© Zennio Avance y Tecnología S.L.
Edition 2
Further information
Page
2
/
2
SAFETY INSTRUCTIONS
•
Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country.
•
Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire
KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other
accessories, in case of being installed.
•
Once the device is installed (in the panel or box), it must not be accessible from outside.
•
Keep the device away from water and do not cover it with clothes, paper or any other material while in use.
•
The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at
http://zennio.com/weee-regulation.
Removing MAXinBOX 24 from DIN rail:
Attaching MAXinBOX 24 to DIN rail:
Figure 3.
Mounting MAXinBOX 24
on a DIN rail
OUTPUTS SPECIFICATIONS AND CONNECTIONS
CONCEPT
DESCRIPTION
Contact type
Potential-free outputs through bistable relays with tungsten pre-contact.
Disconnection type
Micro-disconnection
Rated current per output
16(6)A * 250VAC (4000VA)
16(6)A * 30VDC (480W)
Maximum power
per output
Resistive
4000W
Inductive
1500W
Maximum inrush current
800A/200
μs (fluorescent lamps)
165A/20ms (resistive lamps)
Number of outputs
24 outputs
Outputs per common (Channel)
1 individual output
Different phases connection
Possibility to connect different phases in adjoining outputs
Total maximum current in device
40A per block
Connection type
Screw terminal block
Recommended cable section
0.5mm² to 4mm² (26-10 AWG)
Maximum response time
50ms
Lifetime
Mechanical (min)
3 million cycles (60cpm)
Electrical (min.)
100.000 cycles at max. current (6cpm and resistive load)
WIRING AND ASSEMBLY DIAGRAMS
Figure 2.
Wiring examples (from left to right):
individual outputs in channel A with the same and different phases, channel A as
shutter channel, and channel A and B as fan coil controller (2 pipe and three-speed fan).
⚠
In order to ensure the
expected status of the relays,
please check that the device is
connected to the KNX bus
before energizing the power
circuit.