Temperature limits

The primary limit is located such that the temperature sensitive 
switch can sense the temperature of the heat exchanger tubes. 
On single stage models the limit is mounted to the condenser 
partition panel. On two stage models the limit is mounted just 
above the inlet of the heat exchanger tubes on the right side. If 
a primary limit (LS) fault occurs (the primary limit opens due to 
excessive heat exchanger temperature), then the ICB will flash 
the appropriate code (Table 27) and monitor the primary limit. 
The UCB will energize the indoor blower and the ICB will 
energize the draft motor while the primary limit is open. When 
the primary limit closes and the call for heat still exists, the ICB 
will start the ignition sequence over and the UCB will de-
energize the blower for 45 seconds. However, the auxiliary limit 
is in series with the primary limit and it takes first control. If the 
excessive heat has been high enough to cause the auxiliary 
limit (AUX) to open, then the ICB will flash the primary limit code 
but the furnace will not retry ignition during the same call for 
heat. The auxiliary limit is of the manual reset type and is 
mounted in the upper right hand corner of the panel between 
the burner manifold and the flue gas collector box just behind 
the draft motor. If the auxiliary switch has opened, then special 
attention should be paid to the primary limit as it may be faulty 
as well. However, the auxiliary switch is sized such that multiple 
trips of the primary limit due to complete blower failure will 
cause enough heat to build up and trip the auxiliary.

If the primary limit opens three times within one hour, then the 
UCB will lock on the indoor blower and flash a code on the 
Simplicity Lite Control (Table 26) or sends error message to 
the LCD Smart Equipment™ Control.

Gas valve

The UCB monitors the gas valve (GV). Any time the UCB 
senses voltage at the GV without a call for heat for a continuous 
five-minute period, the UCB will lock on the indoor blower and a 
flash code on the UCB is initiated (Table 26). When the UCB no 
longer senses voltage at the GV the UCB will de-energize the 
indoor blower after the expiration of the indoor blower heating 
off delay.

If the voltage has been sensed at the GV for at least 15 
seconds during the fan on delay for heating and the UCB no 
longer senses voltage at the GV (W1 call for heat removed or 
an ICB fault exists), then the UCB forces the indoor blower on 
for the indoor blower heating off delay.

The gas valve is of the redundant type. If for any reason the 
main gas valve fails in the open position, then the redundant 
valve ahead of the main gas valve will shut off the flow of gas to 
both the pilot and main gas valves.

Centrifugal switch

The centrifugal switch is mounted on the end of the draft motor 
and it is an integral part of the motor assembly. On a call for 
heat, the ICB checks the centrifugal switch (CS) for open state 
before it energizes the draft motor. If it is closed, then the ICB 
will lock out the furnace and flash a code (Table 27). If open, 

then the ICB will energize the draft motor and verify that the 
switch closes before initiating the purging and ignition 
sequence. If at any time during furnace operation the 
centrifugal switch opens, then the ICB will de-energize the pilot 
and main gas valves and monitor the centrifugal switch. If the 
centrifugal switch closes and the call for heat still exists, then 
the ICB will retry the purging and ignition sequence.

Rollout switch

This temperature sensitive switch is located in the burner 
vestibule just above the right hand side of the burner assembly. 
In the event of the flame spilling out into the burner manifold 
area the rollout switch will open, the ICB will close both the 
main and pilot gas valves and flash a code (Table 27). The ICB 
will not retry the ignition sequence during the same call for heat.

Flame sense circuit

The flame sensor is mounted on the left hand side of the burner 
assembly and is positioned such that the pilot flame surrounds 
the tip of the sensor. On a call for heat the ICB checks for the 
flame sense circuit to be open. If open, then the ICB initiates the 
purging and ignition sequence. Once the pilot flame is present, 
the ICB monitors the flame sense circuit for pilot flame stability. 
If the pilot flame is unstable or lost completely, then the ICB will 
immediately close both the pilot and main gas valves. The ICB 
will retry the purging and ignition sequence. If the flame is 
unstable or lost more than 16 times during the same call for 
heat, then the ICB will lock out furnace operation for 5 minutes.

Flash codes or error messages

The UCB will initiate a flash code associated with errors within 
the system. Refer to flash a code on the Simplicity Lite Control 
(See Table 26) or sent error message to the LCD Smart 
Equipment™ Control.

Heat anticipator setpoints

It is important that the anticipator setpoint be correct. Too high 
of a setting will result in longer heat cycles and a greater 
temperature swing in the conditioned space. Reducing the 
value below the correct setpoint will give shorter “ON” cycles 
and may result in the lowering of the temperature within the 
conditioned space.

