Yudian AI-7048 Operation Instruction Manual Download Page 6

5

 

SCHx   

Scale high limit 

units 

Scbx 

Input offset 

For thermocouple, the units of Scb is 0.1 .  For example, when Sc

b=-100, 

the  actual  offset=-10 ,  then  the  measured  temperature  will  be  10   lower 

than that when Sc=0. 

-1999~+4000 

units or 0.1

 

FILx 

Digital filter 

The value of FIL will determine the ability of filtering noise.   

FIL=0, no filtering;   

FIL=1, filtering with mean;   

FIL=2~40, filtering with mean and integral. 

When  a  large  value  is  set,  the  measurement  input  is  stabilized  but  the 

response speed is slow.  Generally, it can be set to 1 to 3. 

If strong interference exists, then you can increase parameter FIL gradually to 

make momentary fluctuation of measured value less than 2 to 5.   

When the instrument is being metrological verified, FIL can be set to 0 or 1 to 

shorten the response time.   

0~40 

Px 

Proportional 

band 

Proportional  band  in  PID  and  APID  control.  Instead  of  percentage  of  the 

measurement range, the unit is the same as PV. 

Generally, optimal P, I, D and CtI can be obtained by auto tuning. They can 

also be manually inputted if you already know the correct values. 

10

9999 units

Ix 

Time of Integral  Time of Integral in PID. No integral effect when I=0 

0

9999 

seconds 

Dx 

Time of 

derivative 

Time of derivative in PID. No derivative effect when d=0 

0

999.9 

seconds 

H.ALx 

Alarm high limit  x  channel  high  alarm  is  triggered  when  PVx  (the  present  value  of  x 

channel)>H.ALx; alarm releases when PVx<H.ALx - HYSx. 

-999~+3200 

L.ALx   

Alarm low limit  x channel low alarm is triggered when PVx<L.ALx; 

alarm releases when PVx>L.ALx+HYSx. 

HYSx   

Hysteresis 

HYS  is  set  to  avoid  high  frequent  alarm  on/off  actions  caused  by  process 

input fluctuation.  It also works at auto-tuning. 

0~999.9

 

AOPx   

Alarm output 

allocation 

(D5 size not 

support this 

function) 

Alarm   

Output to   

Low limit alarm   

High limit alarm 

None 

AL1 

AL2 

For example, AOP1=43 that the low limit alarm of channel 1 is sent to AL2, 

and high limit alarms sent to AL1 

0~44 

Cn   

Number of 

input channels 

Define actual number of input channels. Setting range is 1~4. 

When Cn=2, the lower window display the present value of channel 2 instead 

of the channel number. 

1~ 4 

Cno 

First display 

channel setting 

If  several  of  AI-7048  has  used,  this  parameter  can  define  the  AI-7048  to 

display assigned channel number on display. For example, when Cno=6, the 

controller will display channel number from 6~9. (6, 7, 8, 9) 

 

AF 

Addition 

function setting 

Parameter “AF” was defined as below: 

AF=A x 1 + B x 2 + C x 3 + D x 4 

A=0; Normal speed in channel cycle display; 

A=1; Faster speed in channel cycle display; 

B=0; C=0; 

D=0; Normal application; D=1; Change all of the low alarm to be high alarm; 

 

AF2 

Addition 

function setting 

Parameter “AF2” was defined as below: 

AF=A x 1 + B x 2 

A=0; Normal application; 

A=1; Change all of the high alarm to be high deviation alarm; when deviation 

value (PV – SV) > H.ALx, it will trigger the alarm. When (PV – SV) < H.ALx – 

HYSx,  alarm  off,  set  the  H.ALx  value  to  maximum  will  disable  the  alarm 

function. 

B=0; Normal application; 

 

Reviews: