Z-TRAUQ INC. P9650 Manual Download Page 3

  

 

 

 

 
 

 

                 Max. DC Load Breaking Capacity    

                      Electrical Endurance 

CONNECTION DIAGRAM

 

L1
L2
L3
N

 

DIMENSIONS

 

96

96

   

10

89.5

96

12

80

 

              Front view                                        

       Side view 

  All dimensions are in mm.

 

 

t t 

(s)(s)

    

 

 

10

0.1 

 

k   

1.0 
0.9 
0.8 
0.7 

0.6 

0.5 

0.4 

0.3 

0.2 

0.1 

0.05 

   1                                     

                                                 10

                        20

 

I/I>     

www.z-trauq.com                                                        877-798-7287                                                                [email protected]

A1 A2

Aux.supply

1

2

3 4

5

6

7

8

Rly 1

L1

L3

L2

X1

X1

X1

X2

X2

X2

9 10 11 12 13 14 15 16

95

 
 

 

TECHNICAL SPECIFICATIONS

 

Supply voltage Un (1, 2): 

±15% 

                           

230VAC ±15% 

                (V o lta

  g e  s h ou ld be specified at time of ordering)

Rated frequency:                50/60Hz 
Isolation:                         Over voltage cat. III 
Rated impulse  
 withstand voltage:              4kV (1.2 / 50 µS) IEC 60664 
Power consumption:            3W max. 

 

Rated current input In:          5A (directly connected)

 

Rated frequency:                50Hz 
Burden:                          <0.4VA @ In 
Overload:                       4 x In (continuous) 

 

External CT terminals 
9, 10, 11, 12, 13, 14             Class C recommended with 5A secondary 

 

Overcurrent settings: 
 Low-set trip (I>):               2.0 – 6.0A (40 – 120%) 
 Time multiplier (TM):     

0.05 – 1.0 

 High-set trip (I>>):            x1 – x10 or disable
 High-set definite time:     

Instantaneous (<50mS) 

 

Pick up value:         

+2% of trip setting 

Accuracy: 
 Protection thresholds:         

± 5% 

 Response time:                

± 5% (with a minimum of 50mS) 

Repeat accuracy:               

± 0.5% @ constant conditions 

Ambient temperature:          -10 to +60°C 
Relative humidity:               +95% (non-condensing) 

 

Output: 
 RL1  (3, 4, 5):                  1 x SPDT relay 
Output rating:                 AC1  250V 8A (2000VA) 
                                  AC15  250V 5A (1250VA) 
                                  DC1 25V 8A (200W) 
Electrical life:                    

≥ 150,000 ops at rated load 

Dielectric voltage:          

2kV AC (rms) IEC 60947-1

 

Rated impulse 
 withstand voltage:         

4kV (1.2 / 50µS) IEC 60664 

115VAC

Options: 

 

The P9600 range also includes individual Overcurre nt or Earth fault relays 
available with either IDT or IDMT tripping characte ristics.  

Please refer to separate data sheets. 

Tripping Curve Characteristics 

(Normal Inverse 3/10).

Housing:

                      Flame retardant Lexan

 

Protection:        

IP55 / IP20 (rear) 

Weight:                            ≈

   590g 

Mounting:        

Panel mounting. Cutout = 91 x  91mm (± 0.5mm) 

Max. panel thickness: 

Terminal conductor size:      0.05 - 2.5mm

2

 (30 - 12AWG) 

Recommended tightening 

 torque:                        10in lb (1Nm) 

Wire stripping length:         0.24 – 0.30in (6 – 7.5mm ) 

Approvals:      

Conforms to IEC. CE and         

and RoHS Compliant. 

 EMC: Immunity: EN/IEC 61000-6-2 

       Emissions: EN/IEC 61000-6-4 

Generic: IEC 60255-26 (EMC), IEC 255-3, IEC 

60255-151 

 

     

12mm 