18 - EN
EN - 19
Object
Description
Type2
Room temperature1
Reflects the room temperature sensor which is connected to the ventilation unit (if available)
5.001
9.001
9.002
9.027
Extract temperature1
Reflects the extract air sensor of the ventilation unit (SENSOR_ETA).
Exhaust temperature1
Reflects the exhaust air sensor of the ventilation unit. (SENSOR_EHA)
Outdoor temperature1
Reflects the outdoor air sensor of the ventilation unit.( SENSOR_ODA)
Supply temperature1
Reflects the supply air sensor of the ventilation unit. (SENSOR_SUP)
Room humidity1
Reflects the room humidity sensor which is connected to the ventilation unit (if available)
5.001
5.004
9.007
Extract humidity1
Reflects the extract air sensor of the ventilation unit (HUMID_ETA).
Exhaust humidity1
Reflects the exhaust air sensor of the ventilation unit. (HUMID_EHA)
Outdoor humidity1
Reflects the outdoor air sensor of the ventilation unit.( HUMID_ODA)
Supply humidity1
Reflects the supply air sensor of the ventilation unit. (HUMID_SUP)
CO2 sensor bedroom (up to
8 rooms)
External CO2 sensor input.
This object has to be connected to a KNX sensor that is mounted in a bedroom. Depending on
the measured CO2 level, the ComfoConnect KNX C forces the ventilation unit to run at a minimum
ventilation preset.
�
< 800 ppm: set to ventilation preset 1 at least;
�
≥ 800 ppm: set to ventilation preset 2 at least.
9.008
CO2 sensor bedroom (set)
(up to 8 rooms)
CO2 sensor room
(up to 8 rooms)
External CO2 sensor input.
This object has to be connected to a KNX sensor that is mounted in another room other than a
bedroom. Depending on the measured CO2 level, the ComfoConnect KNX C forces the ventilation
unit to run at a minimum ventilation preset.
�
< 800 ppm: set to ventilation preset 1 at least;
�
≥ 800 and < 1200 ppm: set to ventilation preset 2 at least;
�
≥ 1200 ppm: set to ventilation preset 3 at least.
CO2 sensor room (set)
(up to 8 rooms)
Humidity sensor bathroom
(up to 8 rooms)
External humidity sensor input.
This object has to be connected to a KNX sensor that is mounted in a bathroom. Depending on the
measured humidity level, the ComfoConnect KNX C forces the ventilation unit to run at a minimum
ventilation preset.
�
< 35%: set to ventilation preset 1 at least;
�
≥ 35%: set to ventilation preset 2 at least.
5.001
5.004
9.007
Humidity sensor bathroom
(set)
(up to 8 rooms)
Error1
�
False: all systems are operational;
�
True: the ventilation unit reported an error. Manual inspection and/or intervention is required.
Check the error that is indicated on the display of the ventilation unit.
1.002
Filter replace1
Hours till the ventilation units filter needs replacement.
7.007
Filter dirty1
�
False: the ventilation units filters do not need replacing at this moment;
�
True: the ventilation units filters need replacing.
1.002
State
State/error of the unit:
�
0: a connection with the ventilation unit has been established, no error;
�
30: another unit is detected; this unit is not connected to the ventilation unit;
�
40: incompatible ventilation unit version detected; cannot connect to the ventilation unit;
�
50: no ventilation unit detected.
For safety, when the state of the unit has any other value than 0, the Error object is set to True and
Standby is set to On.
5.001
1 Refer to the manual of the ventilation unit for a description of this functionality.
2 When multiple types are indicated, the actual type can be configured by a parameter. See chapter ‘Parameters’