11
4
~
20mA linear current signal can be converted to 1
~
5V voltage signal by connecting a 250 ohm
resistor and inputted from terminals 11 and 12.
Note 3:
S or S4 module can be installed in COMM slot for communication. If relay, TRIAC no contact switch,
or SSR drive voltage output module is installed in COMM, it can be used as alarm output. If I2
module is installed in COMM and parameter
“
bAud
”
is set to 1, SV1 and SV2 can be
switching by connecting a switch between terminals 3 and 4.
Wiring graph of instruments with D2 dimension as below:
Note 1:
D2 dimension instruments don
’
t support 0
~
5V or 1
~
5V linear voltage input.
However, 0
~
5V or 1
~
5V signal can be converted to 0
~
500mV or 100
~
500mV by
connecting external precise resistors, 4
~
20mA can be converted to 100
~
500mV by
connecting a 25ohm resistor, then be inputted from terminals 9 and 8.
Note 2:
For COMM/AUX slot, if S or S4 communication module is installed, it can be used for
communication; if L2 module is installed in, parameter set bAud = 0, it can be used for AU1 or AU2
alarm output; if set parameter bAud = 2, it can be used for AU1 or AL1 alarm output. If L1, L2, L4,
G, K1, W1 or W2 is installed, it can be the auxiliary output in bidirectional (heating/refrigerating)
control (Auxiliary output doesn
’
t support analog current output); if I2 is installed and bAud = 1, then
it can input on-off signal to switch SP1 and SP2 (AI-516) or switching the program status RUN /
Stop (AI-516P) by connecting a switch between terminals number 3 and 5.