Yoshitake AF-7 Instruction Manual Download Page 2

E

PDT-168

a

- 1 -

Overview

Suited for installation on steam boilers, various pressure vessels, instrumentation apparatus, and the
secondary side of pressure reducing valves. Yoshitake’s Safety Relief Valves prevent accidents due to
the abnormal rise in piping pressure.

1. Features

(1)  The product is designed according to JIS B 8210 for spring loaded safety relief valves for

steam boilers and gas pressure vessels.

(2)  The sealed structure of model AF-7M prevents any external leakage of fluid during operation.

2. Specifications

 Model

AF-7

AF-7M

Type

Open lever type

*

1

Enclosed type

*

2

Fluids

Steam, air, and other

non-corrosive gases

Air and other non-corrosive gases

Pressure range

0.1 ~ 1.0 MPa

Temperature range

5 ~ 350 

5 ~ 300

Super imposed back pressure

0 MPa

Connections

Inlet: JIS 10K RF flange or JIS 20K RF flange (JIS B 2238)
Outlet: JIS 10K FF flange (JIS B 2238)

Size (mm)

25, 40, 50, 65, 80, 100

Body

Carbon steel casting

Material

Valve & valve seat

Stainless steel

   

*

A safety valve which is so constructed that a part of the fluid blown off from the valve seat

        opening is also discharged outside from other part than the valve outlet.

     

*

2

 

A safety valve which is so constructed that the fluid blown off from the valve seat opening

        is not allowed to discharge outside from other part than the valve outlet.

Warnings

(1)  Do not use this product on equipment and apparatus that do not allow any valve seat leakage.

This product has valve seat leakage within tolerance, and cannot be sealed completely

(Zero valve seat leakage cannot be obtained).

This product cannot be used for apparatus and facilities with considerable vibration.

Vibration may cause the product to make errors.

Cautions

Please confirm that the indications on the product name plate coincide with the specifications of
the ordered product model before usage.

  In case they do not coincide, do not use the product and contact us.

Summary of Contents for AF-7

Page 1: ...essure vessel structure specifications Boiler structure specifications 4 6 2 For Air Pressure vessel structure specifications 4 7 I n s t al la t i on 7 1 Example of piping 5 7 2 Warnings and cautions...

Page 2: ...ange JIS B 2238 Size mm 25 40 50 65 80 100 Body Carbon steel casting Material Valve valve seat Stainless steel 1 A safety valve which is so constructed that a part of the fluid blown off from the valv...

Page 3: ...mm AF 7 AF 7M Weight kg 25 25 32 16 200 9 4 0 100 85 226 231 10 40 40 50 25 490 6 6 3 120 110 273 270 20 50 50 65 32 803 8 8 0 135 120 325 321 25 65 65 80 40 1256 0 10 0 160 125 366 361 40 80 80 100 5...

Page 4: ...re 2 Structure No Name of parts No Name of parts 1 Body 14 Nut 2 Valve seat 15 Spring 3 Drain plug R3 8 16 Spindle 4 Seat ring 17 Spring chamber 7 Valve 19 Lever on Model AF 7 10 Valve holder 26 Name...

Page 5: ...ssure from the fluid coming in from the back of the valve holder back pressure adds to the pressure for the valve to close 6 Size selection tables 6 1 For steam Saturation temperature Pressure vessel...

Page 6: ...stalled improperly 4 Please make sure that the product is installed in the proper direction The product will not function if installed in an improper direction 5 Securely support and fasten the piping...

Page 7: ...f the safety valve does not affect the safety valve Installation of the flange on the safety valve inlet 1 As the valve seat is screwed on to the flange inlet there is a difference in level on the fla...

Page 8: ...be used on devices and equipment that vibrate considerably Leakage at the outlet side There is back pressure on the piping at the outlet side Review and change the piping layout Specifications of the...

Reviews: