11 - EN
11 - EN
Time delay values
Sub-menu
Description
Minimum
Maxi-
mum
General
Reset
P26
Note:
Only applies to systems fi t-
ted with an RF switch.
Overrun timer for ventilation setting 3 " using
".
•
After pressing "
"
CONTINUOUSLY
(> 2
sec.), the ComfoAir will switch to the
HIGH
setting for ‘x’ minutes and then automati-
cally returns to the
NORMAL
setting.
If any 3-position switch is operated during
this lagging time the ComfoAir will instantly
revert to the ventilation position as set at
that time.
1 Min.
120 Min. 30 Min.
P27
N/A
0 Min.
120 Min. 30 Min.
Menu P9
Status of programmes (from menu P5 and P6 additional programmes)
Status
Sub-menu
Description
Activated
P90
Open fi re programme active?
Yes (1) / No (0)
P91
Bypass Open?
Yes (1) / No (0)
P94
Analogue input (0-10V) active?
Yes (1) / No (0)
P95
Frost protection or Preheater active?
Yes (1) / No (0)
P97
Enthalpy programme active?
Yes (1) / No (0)
2.7.3 P menus for the installer
Menus with a line at minimum and maximum value are Reading menus.
Menu P3
Setting ventilation programmes
Ventilation programme values
Submenu
Description
Minimum
Maximum
General
Reset
P30
N/A
0% or 15%
97%
nL / HL
15% / 15%
P31
Setting the capacity (in %) of the
exhaust fan in
LOW
POSITION
.
16%
98%
nL / HL
35% / 40%
P32
Setting the capacity (in %) of the
exhaust fan in
MEDIUM
POSITION
.
17%
99%
nL / HL
50% / 70%
P33
Setting the capacity (in %) of the
exhaust fan to
HIGH
POSITION
.
18%
100%
nL / HL
70% / 90%
P34
N/A
0% or 15%
97%
nL / HL
15% / 15%
P35
Setting the capacity (in %) of the
supply fan in
LOW
POSITION
.
16%
98%
nL / HL
35% / 40%
P36
Setting the capacity (in %) of the
supply fan in
MEDIUM
POSITION
.
17%
99%
nL / HL
50% / 70%
P37
Setting the capacity (in %) of the
supply fan in
HIGH
POSITION
.
18%
100%
nL / HL
70% / 90%
P38
Current capacity (in %) of the
exhaust fan.
-
-
Current %
P39
Current capacity (in %) of the
supply fan.
-
-
Current %