TEMPERATURE CONTROLLER
20
USER
’
S MANUAL
21
380V/414V 3Phase 4 Line Type
240V 1 Phase 2 Line Type
13.Wiring modification method
YUDO Temperature Controller
operates with supply voltage 220~240V AC.
But even in case of supply voltage 380~415V AC 3phase 4 line, by re-wiring as shown
below, 220~240V AC can be taken between one phase(R, S or T) and Neutral(N).
YUDO Temperature Controller be supplied with wiring for supply voltage 220~240V AC
unless special instruction. Please check the current wiring.
Caution) Before re-wiring, make sure AC main power OFF and Power Switch OFF on controller.
1. Power off 2. Open the back cover of controller
3. Separate all 3 blue-sleeved wires from L1,L2 and L3
4. Plug all 3 blue-sleeved wires into N
Supply
voltage
380V
Supply
voltage
220V
Controller
220V
Controller
220V
1. Power off
2. Open the back cover of controller
3. Separate all 3 blue-sleeved wires from N
4. Plug blue-sleeved RED wire into L1
5. Plug blue-sleeved WHITE wire into L2
6. Plug blue-sleeved BLACK wire into L3
Warning) Do NOT plug PE wire into N. Plugging PE wire into N may cause damage of
controller, for which YUDO will not take responsibility.
Supply
voltage
220V
Supply
voltage
380V
Controller
220V
Controller
220V
Re-wiring for supply voltage 380V AC from wiring for supply voltage 220V AC
Re-wiring for supply voltage 220V AC from wiring for supply voltage 380V AC