30 - EN
EN - 31
2 or 3 months after installation:
Activity
Y8
Y9
Y10
Y11
Y12
Y13
Y14
Check (flat)filter (pressure drop, damage and seal).
6 months after installation:
Activity
Y8
Y9
Y10
Y11
Y12
Y13
Y14
Check (flat)filter (pressure drop, damage and seal).
Check the outdoor plating of the outdoor assembly
(soiling and damage).
Check the draught excluders (splitting).
Check the servo motors of the valves (functioning).
9 months after installation:
Activity
Y8
Y9
Y10
Y11
Y12
Y13
Y14
Check (flat)filter (pressure drop, damage and seal).
12 months after installation:
Activity
Y8
Y9
Y10
Y11
Y12
Y13
Y14
Check (flat)filter (pressure drop, damage and seal).
Check the draught excluders (splitting).
Check the servo motors of the valves (functioning).
Check the fans (soiling and fixing vibration dampers).
Check the casing (soiling and damage).
Check the hinges/clamps (operation).
Check the valves (seals and bearings).
Check the battery or batteries (soiling and leakage).
Check the thermostat of the hot water battery
(functioning, soiling and leakage).
Check the leakage trays (soiling and functioning).
Check the drip collectors (soiling and functioning).
Check the plate exchanger (soiling).
Summary of Contents for ComfoAir XL Series
Page 17: ...NL 17 Datum Activiteit Paraaf...
Page 32: ...32 EN Date Activity Initials...
Page 48: ...48 DE Datum Aktivit t Unterschrift...
Page 64: ...64 FR Date Activit Paraphe...
Page 80: ...80 IT Data Attivita Sigla...
Page 96: ...96 PL Data Czynno Podpis...
Page 97: ......
Page 98: ......
Page 99: ......