Table 23: Limit control setting

Unit

(Tons)

Capacity, MBH

Limit Control Opens, °F

Input 

Output

Direct Drive

Belt Drive

3

15 (50)

12 (40)

115 (240)

-

4

22 (75)

18 (60)

99 (210)

-

5, 6.3

29 (100)

29 (80)

-

99 (210)

Table 24: Gas heat anticipator setpoints

Gas Valve

Anticipator Setpoint

Honeywell VR8204M

0.60 amp

White-Rodgers 36E36

0.54 amp

Summary of Contents for ZF076

Page 1: ...Burner air shutter adjustment 43 Checking gas input 43 Adjustment of temperature rise 44 Troubleshooting 45 Cooling troubleshooting guide 45 Gas heat troubleshooting guide 46 Flash code troubleshooti...

Page 2: ...od 30 18 Unit dimensions rear view 31 19 Disconnect blower access location 31 20 Belt adjustment 36 21 Pressure drop across coil 37 22 Gas valve piping 40 23 Proper flame adjustment 43 24 Typical valv...

Page 3: ...parts and electrical components installation and servicing of air conditioning equipment can be hazardous Only qualified trained ser vice personnel should install repair maintain or service this equi...

Page 4: ...es refrigerant containers and recovery systems must be designed to handle R 410A If you are unsure consult the equipment manufacturer Failure to use R 410A compatible servicing equipment may result in...

Page 5: ...mbustible material 4 For use with natural gas convertible to LP with kit This product must be installed in strict compliance with the enclosed installation instructions and any applicable local state...

Page 6: ...d Filters Merv 8 4 Coil Guard CG STD Filter 5 2 Pleated Filter CG A Std Cabinet B HDF HingedFLTR Tooless DR E SSD SST Drain Pan F SSD HFD A No Economizer C Economizer w o Barometric RLF F Econ BAS Rdy...

Page 7: ...al Code CSA C22 1 2 Installation Codes CSA B149 1 3 Local plumbing and waste water codes and 4 Other applicable local codes Refer to unit application data found in this document After installation gas...

Page 8: ...air in accordance with section 5 3 of Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 Latest Edition in U S A or Sections 7 2 7 3 or 7 4 of Gas Installation Codes CSA B149...

Page 9: ...f the evaporator coil and must be kept clean or replaced with same size and type Dirty filters will reduce the capacity of the unit and will result in frosted coils or safety shutdown Minimum filter a...

Page 10: ...2 Y1 W2 W1 X R THERMOSTAT TERMINALS CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 1 4 3 1 2 4 Second stage ot required on single stage he g units Jumper is required if there is n...

Page 11: ...tolerances which must be maintained at the compressor terminals during starting and running OCC C RC G Y2 Y1 W2 W1 X R THERMOSTAT TERMINALS CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THER...

Page 12: ...led heaters are wired for single point power supply Power supply need only be brought into the single point terminal block and thermostat wiring to the low voltage terminal strip located in the upper...

Page 13: ...3 50 M3 S 0 47 0 57 0 57 0 61 CFM 1100 1200 1200 1300 4 380 415 3 50 M3 S 0 61 0 61 0 61 0 61 CFM 1300 1300 1300 1300 5 380 415 3 50 M3 S 0 75 0 75 0 75 0 75 0 75 CFM 1600 1600 1600 1600 1600 6 3 380...

Page 14: ...uitable for the purpose NEVER USE A FLAME 6 The furnace and its individual manual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at te...

Page 15: ...od slips in under the top of the access panel opening when installing Refer to Vent and Combustion Air Hood Figure 7 The vent hood is installed by inserting the top flange of the hood into the slotted...

Page 16: ...EDs at the center left of the RRS Economizer Controller indicate POWER green Lit whenever 24 volts AC power is present to the RRS Economizer Controller C and R pins FAULT red Lit then flashes during t...

Page 17: ...t available Free cooling operation When the control determines that the outside air is suitable the first stage of cooling will always be free cooling Thermostat In free cooling with a thermostat inpu...

Page 18: ...No inputs are present for non modulating power exhaust Outputs a 2 10 VDC from ECON on Economizer Expansion module b 24 vac from EX FAN to energize exhaust fan on Economizer Expansion module Operation...

Page 19: ...istor MAT parameter reports input status F C 3 65 VDC reading MAT to COM with open circuit Read only use in current control revision IN1 MAT LEDs at left on upper edge of economizer board POWER POWER...

Page 20: ...power exhaust actuator and economizer actuator Connects through circuit trace to 24V IN pin HOT ECON 2 10 VDC output for the Economizer actuator Econ parameter reports output status 0 100 Used to posi...

Page 21: ...negative for the indoor air quality sensor Connects through circuit trace to 24V IN pin COM R 24V 24 VAC hot supplied for the outdoor air quality sensor Connects through circuit trace to 24V IN pin HO...

Page 22: ...pad layout Keypad The four navigation buttons illustrated in Fig 8 are used to scroll through the menus and menu items select menu items and to change parameter and configuration settings Using the ke...

Page 23: ...E Economizer Module accessory instruction P N 1150208 UAI A 0514 included in this instruction packet for additional menu information Economizer setup and configuration Before being placed into service...

Page 24: ...ry the economizer sets the economizing mode to YES economizing is available When conditions are above the selected boundary the conditions are not good to economize and the mode is set to NO Fig 9 sho...

