© Zennio Avance y Tecnología S.L.
Edition 1
Further information
Page 2/4
GENERAL SPECIFICATIONS
CONCEPT
DESCRIPTION
Type of device
Electric operation control device
External
power supply
Voltage
110-240VAC 50/60Hz
Maximum consumption
250mA@110VAC / 125mA@230VAC
KNX supply
Voltage (typical)
29VDC SELV (with KNX coil)
Maximum rated current (I
BUS
)
320mA
Connection type
Typical TP1 bus connector for 0.80mm Ø rigid cable
Additional
output
Voltage (typical)
29VDC SELV
Maximum rated current (I
AD
)
I
AD
+ I
BUS
≤ 320mA
Operation temperature
-5°C .. +45°C
Storage temperature
-20°C .. +55°C
Operation humidity
5 .. 95%
Storage humidity
5 .. 95%
Complementary characteristics
Class B
Protection class / Overvoltage category
II / III (4000V)
Operation type
Continuous operation
Device action type
Type 1
Electrical stress period
Long
Degree of protection / Pollution degree
IP20 / 2 (clean environment)
Installation
Independent device to be mounted inside electrical panels with DIN rail (EN
50022)
Minimum clearances
Not required
Power failure back-up time
110ms
Maximum current before overload notification
500mA
Response on KNX bus failure
Data saving according to parameterization
Response on KNX bus restart
Data recovery according to parameterization
Operation indicator
See page 1
Weight
521g
PCB CTI index
175V
Housing material / Ball pressure test temperature
PC FR V0 halogen free / 75ºC (housing) - 125ºC (connectors)
MAIN POWER SUPPLY SPECIFICATIONS AND CONNECTIONS
CONCEPT
DESCRIPTION
Power supply protection
fuse
Voltage
110-240VAC 50/60Hz
Current
6.3A
Response type
F (Fast acting)
Connection method
Screw terminal block
Cable cross-section
1.5-4mm² (IEC) / 26-10AWG (UL)
AUXILIARY POWER OUTPUT SPECIFICATIONS AND CONNECTIONS
CONCEPT
DESCRIPTION
Connection method
Screw terminal block
Cable cross-section
1.5-4mm² (IEC) / 26-10AWG (UL)
OUTPUTS SPECIFICATIONS AND CONNECTIONS
CONCEPT
DESCRIPTION
Number of outputs
8
Output type / Disconnection type
Potential-free outputs through bistable relays with tungsten pre-contact /
Micro-disconnection
Rated current per output
AC 16(6)A @ 250VAC (4000VA)
DC 7A @ 30VDC (210W)
Maximum load per output
Resistive
4000W
Inductive
1500VA
Maximum inrush current
800A/200μs
165A/20ms
Different phases connection
Possibility of connecting different phases. It is not allowed to connect power
supplies of different order, SELV with NO SELV, in the same block
Maximum current per block
40A
Maximum current per channel
16A
Short-circuit protection
NO
Overload protection
NO
Over-voltage protection
NO
Connection method
Screw terminal block
Cable cross-section
0.5-2.5mm² (IEC) / 26-12AWG (UL)
Outputs per common
2
Maximum response time
10ms
Mechanical lifetime (min. cycles)
3 000 000
Electrical lifetime (min. cycles)
1
100000 @ 8A / 25000 @ 16A (VAC)
¹ Lifetime values could change depending on the load type.