CT200-G1 User Guide
Table 29: Temperature Calibration
Name
Value
Parameter (8-bit)
0x0D
Size (3-bit)
0x01
Configuration Values (8-bit)
Offset is a signed integer ranging from -6.0 degrees Fahrenheit to +6.0 degrees Fahrenheit.
Table 30: Offset
Value
Binary
Configuration
0xFA
11111010
-6.0 degree Fahrenheit
0xFB
11111011
-5.0 degree Fahrenheit
0xFC
11111100
-4.0 degree Fahrenheit
0xFD
11111101
-3.0 degree Fahrenheit
0xFE
11111110
-2.0 degree Fahrenheit
0xFF
11111111
-1.0 degree Fahrenheit
0x00
00000000
+0.0 degree Fahrenheit (DEFAULT)
0x01
00000001
+1.0 degree Fahrenheit
0x02
00000010
+2.0 degree Fahrenheit
0x03
00000011
+3.0 degree Fahrenheit
0x04
00000100
+4.0 degree Fahrenheit
0x05
00000101
+5.0 degree Fahrenheit
0x06
00000110
+6.0 degree Fahrenheit
Warning:
The offset must be an integer value. Non-integer values, such as 1.5F (0x03),
should not be used.
Display Units
The Display Units parameter specifies the unit of measurement used by the device to display
temperature.
Table 31: Display Units
Name
Value
Parameter (8-bit)
0x0E
Size (3-bit)
0x01
Configuration Values (8-bit)
Configuration values are bit-encoded.
Table 32: Display Units
Value
Configuration
0x00
Fahrenheit (DEFAULT)
0x01
Celsius
29