SAFETY INSTRUCTIONS 

 Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country. 

 Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the entire 

KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other 
accessories, in case of being installed. 

 Once the device is installed (in the panel or box), it must not be accessible from outside. 

 Keep the device away from water and do not cover it with clothes, paper or any other material while in use. 

 The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at 

http://zennio.com/weee-regulation. 

Removing MAXinBOX 24 from DIN rail:

 

Attaching MAXinBOX 24 to DIN rail: 

 

Figure 3.

 Mounting MAXinBOX 24 

on a DIN rail  

 

OUTPUTS SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Contact type 

Potential-free outputs through bistable relays with tungsten pre-contact. 

Disconnection type 

Micro-disconnection 

Rated current per output 

  16(6)A * 250VAC (4000VA)       

  16(6)A * 30VDC (480W) 

Maximum power 
per output  

Resistive 

4000W 

Inductive 

1500W 

Maximum inrush current  

800A/200

μs (fluorescent lamps) 

165A/20ms (resistive lamps) 

Number of outputs 

24 outputs 

Outputs per common (Channel) 

1 individual output 

Different phases connection 

Possibility to connect different phases in adjoining outputs 

Total maximum current in device 

40A per block 

Connection type 

Screw terminal block 

Recommended cable section 

0.5mm² to 4mm² (26-10 AWG) 

Maximum response time 

50ms  

Lifetime 

Mechanical (min) 

3 million cycles (60cpm) 

Electrical (min.) 

100.000 cycles at max. current (6cpm and resistive load) 

 

WIRING AND ASSEMBLY DIAGRAMS 

Figure 2. 

Wiring examples (from left to right):

 

individual outputs in channel A with the same and different phases, channel A as 

shutter channel, and channel A and B as fan coil controller (2 pipe and three-speed fan).

 

  In  order  to  ensure  the 

expected  status  of  the  relays, 
please check that the device is 
connected  to  the  KNX  bus 
before  energizing  the  power 
circuit.

 