INSTRUMENT INSTALLATION AND WIRING
Wiring graph for instruments with dimension A, E or F
Note:The compensation wires for different kinds of thermocouple are different, and
should be directly connect to the terminals. Connecting the common wire between the
compensation wire and the terminals will cause measurement error.
Wiring graph for D dimension(72mmX72m) instruments
:
Wiring graph for D2 dimensio (48mmX48mm) instruments
Wiring graph for Thyristor Trigger Output
Note: it is recommended to use the SCR power module,which includes a pair of SCRs and
diodes. Compared to TRIAC, it is more reliable and consumes less electricity
possible different. So you'd better set setpoint to an often-used value or
middle value first, and then start auto-tuning. For the ovens with good heat
preservation, the setpoint can be set at the highest applicable temperature. It
is forbidden to change SV during auto tuning. Depending on the system, the
auto-tuning time can be from several seconds to several hours.
Note 2:Parameter CHYS (on-off differential, control hysteresis) has influence on
the accuracy of auto-tuning. Generally, the smaller the value of CHYS, the
higher the precision of auto tuning. But CHYS parameter value should be
large enough to prevent the instrument from error action around setpoint due
to the oscillation of input. CHYS is recommended to be 2
℃
Note 3:AI series instrument has the function of self-learning. It is able to learn the
process while working. The control effect at the first run after auto tuning
is probably not perfect, but optimal control result will be obtained after a
period of time because of self-learning.
PARAMETERS AND SETTINGS
●
Field parameter table (Press
and hold for 2 seconds to access)
Code
Name
Description
Setting
Range
default
HIAL
High limit
alarm
Alarm on when PV>HIAL; Alarm off when PV<HIAL-
AHYS.Set to 3000 will disable this function
-999~
+3000
3000
LoAL
Low limit
alarm
Alarm on when PV<LoAL; alarm off when PV>LoAL +
AHYS.Set to -999 will disable this function
-999~
+3000
-999
HdAL
Deviation
high alarm
Alarm on when PV-SV>HdAL; alarm off when PV-SV
<HdAL-AHYS.Set to 3000 will disable this function
-999~
+3000
3000
LdAL
Deviation
Low larm
Alarm on when PV-SV<LdAL; alarm off when PV-SV
>LdAL+AHYS;Set to -999 will disable this function
-999~
+3000
-999
Loc
Parameter
lock
0: auto-tuning and modification of field parameters and
setpoint are allowed.
1: allowed to modify field parameters and setpoint value,
but can't run auto-tuning.
2: allowed to modify field parameters, but can't change
the setpoint or run auto-tuning.
3~255: can only modify "Loc"
808: setting Loc=808 and then pressing
can access
system parameter table
0~255
0
●
System parameter table (set Loc=808 and then press
to access)
Code
Name
Description
Setting
Range
default
AHYS
Alarm
Hysteresis
Avoid frequent alarm on-off action because of the
fluctuation of PV.
0~200
2
AoP
Alarm
output
assignment
Alarm
Output
LdAL
(x1000)
HdAL
(x100)
LoAL
(x10)
HIAL
(x1)
None
0
0
0
0
AL1
1
1
1
1
AL2
2
2
2
2
AU1
3
3
3
3
AU2
4
4
4
4
Example:
AOP =
0 1 0 1
;
LdAL HdAL LoAL HIAL
It shows that HIAL and HdAL are sent to AL1, and
LoAL has no output.
0~4444
111
CtrL
Control
mode
onoF : On-off control
APId : AI PID control, high precision and no-
overshoot
onoF,
APId
APId
Act
Acting
Method
rE:Reverse acting. Increase in measured
variable causes an decrease in the output,
such as heating control.
dr: Direct acting. Increase in measured variable
causes an increase in the output, such as
refrigerating control.
rEbA: Reverse acting with low limit alarm
and deviation low alarm blocking at the
beginning of power on.
drbA: Direct acting with high limit alarm
and deviation high alarm blocking at the
beginning of power on.
rE
dr
rEbA
drbA
P
Proportion
band
Proportion band in PID with unit
℃
or
℉
1~999
Sec
30
I
Time of
Integral
No integral effect when I=0
0~9999
Sec
100s
d
Time of
Derivative
No derivative effect when d=0
0~999.9
Sec
50.0s
Ctl
Control
period
Small value can improve control accuracy.
For SSR or TRIAC output, generally 0.5 to 3
seconds.
Large value can increase using life of relay.
For Relay output, generally 15 to 40 seconds.
0.5~120
Sec
2s
Or
20s
CHYS
Control
Hysteresis
CHYS is used for ON-OFF Control to avoid
frequent on-off actuon of relay.
For a heating system,if PV > SV, Output turns
OFF;PV<SV-CHYS, Output turns ON.
0~200
2
INP
Input
specification
InP
Input type
InP
Input type
0
K
1
S
2
R
3
SPARE
4
E
5
J
6
SPARE
7
N
8~20
SPARE
21
Pt100
0~21
0
dPt
Resolution
0 : 1
℃
/
℉
0.0 : 0.1
℃
/
℉
(only AI-509 have)
0 / 0.0
0.0
Scb
Input Shift
Scb is used to make input shift to compensate the error
produced by sensor or input signal.
PV_after_compensation=PV_before_compeScb.
-200~
+400
0
FILt
PV Input
filter
The value of FILt will determine the ability of filtering
noise.
When a large value is set, the measurement input is
stabilized but the response speed is slow.
Generally, if great interference exists, then you can
increase parameter “FILt” gradually to make momentary
fluctuation of measured value less than 2 to 5.
When the meter of the instrument is being examined at
laboratory, “FILt” should be set to 0 or 1 to short the
response time.
0~40
1
Fru
Selection of
power
frequency
and
temperature
scale
50C: 50Hz,
℃
50F: 50Hz,
℉
60C: 60Hz,
℃
60F: 60Hz,
℉
50C
50F
60C
60F
50C
SPL
Low limit of
SV
Minimum value that SV allowed to be
-999~
3000
0
SPH
Upper limit
of SV
Maximum value that SV allowed to be
400
http:www.yudian.com Yudian Copyright(C)1991-2018
S034-02
Note: The graph suits for upright intruments
with dimension A or E
For instruments with dimension F, just clockwise
rotate the graph 90 degree and the terminal
numbers keep the same.