Table 19: Differential Temperature
Value
Configuration
0x04
2.0 degree Fahrenheit (DEFAULT)
0x06
3.0 degree Fahrenheit
0x08
4.0 degree Fahrenheit
0x0A
5.0 degree Fahrenheit
0x0C
6.0 degree Fahrenheit
Warning:
Default factory settings do not adjust the Cool Mode differential.
Warning:
The differential temperature must be an integer value. Non-integer values,
such as 1.5F (0x03), should not be used.
Warning:
If the thermostat is not configured for multistage HVAC systems then these
parameters have no effect.
This
Configuration Report Command
command is used to advertise the actual value of the
advertised parameter.
Table 20: Report Command for Thermostat Differential Tempera-
ture
Name
Value
Parameter (8-bit)
0x08
Size (3-bit)
0x02
Configuration Values (16-bit)
• Byte 1 = Heating
• Byte 2 = Cooling
Warning:
Unlike the Set Command, the Configuration Report returns the Differential
Temperature for both the Heat Mode and Cool Mode. The Configuration Report does not
explicitly return the Differential Mode.
Thermostat Recovery Mode
The Thermostat Recovery Mode parameter specifies the HVAC recovery mode type. The
recovery mode determines when additional HVAC stages are turned off as the ambient tem-
perature returns to the target temperature.
Fast Mode
The thermostat will leave all stages on (assuming they were already on) until
the ambient temperature reaches the target temperature.
Economy Mode
The thermostat will turn off additional HVAC stages when the ambient tem-
perature reaches the target temperature plus/minus the differential temperature.