background image

© Zennio Avance y Tecnología S.L. 

Edition 1 

Further information 

www.zennio.com

 

Page 2/4 

 

 

 

GENERAL SPECIFICATIONS 

CONCEPT 

DESCRIPTION 

Type of device 

Electric operation control device 

External 
power supply 

Voltage 

110-240VAC 50/60Hz 

Maximum consumption 

250mA@110VAC / 125mA@230VAC 

KNX supply 

Voltage (typical) 

29VDC SELV (with KNX coil) 

Maximum rated current (I

BUS

320mA 

Connection type 

Typical TP1 bus connector  for 0.80mm Ø rigid cable 

Additional 
output 

Voltage (typical) 

29VDC SELV 

Maximum rated current (I

AD

I

AD

 + I

BUS

 

≤ 320mA 

Operation temperature 

-5°C .. +45°C 

Storage temperature 

-20°C .. +55°C 

Operation humidity 

5 .. 95% 

Storage humidity 

5 .. 95% 

Complementary characteristics 

Class B 

Protection class / Overvoltage category 

II / III (4000V) 

Operation type 

Continuous operation 

Device action type 

Type 1 

Electrical stress period 

Long 

Degree of protection / Pollution degree 

IP20 / 2 (clean environment) 

Installation 

Independent device to be mounted inside electrical panels with DIN rail (EN 
50022) 

Minimum clearances 

Not required 

Power failure back-up time 

110ms 

Maximum current before overload notification 

500mA 

Response on KNX bus failure 

Data saving according to parameterization 

Response on KNX bus restart 

Data recovery according to parameterization 

Operation indicator 

See page 1 

Weight 

521g 

PCB CTI index 

175V 

Housing material / Ball pressure test temperature 

PC FR V0 halogen free / 75ºC (housing) - 125ºC (connectors) 

 

 

MAIN POWER SUPPLY SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Power supply protection 
fuse 

Voltage 

110-240VAC 50/60Hz 

Current 

6.3A 

Response type 

F (Fast acting) 

Connection method 

Screw terminal block 

Cable cross-section 

1.5-4mm² (IEC) / 26-10AWG (UL) 

 

AUXILIARY POWER OUTPUT SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Connection method 

Screw terminal block 

Cable cross-section 

1.5-4mm² (IEC) / 26-10AWG (UL) 

 

OUTPUTS SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of outputs 

Output type / Disconnection type 

Potential-free  outputs  through  bistable  relays  with  tungsten  pre-contact  / 
Micro-disconnection 

Rated current per output 

AC 16(6)A @ 250VAC (4000VA) 
DC 7A @ 30VDC (210W) 

Maximum load per output 

Resistive 

4000W 

Inductive 

1500VA 

Maximum inrush current 

800A/200μs 
165A/20ms 

Different phases connection  

Possibility of connecting different phases. It is not allowed to connect power 
supplies of different order, SELV with NO SELV, in the same block  

Maximum current per block 

40A 

Maximum current per channel 

16A 

Short-circuit protection 

NO 

Overload protection 

NO 

Over-voltage protection 

NO 

Connection method 

Screw terminal block 

Cable cross-section 

0.5-2.5mm² (IEC) / 26-12AWG (UL) 

Outputs per common 

Maximum response time 

10ms 

Mechanical lifetime (min. cycles) 

3 000 000 

Electrical lifetime (min. cycles)

100000 @ 8A / 25000 @ 16A (VAC) 

¹ Lifetime values could change depending on the load type. 

 

Reviews: