Make sure that the AC switch of the inverter
is open and that no voltage is present on the
inverter's terminal block.
OFF
HYD 3-6-HP
GRID
8888
> 500W
Check that the DC circuit breaker of the inverter is in
the OFF position.
Make sure there is a domestic load of at least 500 W by using a current
clamp to measure under the import/export meter.
Current flow
Loads
Import/Export meter
Turn on the batteries:
In case of
WeCo
or
Azzurro
batteries, set the
switch to 1 (if present) press the POWER button of
each battery for 1 second, the RUN LED will turn
on and the internal contact will close
automatically.
To turn on the
Pylontech
batteries:
bring the switch on the
front of
all the batteries
to the ON position.
Press the red SW button of
a single
battery for one
second, the internal
contactor will close
automatically.
12. INITIAL SET UP PROCEDURE
Turn ON the AC circuit breaker located between
the inverter and AC grid.
Hybrid Inverter
GRID
ON
To supply DC voltage to the hybrid inverter, turn
the circuit breaker to the ON position