Yoshitake GD-24 Installation & Operation Manual Download Page 7

-6- 

EPDT-209

 

6. Installation 

6.1 Piping Example 

 

 
 

 

 
 

 

 
 

 

 
 

 

6.2  Warning and precaution on installation 

 

Warning

 

In case installing safety relief valve as safety device at outlet side, joint relief pipe at outlet of 
safety relief valve and guide it to safety place where steam can relief out. 

 

Caution

 

( 1 )  Do not disassemble the valve unreasonably. 

*Disassembling the valve at your discretion may affect the original performance. 

( 2 )  Remove foreign matter and scales from the lines before installing the valve. 

*Failure to do so may prevent the valve from functioning correctly. 

( 3 )  Install a strainer (Screen: 60 mesh) at the valve inlet side. 

*Failure to do so may hamper correct pressure control, which affects the original 

 performance. 

( 4 )  Install a safety relief valve at the valve outlet side for protection of equipments. 

*Failure to do so prevents problem detection, resulting in equipment damage. 

( 5 )  Install a pressure gauge at both the inlet and outlet sides of the valve. 

*Failure to do so may hamper correct pressure adjustment. 

( 6 )  When installing quick open and close valves, such as a solenoid valve, secure at least 3 m 

from the valve. 
*Failure to do so may result in malfunction or drastically shortened service life. 

( 7 )  When pressure reducing in two stages, secure at least 3 m between the valves. 

*Failure to do so may result in malfunction, affecting the original performance. 

( 8 )  Install the valve in proper direction of the fluid flow. 

*Failure to do so affect the performance. 

( 9 )  Do not apply excessive load, torque or vibration to the valve. 

*Doing so may result in malfunction or drastically shortened service life. 

(10)  Secure the necessary maintenance space at the installation site of the pressure reducing 

valve.    
*In case there is not enough space for maintenance, pressure reducing valve cannot be 

disassembled at the time of maintenance.       

(11) The set pressure of safety relief valve must be higher than the set pressure of pressure 

reducing valve.   

*In case reseating pressure of safety relief valve is lower than the set pressure of 

pressure reducing valve, safety relief valve will continue to blow.       

(12)  Do not freeze pressure reducing valve.   

*Freezing may damage pressure reducing valve.     

(13)  Do not allow pipe adhesive materials to leak into pressure reducing valve.       

*In case the adhesive material is acquired in pressure reducing valve, it causes 

malfunction.  

Summary of Contents for GD-24

Page 1: ...lease carefully store this manual in a handy place The following safety symbols are used in this manual Warning Caution Contents 1 Features 1 2 Specifications 1 3 Dimensions and Construction 3 1 Dimen...

Page 2: ...rusty water problems 3 A stainless steel valve seat reduces wear and increases durability 4 A sealed construction prevents external leakage even if the diaphragm should break 5 The valve can be mount...

Page 3: ...3 1 Dimensions Weight GD 24 24B mm Nominal size d L H H1 Weight kg 15A Rc 1 2 80 193 41 5 1 8 20A Rc 3 4 90 210 45 2 4 25A Rc 1 100 230 50 3 3 32A Rc 1 1 4 120 265 60 4 7 40A Rc 1 1 2 150 315 62 8 2 5...

Page 4: ...ing 22 Plug 27 Label 28 Spring Washer 4 Operation Refer to the parts number in 3 2 Construction Turning the adjusting screw 11 to compress the adjusting spring 17 and the load of adjusting spring is i...

Page 5: ...he pipe is ideal Cv Value Nominal size 15A 20A 25A 32A 40A 50A Cv value 1 5 1 9 3 4 7 10 Calculation formula for Cv value P G V Cv 365 0 P1 Inlet pressure MPa A V Rated flow rate m3 h P2 Reduced press...

Page 6: ...5 EPDT 209 5 2 Flow Rate Characteristics Chart 5 3 Pressure Characteristics Chart...

Page 7: ...lenoid valve secure at least 3 m from the valve Failure to do so may result in malfunction or drastically shortened service life 7 When pressure reducing in two stages secure at least 3 m between the...

Page 8: ...nt parts Be sure to follow the following steps to complete proper adjustment Refer to the parts number in 3 2 Construction 1 Close the stop valves at both sides of the pressure reducing valve and thor...

Page 9: ...and after pressure reducing valve and remove all foreign matter and scales via the by pass line before operation Failure to do so may cause the malfunction of pressure reducing valve Consumable parts...

Page 10: ...oxes are consumable parts Nut Spring Lock Washer Diaphragm Shell Diaphragm Suspension Metal Pressure Gauge Body Valve Seat Set Screw Washer Disc Valve O ring Spring Cap Adjusting Screw Sealed Nut Bolt...