2.2 P-menus for the installer
Menus without a value at minimum and maximum are Reading menus.
Menu P3 > Setting ventilation programmes
Ventilation programme values
Submenu
Description
Minimum
Maximum
General Reset
P30
Setting the capacity (in %) of the exhaust fan in
ABSENT
POSITION
.
0% or 15%
97%
nL / HL
15% / 15%
P31
Setting the capacity (in %) of the exhaust fan in
LOW
POSITION
.
16%
98%
nL / HL
35% / 40%
P32
Setting the capacity (in %) of the exhaust fan in
MEDIUM
POSITION
.
17%
99%
nL / HL
50% / 70%
P33
Setting the capacity (in %) of the exhaust fan to
HIGH
POSITION
.
18%
100%
nL / HL
70% / 90%
P34
Setting the capacity (in %) of the supply fan to
ABSENT
POSITION
.
0% or 15%
97%
nL / HL
15% / 15%
P35
Setting the capacity (in %) of the supply fan in
LOW
POSITION
.
16%
98%
nL / HL
35% / 40%
P36
Setting the capacity (in %) of the supply fan in
MEDIUM
POSITION
.
17%
99%
nL / HL
50% / 70%
P37
Setting the capacity (in %) of the supply fan in
HIGH
POSITION
.
18%
100%
nL / HL
70% / 90%
P38
Current capacity (in %) of the exhaust fan.
-
-
Current %
P39
Current capacity (in %) of the supply fan.
-
-
Current %
Menu P4 > Reading the temperatures
Temperature values
Submenu
Description
Minimum
Maximum
General Reset
P41
Comfort temperature
12 ºC
28 ºC
20 ºC
P45
Current value of T1 (= outside air temperature)
-
-
Current ºC
P46
Current value of T2 (= supply air temperature)
-
-
Current ºC
P47
Current value of T3 (= return air temperature)
-
-
Current ºC
P48
Current value of T4 (= exhaust air temperature)
-
-
Current ºC
Menu P5 >Setting additional programmes
Additional programme values
Submenu
Description
Minimum
Maximum
General Reset
P50
Activation of the open fire programme.
0 (= No)
1 (= Yes)
0
P51
Confirming the presence of a pre heater
0 (= No)
1 (= Yes)
0
Only change if a pre heater is installed afterwards or a general reset is given.
P52
Setting the pre heater programme.
■
0; Extreme protection;
■
1; High protection;
■
2; Nominal protection;
■
3; Economy.
0
3
2
In extreme protection mode the pre heater is switched on soonest; this level offers the best guarantee of
balanced ventilation. Vice versa, in economy mode the pre heater switches on at the last possible moment;
balanced ventilation is not guaranteed in this mode.
P54
Confirming the presence of a bypass.
0 (= No)
1 (= Yes)
1
The standard ComfoAir configuration includes a bypass. Therefore, leave the value at ‘1’.
P56
Setting the required air volume in the house.
■
nL: ”normal air volume”;
■
HL: "high air volume".
nL
HL
HL
Setting the air volume is the starting point for programming the air specifications and setting the fans.
P58
n/a
0
1
0