The  following  function  settings  are  valid  depending  on  the 

value  of  the  function  2    for 

timer  mode  (2-0  to  2-6) 

or 

counter mode (2-7).

   

ENS20 as timer (2-0 to 2-6, see function 2)  

Timing begins  with turning  on the starting signal (1-3)  and 

can  be  interrupted  by  this  input  as  desired.  The  START 

input 1-3 can be closed by a cable link. In this case timing 

begins directly with switching on the mains voltage. RESET 

and START input have an internal noise pulse suppression. 

They may be activated by contacts or electronic initiators. 
 

ENS20 as counter (2-7, see function 2)  

All  functions  3  to  8  also  apply  to  the  counter  mode.  The 

clock input is provided at the terminals 3 (+12..24 V) and 1 

(0  V).    Counting  is  done  by  closing  an  external  counting 

contact.  Also 2- or  3-wire  semiconductor outputs  of initia-

tors can be used. The falling edge is counted.   

Programming   

 

 

Display 

 

Function 2 

Timing ranges

 

2 – 0 

0.01 

-

 9.99 s 

2 – 1 

0.1 

-

 99.9 s 

2 – 2 

-

 999 s 

2 – 3 

0.1 

-

 99.9 min 

2 – 4 

-

 999  min 

2 – 5 

0.1 

-

 99.9 h 

2 – 6 

-

 999 h 

2—7 

Counter mode 

Display

 

Function 3:   
Timing functions

 

3– 0 

On-delay. 

Timing begins with applying of 

the mains voltage and closing of the 

START-contact. After timing the contacts 

switch from 15-16 to 15-18 until the arrival 

of a resetting signal, at least however for 

100 ms.  

3 – 1 

Impulse-limiting.  

 As On

-

delay, however 

the contacts are switched on with applicati-

on of the mains voltage immediately (15-

18) and back to 15

-

16 after timing.  

3 – 2 

Flashing (T1=T2). 

The ENS20 works after 

applying of the mains voltage and closing 

of the START contact as symmetrical cyc-

ling timer. The cycle starts with output off 

(relay switched off). On and off time are 

equal.   

3 – 3 

Flashing (T2=100ms). 

In this operating 

condition the output relay switches periodi-

cally for 100ms. The total cycle time is de-

termined by the preselected current value.   

3 – 4 

Signal off-delay.  

 The control is made by 

the START contact. The contacts switch on 

immediately and after opening the starting 

contact timing begins. After timing the 

contacts switch back to 15-16. A stop is not  

possible here.   

3 – 5...  

Free for customized special functions 

 

 

Dispaly

 

Function 4:   
Counting direction 

 

4 – 0 

upward. 

Timing/counting begins with zero 

and ends with the preselected value. A 

RESET signal sets back to zero.   

4 – 1 

downward. 

Timing  begins  with  the  presel-

ected value and ends with zero. A RESET 

signal sets back to the preselected value.  

 

Display 

 

Function 5:   
Power failure function 

 

5 – 0 

Continuation. 

Timing is continued after 

power failure with the value reached last. 

 

 

5 – 1 

Restart. 

Timing begins after power failure 

with zero or with the preselected value 

(RESET after power failure).   

Display

 

Function 6:  

Enable/disable programming

 

6 – 0 

Programming enabled during timing. 

Programming during timing (i.e. the START 

signal is turned on) is enabled. Timing is 

stopped and continued after the recent 

time preselection with the new values.   

6 – 1 

Programming disabled during timing. 

The programming mode by "

<

" and "

>

-

keys is not possible during timing (i.e. the 

START signal is turned on). Programming 

only, if the START input is turned off. 

Display 

 

Function 8:  

Input frequency

 

8 – 0 

Input frequency 

 at start/count 

50 Hz.

 

8 – 1 

Input frequency 

 at start/count 

500 Hz.

 

Display

 

Function 7:  

Aux. contact, only version 52311x 

 

7 – 0 

Auxiliary contact is immediate contact.   

Timer mode: The 2nd contact switches 

with applying the START signal . 

Counter mode: The 2nd contact switches 

on with the first counting pulse. 

7 – 1 

Auxiliary  contact  is  progammable  pre-

contact

 

The display shows next 

"Pxx ". 

 xx  is  the  timer/counter  value  of  the  2nd 

contact. Set the value with 

<, > 

e.g.

"P52".

  

Through this the 2nd contact switches on 

52 clocks before reaching the timer/counter 

preselection (1st contact). With the value 

"P00 " 

 the 2nd  contact  switches at the 

same time as the 1st contact with reaching 

the preselection value.   

Summary of Contents for ENS20

Page 1: ...ermitted All relevant safety regulations and standards must be attended to Non observance of the safety regulations may cause death severe injuries or substantial damage to property Before use please read the operating instructions and keep it in a safe place Make sure that the operating instructions are always available for installation initial operation and maintenance The installation and opera...

Page 2: ... 25 26 28 L1 L RESET START COUNT N M Option 0V ENS20 is a panel mounting device for 45 x 45 mm cutout The front of the device is water and dust proof A plastic front frame with external dimensions of 55 x 55 mm is available as an accessory The programming mode is activated by simultaneously pressing of and keys Note The LOCK function must be deactivated There are 8 functions 1 8 which are working ...

Page 3: ...100ms In this operating condition the output relay switches periodi cally for 100ms The total cycle time is de termined by the preselected current value 3 4 Signal off delay The control is made by the START contact The contacts switch on immediately and after opening the starting contact timing begins After timing the contacts switch back to 15 16 A stop is not possible here 3 5 Free for customize...

Page 4: ...l contact Time base quartz stabilized time tolerance 0 1 Min power off time function 5 1 100 ms function 5 0 200 ms Input frequency counter 50 500 Hz programmable Trigger closing of the contact falling edge Time ranges 7 between 0 01 s and 999 h Temperature range 0 C 500 C Dielectric strength 4 kV DIN VDE 0110 1 1997 04 Weight approx 200 g Order No 523110 ENS20 AC230 V 2 changeover contacts Order ...

Page 5: ...5 52070 Aachen Germany Tel 49 0 241 9105010 Fax 49 0 241 91050138 info zander aachen de www zander aachen de 5 Digital Timer Counter ENS20 L05 E61 282 00 Operating Instructions English translation Errors and technical changes reserved ...

Reviews: