Identification: MD-AL-GI-00
Rev. 1.0 07.06.21 - Application: GID
Connext User Manual
Rev. 1.2 07/06/2021
Figure 19 - RJ45 pinout Connector
2)
Follow the polarity shown in the figure and the pinout in the table.
RJ45 pin
24-pin terminal block
4 (blue cable)
9
5 (white/blue cable)
10
Table 12 – RS485 connections to photovoltaic inverters
4.4.
Connecting to current sensors or meter
The accessory current sensors have the function of measuring (when necessary) the power
produced by the photovoltaic system and the power exchanged with the grid.
Current sensors and meter are needed with other-brand inverters and Azzurro photovoltaic
inverters.
NOTE: IF ON THE SYSTEM THERE IS ONE OF THE FOLLOWING INVERTERS, 1PH HYD3000-
HYD6000-ZSS, 3PH HYD5000-HYD20000-ZSS, 3000SP, REFER TO THE RESPECTIVE MANUALS
FOR THE SENSOR CONNECTION (ZSM-ACC-TA) AND / OR THE METER (DTSU666).
4.4.1.
Sensor for measuring 1-ph photovoltaic production
If at least one photovoltaic inverter does not belong to the Azzurro brand and the photovoltaic
production needs to be measured, it is necessary to install an accessory sensor (ZSM-ACC-TA).
The sensor must be placed directly on the output of the photovoltaic inverter and connected to the
Connext system via pins 21 and 22 of the 24-pin terminal block, as shown below.