EN - 27
10. Press OK to confirm. A second
number next to the chosen number is
blinking.
11. Press
or
to choose the sub
parameter menu number.
12. Press OK to confirm.
■
When the first chosen parameter
number is an 8: A third number
next to the chosen numbers is
blinking.
■
Else: The parameter value
appears. Skip to step 15.
13. Press
or
to choose the final
sub parameter menu number.
14. Press OK to confirm. The parameter
value appears.
15. When the appeared value is blinking,
press
or
to change the
parameter value.
Only a parameter value that is
blinking can be changed.
16. Press OK to confirm. The text says
SAVED for 2 seconds. The main
parameter menu number is blinking.
17. Press OK to confirm. The text says
SAVED.
18. Press MENU to return to the main
menu.
The password (14) will stay
active for approximately 5 more
minutes.
Or go back to step 9 to set
another program.
List of specific ComfoSense parameters (Not present in the ventilation unit)
P#
min
max
Default Description
890
0
23
8
Default start time of new week program.
891
0
23
17
Default end time of new week program.
892
0
4
2
Default speed level:
■
0 = away;
■
1 = low;
■
2 = medium;
■
3 = high;
■
4 = sensor*.
893
0
1
1
■
RF enabled (1)
■
RF disabled (0).
894
0
1
1
■
Clock visible in Default Screen (1)
■
Clock not visible Default Screen (0).
895
0
1
1
■
Night cooling symbol visible in Default Screen (1)
■
Night cooling symbol not visible in Default Screen (0).
896
0
1
0
■
Degrees in Fahrenheit** (1)
■
Degrees in Celsius (0).
897
0
255
-
Software version (read only value)
898
1
5
-
Quality RF reach
■
1 = bad;
■
5 = good.
899
0
1
0
Reset ventilation program (PROG)
* Only available if the mentioned function is connected.
** Shown temperature in °F will be changed in steps of 2 degrees.
The complete list of parameters can be found in the manual of the
ventilation unit.