© Zennio Avance y Tecnología S.L.
Edition 6
Further information
Page 1/2
KCI 4 S0
KNX Consumption Interface
ZRX-KCI4S0
TECHNICAL DOCUMENTATION
FEATURES
•
4 channels for consumption counters (meters) with S0-pulse outputs
(UNE-EN 62053-31)*
•
Registration of consumed electric power, cost and CO2 emissions that
can be split in up to 4 time intervals
•
Compliant with UNE-EN 62053-31 Class B
•
Total data saving on KNX bus failure
•
Integrated KNX BCU (TP1-256)
•
Size 67 x 90 x 36 mm (2 DIN units)
•
DIN rail mounting according to IEC 60715 TH35, with fixing clamp
•
CE, UKCA, RCM directives compliant (marks on the right side)
*Other counters (meters) with dry-voltage output or not complying S0 standard
may also work (previous test is recommended)
1. Battery holder
2. EMPTY batt. LED indicator
3. LOW batt. LED indicator
4. Programming button
5. Programming LED
6. Input Indicator LED
7. Input connectors
8. KNX connector
9. Fixing clamp
Figure 1: KCI 4 S0
Programming button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe mode.
Programming LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. During the start-up
(reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash.
LOW batt. LED: if this LED is blinking in red, replace the batteries as soon as possible.
EMPTY batt. LED: if this LED is blinking in red, the batteries are empty.
GENERAL SPECIFICATIONS
CONCEPT
DESCRIPTION
Type of device
Electric operation control device
KNX supply
Voltage (typical)
29 VDC SELV
Voltage range
21-31 VDC
Maximum
consumption
Voltage
mA
mW
29 VDC (typical)
12.5
363
24 VDC¹
15
360
Connection type
Typical TP1 bus connector for 0.8 mm Ø rigid cable
External power supply
2 CR2032 battery (2 x 3 V). It allows to keep counting pulses without the
KNX bus power supply
Operation temperature
0 .. +55 °C
Storage temperature
-20 .. +55 °C
Operation humidity
5 .. 95%
Storage humidity
5 .. 95%
Complementary characteristics
Class B
Protection class
III
Operation type
Continuous operation
Device action type
Type 1
Electrical stress period
Long
Degree of protection
IP20, clean environment
Installation
Independent device to be mounted inside electrical panels with DIN rail (IEC
60715)
Minimum clearances
Not required
Response on KNX bus failure
Data saving according to parameterization
Response on KNX bus restart
Data recovery according to parameterization
Operation indicator
Programming LED indicates programming mode (red) or safe mode
(blinking red). LOW and EMPTY batt. LED indicate the battery level when
blinking in red (KNX supply necessary). LED input indicator blinks when a
pulse is received.
Weight
89 g (+ 6 g bat.)
PCB CTI index
175 V
Housing material
PC FR V0 halogen free
¹ Maximum consumption in the worst-case scenario (KNX Fan-In model).