MAXinBOX 24 

 

Multifunction actuator with 24 (16A) outputs 
ZIO-MB24 

Technical Documentation

 

 

 
FEATURES

 

 

  6 configurable blocks: 

o

 

Shutter channels (up to 12). 

o

 

Individual outputs (up to 24). 

o

 

2-pipe fan coil control (up to 6 fan coils). 

  Manual output operation with push button and LED status indicator. 

  Suitable for capacitive loads, maximum 

140

 

μF

  Possibility of connecting different phases in adjoining outputs. 

  30 logic functions. 

  Total data saving on KNX bus failure. 

  Integrated KNX BCU. 

  Dimensions 69 x 96 x 210mm (12 DIN units). 

  DIN rail mounting (EN 50022), through pressure. 

 

Conformity with the CE directives (CE-mark on the right side).

 

 

 

Programming/test button

: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it  enters the safe 

mode.

 

If this button is held for more than 3 seconds, the device enters the test mode. 

 

Programming/Test  LED: 

programming  mode  indicator  (red). When  the  device  enters  the  safe  mode,  it  blinks  (red)  every  half  second.  The  manual 

mode is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it starts a blue blinking 
sequence.

 

1

. Output 

2

. Output status LED

 

3

. Output control button

 

4

. Fixing clamp  

5

. Programming/Test button 

6

. Programming/Test LED

 

7

. KNX connector 

 

Figure 1. 

MAXinBOX 24

 

 

GENERAL SPECIFICATIONS 

CONCEPT 

DESCRIPTION 

Type of device 

Electric operation control device 

KNX 
supply 

Voltage (typical) 

29VDC SELV 

Voltage range 

21…31VDC 

Maximum 
consumption 

Voltage 

mA 

mW 

29VDC (typical) 

3.92 

113.68 

24VDC

(1)

 

10 

240 

Connection type 

Typical bus connector TP1 for 0.80mm Ø rigid cable  

External power supply 

Not required 

Operation temperature 

0ºC to +45ºC 

Storage temperature 

-20ºC to +55ºC 

Operation humidity 

5 to 95% RH (no condensation) 

Storage humidity 

5 to 95% RH (no condensation) 

Complementary characteristics 

Class B 

Protection class 

II 

Operation type 

Continuous operation 

Device action type 

Type 1 

Electrical stress period 

Long 

Degree of protection 

IP20, clean environment 

Installation 

Independent device to be mounted inside electrical panels with DIN rail (EN 50022) 

Minimum clearances 

Not required 

Response on KNX bus failure  

Data saving according to parameterization 

Response on KNX bus restart 

Data recovery according to parameterization 

Operation indicator 

The  programming  LED  indicates  programming  mode  (red)  and  test  mode  (green). 
Each output LED indicates its status (green) 

Weight 

700g 

PCB CTI index 

175V 

Housing material 

PC FR V0 halogen free 

(1)

 Maximum consumption in the worst case scenario (KNX Fan-In model)

 

 