background image

 

 

 

KLIC-DA LT

 

http://www.zennio.com

 

Technical Support:

 

http://zennioenglish.zendesk.com 

 

12 

 

Additional Information (Status)

, which enables or disables the 

supervision of a set of indicators related to the power 
consumption/production and to the water flow. See section  3.1.1.6. 

Depending on the Altherma LT system being interfaced, the checkboxes of the 
required functions  need to be marked. This will make some communication objects 
visible, as described in the following sections of this user manual.  

One more parameter should be configured: 

Send Status Objects on Bus Voltage 

Recovery?

, which may be set to one of the following: 

 

No

 (default): no objects will be sent to the KNX bus during the device start-up 

after a bus power failure or a download from ETS.  

 

Yes

: the following objects will be sent to the KNX bus (to update other KNX 

devices) when the device starts up after a bus power failure  or a download 
from ETS: 

  [DHW] On/Off (Status)  

  [DHW] Booster mode On/Off (Status) 

  [DHW] Temperature (Status) 

  [DHW] Operating (Status) 

  [Climate] On/Off (Status)  

  [Climate] Operation mode (Status)  

  [Climate] Temperature (Status) 

  [Climate] Operating (Status) 

  [Temperatures] DHW tank 

  [Temperatures] Outdoor Temperature 

  [Temperatures] Leaving water 

  [Temperatures] Leaving water (PHE) 

  [Temperatures] Inlet water 

  [Temperatures] Refrigerant 

  [Actuators] Pump 

  [Actuators] Compressor 

  [Actuators] BUH: step 1 

  [Actuators] BUH: step 2 

  [Addit. Info.] Flow rate 

  [Addit. Info.] Electrical energy consumpt. 

  [Addit. Info.] Energy production 

It is possible to apply a certain delay (0 to 255 seconds) to the above sending 
once the device start-up is over. Therefore, a new parameter called 

Sending 

Delay

 will show if the above is set to “Yes”. 

Regarding the

 start-up of the device

, it is advisable to read section   2.1, as it contains 

details on how the interaction between KLIC-DA LT and the Altherma LT system starts.

 

 

Summary of Contents for KLIC-DA LT

Page 1: ...KLIC DA LT KNX DAIKIN Altherma LT Gateway ZN1CL KLIC DA U SER MANUAL Application Program Version 1 0 User Manual Version 1 0 _a www zennio com...

Page 2: ...Management DHW 7 2 2 Climate control management 7 2 3 Error Handling 7 2 4 Additional Indicators 8 2 5 Start up 8 3 ETS Parameterisation 10 3 1 Default Configuration 10 3 1 1 Configuration 11 3 1 1 1...

Page 3: ...m the specific Altherma user interfaces Moreover any status updates and feedback received from the Altherma system will also be forwarded by KLIC DA towards other KNX devices Figure 1 KLIC DA Daikin A...

Page 4: ...erface too KLIC DA is meant to replace the aforementioned additional interface and thus to communicate only to the main interface and not to the Altherma LT system directly The main functions performe...

Page 5: ...ning elements is as follows Programming Button 3 a short press on this button will set the device into the programming mode making the red component of the LED 2 indicator light up If the button is he...

Page 6: ...em disconnected the effective colour will be orange still as the red and green components will be lighting still Input Terminal for the Two Wire Communication Cable 4 slot for the connection of the tw...

Page 7: ...unction The ON OFF state of the Buster mode The setpoint temperature of the DHW tank It can also report whether the DHW tank is currently under operation or not 2 2 CLIMATE CONTROL MANAGEMENT In relat...

Page 8: ...ay initialise at a different moment than the main control so it is advisable to restart the Altherma system after installing KLIC DA and downloading the application Notwithstanding the above in order...

Page 9: ...after the initial sequence according to them The above sequence occurs whenever KLIC DA powers up or detects communication errors with the P1 P2 bus It also takes place when the Altherma system itself...

Page 10: ...to start the configuration In the following sections a detailed explanation is provided about how to parameterise the different functionalities of the device in ETS 3 1 DEFAULT CONFIGURATION This sec...

Page 11: ...ables or disables the room climate function See section 3 1 1 2 Error Handling which enables or disables the error monitoring function See section 3 1 1 3 Advanced While all of the above will still re...

Page 12: ...update other KNX devices when the device starts up after a bus power failure or a download from ETS DHW On Off Status DHW Booster mode On Off Status DHW Temperature Status DHW Operating Status Climate...

Page 13: ...maximum temperature set in the main user interface KLIC DA LT will truncate it and send the Altherma LT system the maximum permitted setpoint On the other hand in case the value is under the minimum p...

Page 14: ...imate system Climate Temperature two byte object that sets the desired setpoint temperature for the climate system In case the value received through this object exceeds the allowed setpoint range the...

Page 15: ...munication error and will then require that the Altherma LT system is switched off prior to removing the unneeded additional control Once removed the Altherma LT system can be switched back on KLIC DA...

Page 16: ...ver the Altherma LT system notifies a temperature change KLIC DA LT will automatically send the corresponding object to the KNX bus 3 1 1 5 ACTUATORS STATUS No additional parameter configuration is re...

Page 17: ...d by the Altherma LT system Addit Info Energy Production four byte object that reflects the total energy production in kWh till now as reported by the Altherma LT system Addit Info Flow Rate two byte...

Page 18: ...to the bus write or read requests after a bus failure the marks W or R will be shown respectively for transmissions or read requests No Size I O Flags Data Type DPT Functional Range 1st boot P Reboot...

Page 19: ...60 0 W W Temperatures Refrigerant Current Refrigerant Temperature 22 1 Bit O C T R DPT_Switch 0 1 W W Actuators Pump Status of Pump On Off 23 1 Bit O C T R DPT_Switch 0 1 W W Actuators Compressor Stat...

Page 20: ...your inquiries about Zennio devices http zennioenglish zendesk com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 Fax 34 925 337 310 www zennio com...

Reviews: