Zander Aachen SR3C Operating Instructions Download Page 3

 

 

H. ZANDER  GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Germany 

Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138 • 

[email protected] • www.zander-aachen.de 

Emergency Stop Safety Relay SR3C 

M03 

Ver. B 

E61-137-00 

Operating Instructions

 

English translation 

Errors and technical changes reserved 

Maintenance 

The  device  must  be  checked  once  per  month  for  proper 
function  and  for  signs  of  tampering  and  bypassing  of  the 
safety function.

 

Techn. Data 

Corresponds to the standards 

EN 60204-1; DIN EN ISO 13849-1; EN 62061;   

 

 

IEC 61508 Parts 1-2 and 4-7; IEC 61511-1 

Operating voltage 

 

AC 230 V, AC 115 V  50-60 Hz; AC/DC 24 V; AC: 50-60 Hz    

Permissible deviation 

 

+ / - 10 % 

Power consumption 

 

AC 230 V 

 

AC 24 V  

DC 24 V

 

 

 

approx. 6.9 VA   

approx. 4.5 VA 

approx. 2.3 W 

Control voltage at S11 

 

DC 24 V 

Control current S11...S14 

 

approx. 60 mA 

Safety contacts 

 

3 NO contacts  

Auxiliary contacts 

 

1 NC contact  

Max. switching voltage 

 

AC 250 V 

Safety contact breaking capacity (13-14, 23-24, 33-34)    

AC: 

250 V, 2000 VA, 8 A for ohmic load 

(6 switching cycles/ min)

    

 

 

 

250 V, 3 A for AC-15 

 

 

DC:   40 V, 320 W, 8A for ohmic load 

(6 switching cycles/ min)

   

 

 

 

24 V, 3 A, for DC-13 

 

 

Max. total current through all 3 contacts: 

 

 

 15 A (13-14, 23-24, 33-34) *)  

Auxiliary contact breaking capacity (41-12)  

AC:  

250 V, 500 VA, 2 A for ohmic load 

 

 

DC:   40 V, 80 W, 2 A for ohmic load  

Minimum contact load  

 

5 V, 10 mA  

Contact fuses 

 

10 A gG  

Max. line cross section 

 

0.14 - 2.5 mm

2

  

Tightening moment (Min. / Max.) 

0.5 Nm / 0.6 Nm 

Typ. switch-on delay / switch-off delay for NO contacts 

< 30 ms / < 20 ms 

requested via safety circuit 
Max. length of control line 

 

1000m with 0.75 mm

2

  

Contact material 

 

AgSnO

Contact service life 

 

mech. approx. 1 x 10

7

 

Test voltage 

 

2.5 kV (control voltage/contacts)  

Rated impulse withstand voltage, leakage path/air gap 

4 kV  (DIN VDE 0110-1)  

Rated insulation voltage 

 

250 V  

Degree of protection 

 

IP20  

Temperature range 

 

-15 °C to +40 °C *)  

Max. altitude 

 

 2000 m (above sea level) 

Degree of contamination 

 

(DIN VDE 0110-1)  

Overvoltage category 

 

(DIN VDE 0110-1)  

Weight  

 

approx. 230 g  

Mounting 

 

DIN rail according to EN 60715 TH35 

Safety  
Characteristics  
According to 
EN ISO 13849-1 

 

Note:

 

Additional data can be requested from the manufacturer for 
applications that deviate from these conditions. 

The device is certified according to EN ISO 13849-1 up to a 
Performance Level of PL e. 

Device cannot be switched on again after an emergency 
stop:  

• 

Check whether the emergency stop circuit was closed 
again. 

• 

Was the start button opened before closing of the emer-
gency stop circuit (with manual start)? 

• 

Is the feedback loop closed? 

If  the  fault  still  exists,  perform  the  steps  listed  under 
“Commissioning Procedure”. 
If  these  steps  do  not  remedy  the  fault  either,  return  the 
device to the manufacturer for examination. 

Opening  the  device  is  impermissible  and  will  void  the 
warranty.  

Device does not switch on: 

• 

Check the wiring by comparing it to the wiring diagrams. 

• 

Check the safety switch used for correct function and 
adjustment. 

• 

Check whether the emergency stop circuit is closed. 

• 

Check whether the start button (with manual start) is 
closed. 

• 

Check the operating voltage at A1 and A2. 

• 

Is the feedback loop closed? 

What to Do in  
Case of a Fault? 

The  device  is  otherwise  maintenance  free,  provided  that  it 
was installed properly.

 

Safety characteristics according to EN ISO 13849-1 for all variants of SR3C 

Load (DC-13; 24 V) 

<= 0,1 A 

<= 1 A 

<= 2 A 

T10d 

[years] 

20 

20 

20 

Category

 

PL 

PFHd 

[1/h] 

1.2E-08 

1.2E-08 

1.2E-08 

nop

 [cycle / year]  

<= 500,000 

<= 350,000 

<= 100,000 

*) If several SR3C devices are closely spaced under load, the max. total current at the ambient temperature of T=20 °C: 9 A; at T=30 °C: 3 A; at T=40 °C =1 A.  
   If these currents are exceeded, a spacing of 5 mm between the devices must be observed. 