User Information
2
Safety Output-Extension Module TE- OR3
H10
Ver. A
E61-058-00
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Germany
Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138 •
[email protected] • www.zander-aachen.de
Advice:
Follow the guidelines in
„Electrical Connection“
during the start-up.
Commissioning
Procedure
1. Feedback loop:
If a feedback loop is necessary for the application, it has to
be wired as shown in Fig.1
2. Connecting control line:
Connect the terminal
In
and the terminal
O1
,
O2
or
O3
with
a jumper, depending on which output of the basic module
the TE-OR3 shall react.
Caution:
Wiring only in de-energized state.
Each expansion module may only be connected
to one safety output of the basic device.
Multiple connection is not permitted.
3. Starting the device:
Turning on the safety output of the basic module.
Caution:
The safety contacts will close immediately by turning on the
control line.
The LEDs
K1
and
K2
are lit.
4. Triggering safety function:
Turning off the safety output of the basic module. The
safety contacts will open immediately.
The LEDs
K1
and
K2
go out.
5. Reactivation:
Turning on the safety output of the basic module. The
safety contacts will close immediately.
The LEDs
K1
and
K2
are lit.
The device has to be wired as shown in Fig. 1.
Applications
Fig. 1:
Single channel emergency stop. (category 4, up to PL e
/
SIL 3)
Connecting load to safety contacts.
(Figure shows example. Voltage „+V“ according to technical data)
If a feedback loop is necessary for the application, it can be wired to
the auxiliary contact 41-42 (e.g. like in Fig.1).
Wiring diagram
Caution:
Safety contacts will be activated immediately by switching on the
control line.
Up to 5 extension modules may be connected to each safety output of
the basic module.