MAXinBOX FC 0-10V VALVE
2-pipe or 4-pipe fan coil controller with 0-10VDC valve and up to 4 fan speed
ZCL-FC010V
TECHNICAL DOCUMENTATION
FEATURES
•
2 x 0-10VDC individual outputs for valve control.
•
4 individual outputs (suitable for capacitive loads, maximum 140µF)
capable of controlling up to 4 fan speeds.
•
4 analog/digital inputs.
•
Manual output operation in 0-10VDC and individual outputs with push
button and status indicator LED.
•
Logical functions.
•
Output timing facilities.
•
Total data saving on power failure.
•
DIN rail unit assembly (EN 50022), with snap fit clamp.
•
Size 67 x 90 x 80 mm (4.5 DIN units).
•
KNX BCU integrated
•
Possibility to connect different phases in adjoining outputs.
•
Conformity with the CE directives (CE-mark on the right side).
1. Analog/Digital inputs
2. 0-10VDC outputs
3. Output status LED indicator
4. Output control button
5. Programming/Test LED
6. Lower outputs
7. KNX connection
8. Programming/Test button
Figure 1: MAXinBOX FC 0-10V VALVE
Programming/test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe
mode. If this button is held for more than 3 seconds, the device enters the test mode.
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual mode
is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it starts a blue blinking sequence.
GENERAL SPECIFICATIONS
CONCEPT
DESCRIPTION
Type of device
Electric operation control device
KNX supply
Voltage (typical)
29VDC SELV
Voltage range
21..31VDC
Maximum
consumption
Voltage
mA
mW
29VDC (typical)
11
319
24VDC¹
15
360
Connection type
Typical TP1 bus connector for 0.80mm Ø rigid cable
External power supply
Not required
Operation temperature
0°C .. +55°C
Storage temperature
-20°C .. +55°C
Operation humidity
5 .. 95% (No condens.)
Storage humidity
5 .. 95% (No condens.)
Complementary characteristics
Class B
Protection class
II
Operation type
Continuous operation
Device action type
Type 1
Electrical stress period
Long
Degree of protection
IP20, clean environment
Installation
Independent device to be mounted inside electrical panels with DIN rail (EN
50022)
Minimum clearances
Not required
Response on KNX bus failure
Data saving according to parameterization
Response on KNX bus restart
Data recovery according to parameterization
Operation indicator
The programming LED indicates programming mode (red) and test mode
(green). Each output LED indicates its status
Weight
248g
PCB CTI index
175V
Housing material
PC FR V0 halogen free
¹ Maximum consumption in the worst case scenario (KNX Fan-In model)
1
7
8
3
5
6
2
4