2
7
For the user
Time delay values
Sub-menu
Description
Mini-
mum
Maxi-
mum
Default
P25
Note:
Only applies to systems
fi
t-
ted with an RF switch.
Overrun timer for ventilation setting
3 (using "
").
•
After pressing "
" BRIEFLY (<
2 sec.), the ComfoAir runs at the
HIGH setting for ‘x’ minutes and
then automatically returns to the
programmed setting.
1 Min.
20 Min.
10 Min.
P26
Note:
Only applies to systems
fi
t-
ted with an RF switch.
Overrun timer for ventilation setting
3 "
".
•
After pressing "
" for LONGER
(> 2 sec.), the ComfoAir runs at
the HIGH setting for ‘x’ minutes
and then automatically returns to
the programmed setting.
1 Min.
120 Min.
30 Min.
P27
n/a
0 Min.
120 Min.
30 Min.
Menu P9
Status of programmes (from menu P5)
Ventilation programmes
Sub-menu
Description
Activated
P90
Open fi re programme active?
Yes (1) / No (0)
P91
Bypass Open (=Yes) / Closed (=No)?
Yes (1) / No (0)
P94
0 – 10 V programme active?
Yes (1) / No (0)
P95
Frost protection active?
Yes (1) / No (0)
P97
Enthalpy programme active?
Yes (1) / No (0)