Status Displays 
 
The status messages display the operational status of the meter in an easily under-
standable manner (see table below).  

 
Note : 

 
The status messages in the table below only appear in the main display (en-
ergy)!  
 
In all cases, in which the warning triangle represents a status message, you 
should check first whether the problem is permanent or occurs only temporar-
ily.
 
 
If the symbol appears permanently, a service company should be called! 
 
A few displays can be conditional upon the system and do not necessarily mean that 
the meter is defect. The warning display disappears after a short period when the 
system is operating properly. 
 
 
 

 

Technical Data 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

* HC = heat computer 
** VMU = volumetric measuring unit 

Symbol 

Status 

Display 

Event / Reaction 

 

Flow existent 

 

System is operating. 

 

Indicator for a possible 

defect! 

Always on 

If warning triangle appears 

permanently, please notify a 

service company. 

 

Data transfer on the 

interface 

Only on when 

data is being 

transmitted 

 

.and..

 

Emergency operation! 

Always on 

Energy is still being displayed 
and calculated correctly. All 
other displays however, are 
blocked and the button also 
no longer reacts. 

Notify service company 

 

 

 

Type 

 

zelsius 

 

Temperature range HC* 

°C 

1 ...130 

Temperature range VMU** 

°C 

15 ... 90 

Temperature difference 
range 

Kelvin 3 

...100 

Type of temperature sensor 

 

Pt 500 

Temperature range sensor 

°C 

0 ... 130 (Silicon) 

Dimensions sensor 

mm 

5,0 / 5,2 (cable 1,5 m) 

Nominal flow rate 

Qp         m³/h 

0,6 

1,5 

2,5 

Nominal diameter 

DN         mm 

15 

15 

20 

Highest flow rate 

Qs        m³/h 

1,2 

3,0 

5,0 

Transitional flow rate Qt 

(Class A)

 

l/h 120 

150 

250 

Minimum flow Qmin 

(Class A)

l/h 24 

60 

100 

Nominal pressure 

bar 

16 

Media temperature VMU 

Tmax    °C 

90 

Pressure loss at Qp 

bar 

 0,25 

Starting flow rate typical 

 

 

Horizontal ca. 

l/h 

Display range LC-Display 

 

8 positions, 3 after comma 

Battery V 

3,0 

(Lithium) 

Battery life 

years 

 6 

Protection class 

 

IP 54 

Ambient temperature 

°C 

0 ...55 

Weight measuring capsule 

ca. 680 

 

 

 

Connecting thread capsule 

inch 

G 2 B 