Yoshitake TD-10NA Instruction Manual Download Page 5

E

PDT-079d

 

-4- 

 
 
 
 
 
 
 

 
 
 

TD-10NA                    TD-30NA 

(6)

 

Carry out the connection with pipes properly. 

  Improper piping connection may cause the leakage of fluid. 

(7)

 

Do not use a quick-operating valve in front and behind of trap not to produce water hammer. 

 

Trap can be damaged. 

 
 
 
 
 
 
 
 
 

(8)

 

Install a trap lower position as possible to collect condensate. And keep piping slope. 

(9)

 

Do not insulate the product. 

(10)

 

When installing a trap on main pipe of steam, prepare drip leg before the trap. 

(11)

 

Install a trap where atmosphere temperature is lower than discharging condensate has. 

(12)

 

By-pass line provided in parallel to the trap can give such advantages as follows. 

By opening the by-pass valve, large volume of condensate and air on start up can be quickly discharged. 

Newly installed piping can be blown off easily by closing the valves on the inlet and outlet sides and by 

opining the by-pass valve. 

 

Inspection of a trap and replacement of parts can be done without stopping the line operation. 

 
 
 

6.2 Example of piping 

Description

 

Correct

 

Incorrect

 

When installing by-pass 

line,  prepare  stop  valve 
to  the  outlet  side  of  a 
trap.

 

 
 
 
 
 
 
 

 

Steam  trapping  near  a 

regulating valve shall be 
provided  to  the  inlet 
side.

 

 
 
 
 
 
 

 

  (mm) 

 

TD-10NA 

90 

90 

70 

TD-30NA 

 

Summary of Contents for TD-10NA

Page 1: ...us injury Caution This symbol indicates a hazardous situation that if not avoided may result in minor or moderate injury Caution may also be used to indicate other unsafe practices or risks of propert...

Page 2: ...rating pressure range is considerably wide calling for no adjustment Any installation angles horizontal inclined or vertical are available permitting easy piping The trap is kept warm with insulation...

Page 3: ...nsate temperature becomes almost equal to the saturated steam temperature the condensate passing through the bottom A of the disc becomes re evaporating jet Because of this a low pressure section is g...

Page 4: ...e Capacity Installation 6 1 Warning and Caution for Installation Warning Plumb in the piping of the outlet side to the safe place where blowing steam condensate can not affect It is dangerous if fluid...

Page 5: ...lower than discharging condensate has By pass line provided in parallel to the trap can give such advantages as follows By opening the by pass valve large volume of condensate and air on start up can...

Page 6: ...positioned at the bottom of condensate producing device Condensate from every device shall be trapped independently The inlet and outlet piping shall be the same nominal size as a nominal size of the...

Page 7: ...pipe shall be positioned above the water level in the pit While stopping the trap may suction dirty water in the pit which may lead to malfunction Operating Procedure 7 1 Warning and Caution for Opera...

Page 8: ...hen repair the product proper parts must be used And do not alter product Using the improper parts and alternation of the product may be result on injury or burns by breakage of product blowing out of...

Page 9: ...matter stuck or oil film on the disc and valve seat Disassemble and clean it Refer to 8 4 Disassembly Drawing about the name of parts mentioned above Contact us or our agent if necessity of parts rep...

Page 10: ...of the body for TD 30NA differs Part names shown in boxes are consumable items Disposal When dispose the products we recommend each parts is disposed after checking what the material is Please refer...

Reviews: