Safety Emergency Stop Relay SR3D
E10-2
Ver. B
E61-139-00
Maintenance
The device must be checked once per month for proper
function and for signs of tampering and bypassing of the
safety function. The device is otherwise maintenance free,
provided that it was installed properly.
Techn. Data
In compliance with
EN 60204-1; EN ISO 13849-1; EN 50156-1 ; EN 62061
Operating voltage
AC 230 V, AC 115 V, AC/DC 24 V
Rated supply frequency
50-60 Hz
Allowable tolerance
+ / - 10 %
Power consumption
DC 24 V
AC 230 V
approx. 2 W
approx. 6.9 VA
Control voltage at S11
DC 24 V
Control current at S11...S14
max. 100 mA
Safety contacts
3 NO
Auxiliary contacts
1 NC
Switching voltage max.
AC 250 V
Contact rating of safety contacts (13-14, 23-24, 33-34) *)
AC:
250 V, 2000 VA, 8 A for resistive load,
250 V, 3 A for AC-15
DC: 50 V, 400 W, 8 A for resistive load;
24 V, 3 A for DC-13
Cumulative current
Max. 15 A (13-14, 23-24, 33-34)
Contact rating of auxiliary contact (41-42)
AC: 250 V, 500 VA, 2 A for resistive load
DC: 50 V, 100 W, 2 A for resistive load
Minimum voltage/current
24 V, 20 mA
Min. External fuses for safety contacts
6 A slow-blow or 8 A quick-blow or 10 A gG
Wire width
0.14 - 2.5 mm
2
Length of control lines
Max. 1000m at 0.75 mm
2
Contact material
AgNi, AgSnO
2
Service Life
mech. approx. 1 x 10
7
Rated impulse withstand voltage
2.5 kV (control voltage / contacts)
Dielectric strength
4 kV (DIN VDE 0110-1)
Rated insulation voltage
250 V
Protection
IP20
Temperature range
DC 24 V:
-15 °C bis +55 °C
AC 115 V / 230 V:
-15 °C bis +55 °C
(see load curve)
Degree of pollution
2
(DIN VDE 0110-1)
Overvoltage category
3
(DIN VDE 0110-1)
Weight
approx. 230 g
Mounting
DIN rail according to EN 60715 TH35
Advice:
For other applications than
described, please contact
the manufacturer for further
information.
Safety
Characteristics
according to
EN ISO 13849-1
Device cannot be switched on again after an emergency
stop:
•
Check whether the emergency stop circuit was closed
again.
•
Was the start button opened before closing of the emer-
gency stop circuit (with manual start)?
•
Is the feedback loop closed?
If the fault still exists, perform the steps listed under
“Commissioning Procedure”.
If these steps do not remedy the fault either, return the
device to the manufacturer for examination.
Opening the device is impermissible and will void the
warranty.
Device does not switch on:
•
Check the wiring by comparing it to the wiring diagrams.
•
Check the safety switch used for correct function and
adjustment.
•
Check whether the emergency stop circuit is closed.
•
Check whether the start button (with manual start) is
closed.
•
Check the operating voltage at A1 and A2.
•
Is the feedback loop closed?
What to do in
Case of a Fault?
For furnaces which operate continuously where regular
inspection at sufficient short intervals in accordance to EN
50156-1 may not be performed, are excluded from this.
*) If several SR3D-24V are mounted closely together the maximum cumulative current is 9A at an ambient temperature of 20 °C or 3 A at 30 °C or 1 A at 40 °C.
If the current exceeds these limits, keep a minimum space of 5 mm between the devices.
Safety Emergency Stop Relay SR3D
Load (DC-13; 24 V) per contact
<= 0,1 A
<= 1 A
<= 2 A
Max. lifetime [years]
20
20
20
Category:
4
4
4
PL
e
e
e
PFHd [1/h]
1,2E-08
1,2E-08
1,2E-08
nop [Cycles per year]
<= 500.000
<= 350.000
<= 100.000
Calculation under the following conditions:
Days of operation per year: 365; Hours of operation per day: 24; Switching-Cycle per hour: 1;
Maximum load AC-15 / DC-13
Max. lifetime [years]
20
Proof test interval [years]
20
PFH [1/h]
6,2E-11
PFD
AVG
5,43E-06
SILCL
3
Safety
Characteristics
according to
EN 62061 /
EN 61508