Yoshitake OB-3 Quick Start Manual Download Page 8

                                             

7

                                  ■

EPDT-258b

 

 

 

5. Maintenance and Inspection 

 

5.1

 

  Cautions before use   

          Caution 

(1) Do not disassemble the product without reason. 
* If you disassemble the product for no reason, the original performance of the product is not achieved. 
(2) When plumbing the product, make sure to remove foreign substances, scale, etc. from the pipes. 
* If foreign substances, scale, etc. enter the product, the original performance of the product is not achieved. 
(3) Make sure to install a strainer (60 to 80 mesh) on the inlet side of the product. 
* If foreign substances, scale, etc. enter the product, the original performance of the product is not achieved. 
(4)  Install  pressure  gauges  on  the  inlet  and  outlet  sides  of  the  product  to  confirm  the  operation  of  the 

product.     

* Otherwise, the temperature is not adjusted correctly and, therefore, the original performance of the product 

is not achieved. 

(5) To install the product, confirm the inlet, outlet and posture of the product. 
* If the product is installed in a wrong way, it may not perform its original functions. 
(6) Install the product in a place where the temperature does not exceed the preset temperature. 
*  If  the  ambient  temperature  becomes  higher  than  the  present  temperature,  the  temperature  cannot  be 

adjusted correctly. 

(7) Install a thermometer near the thermal bulb. 
* Otherwise, the temperature cannot be adjusted correctly. 
(8) Install the thermal bulb in a way that makes three fourths or more of its total length come into contact with 

the fluid to be heated. 

* Otherwise, the temperature cannot be adjusted correctly and the original performance of the product is not 

achieved. 

(9) Make sure that the installation posture of the thermal bulb is correct. If there are T marks on the flanges 

or joint nuts, follow the instructions on how to install them. 

* Otherwise, the temperature cannot be adjusted correctly. 
(10) The bending radius of the capillary tube must be 40 mm or more. Do not bend it at an acute angle, nor 

twist it or pull it forcibly. 

*  Otherwise,  the  capillary  tube  may  be  damaged  and  the  original  performance  of  the  product  is  not 
achieved. 
(11) Make sure that the capillary tube is not in contact with the steam pipe. 
* Otherwise, the temperature cannot be adjusted correctly and the original performance of the product is not 

achieved. 

(12) Install pipes in a way that does not add excessive load, bending force, vibration, etc. on the product. 
*  Otherwise,  the  product  may  not  function  correctly  or  the  service  life  of  the  product  may  be  extremely 

shortened. 

 

 
5.2 Installation of Main Unit 

(1) Install the temperature regulator valve vertically against the horizontal pipe, placing its frame above. 
(2) If the ambient temperature becomes higher than the preset temperature, it may cause malfunction of the 

product, so install the product in a place where the temperature does not exceed the preset temperature. 

(3) Make sure to install a pressure gauge and a strainer bypass pipe in the piping. (See 6.6 Piping Diagram.)     
(4) If the pressure of the heating fluid is higher than the maximum pressure, use the product after reducing the         

pressure with the pressure reduction valve, etc. 

(5)  Implement  the  plumbing  in  a  way  that  does  not  add  excessive  load,  bending  force,  vibration,  etc.  to the 

main unit. 

(6) If the product is to be left unused for a long time, completely drain the pipes and close the gate valves at the 

front and the rear of the temperature adjustment valve. 

(7) When supplying air or water, make sure to remove foreign substances from the pipes through the bypass 

pipe and then open the temperature adjustment valve circuit. 

 

 

 

 

 

 

 

 

Summary of Contents for OB-3

Page 1: ...ult in minor or moderate injury or may result in only property damage Table of Contents 1 Usage of the Product 1 2 Specifications 1 2 2 1 Specifications 1 2 2 Temperature adjusting range 2 2 3 Tempera...

Page 2: ...on Heating Cold water Refrigerant Heated Cold and hot water Oil Non dangerous fluid Maximum Pressure Body 15 40A 0 7MPa 1 0MPa 50A 0 5MPa 0 7MPa 65A 0 5MPa 0 7MPa 80A 0 4MPa 0 5MPa 100A 0 4MPa 125A 0...

Page 3: ...2m 2 3 3 5 2 3 5m 2 5 3 5 4 3 5 5m 4 4 5 If the preset temperature is higher than 100 C add 1 0 C The preset temperature error is the maximum temperature width ranging from the time when the valve cl...

Page 4: ...erence in bellows structure mm mm Nominal size R Standard 15A 40A 2000 Nominal size d L H H B Weight kg 15A Rc 1 2 148 55 510 160 11 20A Rc 3 4 148 55 510 160 11 25A Rc 1 160 60 520 160 12 32A Rc1 1 4...

Page 5: ...160 15 20A 130 60 520 160 16 25A 140 70 540 160 18 32A 150 75 550 160 21 40A 160 75 550 160 23 50A 180 110 620 160 29 65A 215 125 650 160 38 80A 260 135 670 160 48 100A 300 160 750 180 58 125A 360 190...

Page 6: ...t pressure P1 outlet P2 and steam flow rate are 0 3MPa 0 15MPa 9 m3 h respectively first find intersection point a of the differential pressure 0 15MPa 0 3MPa 0 15MPa and the flow rate 9 m3 h Since th...

Page 7: ...tlet P2 and steam flow rate are 0 3MPa 0 15MPa 9 m3 h respectively first find intersection point a of the differential pressure 0 15MPa 0 3MPa 0 15MPa and the flow rate 9 m3 h Since the intersection p...

Page 8: ...f there are T marks on the flanges or joint nuts follow the instructions on how to install them Otherwise the temperature cannot be adjusted correctly 10 The bending radius of the capillary tube must...

Page 9: ...stallation posture does not affect the function even if the installation is made regardless of the T mark position See the diagram below showing an example of thermal bulb insertion Thermal bulb insta...

Page 10: ...erature than the max allowable temperature of the product 2 Turn the handle and move the indicator to the desired temperature position on the scale To raise the temperature turn the handle countercloc...

Page 11: ...1 Disassemble and clean or replace 2 Replace the product 3 Reinstall them at points where the circulation is best 5 8 Precautions during maintenance and inspection Warning 1 When using a hot fluid do...

Page 12: ...EPDT 258b 6 Handling of Protection Pipe Option 6 1 A set of protection pipes 6 2 Insert a gasket into the protection pipe 6 3 Insert a thermal bulb into the protection pipe and screw in a screwing joi...

Page 13: ...PDT 258b 6 4 Fasten the joint nut with a wrench or spanner 6 5 Inject liquid which is the same as the liquid to be heated from the plug hole on the screwing joint side 6 6 Attach the plug after inject...

Page 14: ...product Yoshitake supplies the repair parts for 5 years otherwise individually agreed 3 This warranty does not cover the damage due to any of below 1 Valve seat leakage or malfunction caused by forei...

Reviews: