KLIC-FJ
Technical Support:
28
communicating with the A/C unit), KLIC-FJ is not able to establish
communication for more than 2 and a half minutes.
For example, if 2 controllers are configured, but only KLIC-FJ is connected
(slaver), due to there is no master remote wired controller in the installation,
the error will be enabled.
Note
:
If communication error is enabled, error control will not be enabled.
Errors in the A/C unit
: errors reported by the A/C unit itself. KLIC-FJ can
notify the KNX bus about the reported error code, although referring to the
specific documentation of the A/C machine is advisable in order to obtain
further information.
Notes
:
➢
Once indoor unit is configured, if it does not locate any of the controllers,
error 0012 will be notified.
➢
If KLIC-FJ is configured as master (by selecting only 1 controller) and
there is a master remote wired controller installed, even though no errors
are reported, the unit will not response to any KLIC-FJ or remote wire
control orders.
ETS PARAMETRISATION
The error handling function does not entail any parameter configuration. The following
objects are available by default:
Internal error objects:
➢
“
[AC] Internal Error: Communication
”: 1-Bit object which indicates that
during 2 minutes no response of the A/C unit is received.
➢
“
[AC] Internal Error: Control
”: 1-Bit object which indicates that the
configured master-slave control in KLIC-FJ is not appropriate.
In case any of the above errors is detected, the corresponding object will be
sent periodically (with a value of “1”) to the KNX bus. Once the error is over, it
the object will be sent (once) with a value of “0”.