Zennio KNX ZRX-KCI4S0 Technical Documentation Download Page 2

© Zennio Avance y Tecnología S.L. 

Edition 6 

Further information 

www.zennio.com

 

Page 2/2 

  
 
 
 
 
 
 
 
 
 
 
 

 

SAFETY INSTRUCTIONS AND ADDITIONAL NOTES 

 Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country. 

 Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for th e entire 

KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other 
accessories, in case of being installed. 

 Once the device is installed (in the panel or box), it must not be accessible from outside. 

 Keep the device away from water (condensation over the device included) and do not cover it with clothes, paper or any other material 

while in use. 

 The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructi ons at 

https://www.zennio.com/en/legal/weee-regulation. 

INPUTS SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of S0 or dry 
inputs 

Inputs per common 

Operation voltage 

6 VDC 

Connection method 

Screw terminal block (0.4 Nm max.) 

Cable cross-section 

0.5-2.5 mm²  (IEC)  /  26-12 AWG 
(UL) 

Maximum cable length 

30 m 

Minimum pulse duration 

30 ms 

 

 

WIRING DIAGRAMS 

Figure 2: Example of connections with SO pulse generators 

Attaching KCI 4 S0 to DIN rail: 

Removing KCI 4 S0 from DIN rail:

 

BATTERIES REPLACEMENT 

1.

Extract the battery holder from the upper side of KCI. It is recommended to have the bus KNX connected during this 
process to prevent S0 pulses loss. 

2.

Place the batteries in the battery holder (respecting the polarity shown) and insert it as indicated in the figure. 

2

 

1

 

Figure 3: Mounting KCI 4 S0 on DIN rail 

Reviews: