heating valve 

2 pipes 

V1 

Cooling and/or 

heating valve 

  