Individual object for automatic mode:
enables the “
[AC] Fan: Automatic
”
and “
[AC] Fan: Automatic (Status)
” one-bit objects, which will let
activating/deactivating the automatic mode or reading the current status,
respectively
.
Moreover, the polarity can be configured by parameter:
Automatic Mode Object Polarity
: sets the polarity of the above objects:
“0 = Automatic On; 1 = Automatic Off” or “0 = Automatic Off; 1 = Automatic
On
”.
Figure 8.
AC Gateway. Configuration. Fan.
If individual object for automatic mode is enabled, the behaviour is as follows:
When activating automatic mode, fan percentage status will be 0%.
When deactivating automatic mode, fan level 1 is set.
Notes
:
In automatic mode, effective fan speed it is not possible to know the effective
fan speed, so, when activated, fan speed status will stay with 0% value.
In dry mode, A/C unit sets fan speed in automatic mode. Due to this fact the
fan speed control orders will be ignored during this mode.
TEMPERATURE SETPOINT
The following objects to control and supervise setpoint temperature will be available by
default:
“[AC] Temperature Setpoint”:
2-Byte object that allow selecting decimal
temperature values that belong to the range [10º-32º].