background image

TEMPERATURE CONTROLLER

20

USER

S MANUAL

21

380V/414V 3Phase 4 Line Type

240V 1 Phase 2 Line Type

13.Wiring modification method

YUDO Temperature Controller

operates with supply voltage 220~240V AC.

But even in case of supply voltage 380~415V AC 3phase 4 line, by re-wiring as shown
below, 220~240V AC can be taken between one phase(R, S or T) and Neutral(N).
YUDO Temperature Controller be supplied with wiring for supply voltage 220~240V AC
unless special instruction. Please check the current wiring.

Caution) Before re-wiring, make sure AC main power OFF and Power Switch OFF on controller.

1. Power off           2. Open the back cover of controller
3. Separate all 3 blue-sleeved wires from L1,L2 and L3 
4. Plug all 3 blue-sleeved wires into N

Supply

voltage

380V

Supply

voltage

220V

Controller

220V

Controller

220V

1. Power off
2. Open the back cover of controller
3. Separate all 3 blue-sleeved wires from N 
4. Plug blue-sleeved RED wire into L1
5. Plug blue-sleeved WHITE wire into L2
6. Plug blue-sleeved BLACK wire into L3

Warning) Do NOT plug PE wire into N. Plugging PE wire into N may cause damage of 

controller, for which YUDO will not take responsibility.

Supply

voltage

220V

Supply

voltage

380V

Controller

220V

Controller

220V

Re-wiring for supply voltage 380V AC from wiring for supply voltage 220V AC

Re-wiring for supply voltage 220V AC from wiring for supply voltage 380V AC

Summary of Contents for CGF 560

Page 1: ...566010 U K Mobile 98 912 2776072 e mail amin yudo co uk U S A YUDO INC HQ TEL 1 614 873 1300 FAX 1 614 873 6873 e mail slee yudousa com jaagaard yudousa com Central Division TEL 1 630 529 7487 FAX 1...

Page 2: ...Mode 3 MANUAL Mode 7 Menu Setting 8 1 User s Setting Menu 2 Supplier s Setting Menu 8 Error Code Display Function 15 9 Integrated Control Function 16 10 Connector Cable 17 1 How to wire a Heater and...

Page 3: ...9 Make it sure to earth ground wire of the controller Neglect to earth the ground wire green line can cause damage to fuse and Triac due to noise voltage 10 Turn on the Main Power Switch first 11 The...

Page 4: ...ersion key 10 AUTO LED Displays Auto Mode is selected 11 STAND BY LED Displays Stand by Mode is selected 12 MANUAL LED Displays Manual Mode is selected 13 MODULE Handle 14 MODULE Power Switch 15 MODUL...

Page 5: ...m as 50 C AL L Lowest Limit Alarm as 50 C AL H start at 250 C of measured temperature AL L at 150 C Output power is reduced to maintain at the STAND BY Temperature STAND BY Mode will finish after the...

Page 6: ...75 Stand by Mode is operated for 1 hour and the Temperature for Standby Mode is set as 140 C 75 x 200 C Choose ON or OFF with key To save press and keys together This is provided to help the Integrat...

Page 7: ...t Power for 1 minute at the beginning of Power Supply in order to check connection state of a heater and sensors and start smooth control action at low heat state Hold and keys for 3 seconds at the sa...

Page 8: ...DESCRIPTION 1 tC oP Sensor Disconnection 2 tC St Sensor Short Circuit 3 tC rE Sensor Polarity Reverse 4 AL H High Limit Alarm 5 AL L The Low Limit Alarm 6 Ht oP Heater Disconnection 7 Ht St Heater Sh...

Page 9: ...d STANDBY function Connector means a component attached to the end part of cable in order to make it easy to connect disconnect the wire to the mold controller Various kinds of connectors are used dep...

Page 10: ...ation 3 Options NO CONTROLLER CONNECTOR QUANTITY 1 1 ZONE 4P Round Jack 1 EA 2 2 ZONE 16 P 1 EA 3 3 4 ZONE 16 P 1 EA 4 5 6 ZONE 24 P 1 EA 5 7 8 ZONE 24 P 2 EA 6 9 12 ZONE 24 P 2 EA 7 13 16 ZONE 24 P 3...

Page 11: ...r 1 Power off 2 Open the back cover of controller 3 Separate all 3 blue sleeved wires from L1 L2 and L3 4 Plug all 3 blue sleeved wires into N Supply voltage 380V Supply voltage 220V Controller 220V C...

Page 12: ...mold or it s coat is peeled so as to contact mold or line T C Sensor type between mold and controller is different EX CA K IC J IC J CA K Check point Check T C wire with tester When disconnected repl...

Reviews: