KLIC-DD
Technical Support:
23
➢
5 levels:
The fan speed percentages will be interpolated as shown in Table
Initial Speed
Percentage
Interpolated Speed
Percentage
Level
0%
0%
Auto
1-20%
20%
Minimum
21-40%
40%
Minimum-
Medium
41-60%
60%
Medium
61-80%
80%
Medium-
Maximum
81-100%
100%
Maximum
Table 3.
Fan speed percentages for 5 levels.
Step control:
the selection of this option ("Yes") enables the 1-bit object "Fan
[1 bit] Sending" that allows increasing (sending the value "1") or decreasing
(value "0") the fan speed in one level (for example, for 3 levels, in the minimum
level of fan speed, the value "1" is sent via the object "Fan [1 bit] Sending", the
fan speed level will go to medium).
The step control is
not cyclical
. This means that, being in the Auto level (0%),
when decreasing the fan speed level, the A/C machine will stay in the auto
mode until the speed level is increased. The same way, when the speed level
is in the maximum level (100%), the machine will remain in this level until
receiving an order to decrease the speed.