Page 25: ...LEFT FRONT Table 8 ZF036 076 metric Size Tons Model Weight kg Center of Gravity mm 4 point Load Location kg 6 point Load Location kg Shipping Operating X Y A B C D A B C D E F 036 3 0 ZF036 228 225 10...

Page 26: ...F 15 45 25 70 25 55 25 55 Gas Limit Setting F Direct Drive 240 210 Gas Limit Setting F Belt Drive 210 210 Gas piping connecting in 1 2 1 2 1 2 1 2 DIMENSIONS inches Length 82 1 4 82 1 4 82 1 4 82 1 4...

Page 27: ...VAP FAN DATA Quantity 1 1 Fan Size Inch 12 x 10 12 x 11 Type Centrifugal Centrifugal Motor Sheave 1VL44 IVM50 Blower Sheave AK54 AK56 Belt A35 A36 Motor HP each 1 1 2 1 1 2 RPM 1450 1450 Frame size 56...

Page 28: ...3 25 2EH04512046 12 2 2 18 5 29 4 30 415 3 50 7 8 51 5 12 1 1 3 4 24 NONE 15 3 20 2EH04510746 5 1 1 7 1 15 3 20 2EH04511046 7 5 1 10 4 19 2 20 2EH04511546 10 2 2 14 2 23 9 25 2EH04512046 14 6 2 20 3 3...

Page 29: ...as heat front view 829 325 8 1140 447 8 64 21 2 213 83 8 292 111 2 445 171 2 445 171 2 181 77 8 171 63 4 206 81 8 137 53 8 2089 821 4 165 61 2 178 7 111 43 8 165 61 2 819 321 4 819 32 1 4 mm inch 829...

Page 30: ...omizer rain hood Figure 17 Unit with fixed outdoor air motorized damper rain hood DETAIL A 699 271 2 699 271 2 41 15 8 260 101 4 1140 447 8 502 193 4 mm inch DETAIL B 454 177 8 184 71 4 699 271 2 485...

Page 31: ...th Belt Drive Option Control Box Access A B Wiring Entry See Detail B Mounting Bracket for Disconnect Switch Field Supplied Field Supplied Disconnect Switch Location Blower Motor Access Filter Access...

Page 32: ...25 LOW 0 67 645 0 63 620 0 58 595 0 53 575 CFM UNIT TONNAGE MOTOR SPEED AVAILABLE EXTERNAL STATIC PRESSURE IWG 0 20 0 30 0 40 0 50 0 60 CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS 31 HI 1699 825...

Page 33: ...25 1101 980 1130 1045 1158 1075 CFM UNIT TONNAGE AIR FLOW CFM AVAILABLE EXTERNAL STATIC PRESSURE IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM...

Page 34: ...75 1118 1150 1148 1250 1176 1360 CFM UNIT TONNAGE AIR FLOW CFM AVAILABLE EXTERNAL STATIC PRESSURE IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM...

Page 35: ...id bases and are inherently protected These motors can be selected to operate into their service factor because they are located in the moving air upstream of any heating device Table 20 Static resist...

Page 36: ...4 Knowing the pressure drop across a dry coil the actual volumetric flow rate through the unit can be determined from the curve in Pressure Drop vs Supply Air flow rate Figure 21 After readings have b...

Page 37: ...the fan off delay for cooling To be available a compressor must not be locked out due to a high or low pressure switch or freezestat trip Simplicity Lite Control or Evaporator Low Limit sensor detecti...

Page 38: ...ser fan If the call for cooling is still present at the conclusion of the ASCD the UCB will re energize the halted compressor Should a freezestat open three times within two hours of operation the UCB...

Page 39: ...and on any compressor reset or lock out Flash codes or error messages The UCB will initiate flash a code on the Simplicity Lite Control see Table 26 or sent error message to the LCD Smart Equipment Co...

Page 40: ...peration of the draft motor The UCB continues the operation of the indoor blower for a configurable amount of time after the call for heat is satisfied Two stage furnace only If a W1 only call for hea...

Page 41: ...of the main gas valve will shut off the flow of gas to both the pilot and main gas valves Centrifugal switch The centrifugal switch is mounted on the end of the draft motor and it is an integral part...

Page 42: ...installed Operating instructions Lighting the pilot and main burners 1 Turn off electric power to unit 2 Turn room thermostat to lowest setting 3 Turn gas valve knob to on position 4 Turn on electric...

Page 43: ...unction properly Burner instructions To check or change burners pilot or orifices CLOSE MAIN MANUAL SHUT OFF VALVE AND SHUT OFF ALL ELECTRIC POWER TO THE UNIT 1 Remove the screws holding either end of...

Page 44: ...e readings of both the return air and the heated air in the ducts about six feet from the furnace where they will not be affected by radiant heat Increase the blower Volumetric Flow Rate to decrease t...

Page 45: ...terminal is connected to the G terminal of the UCB and for loose wiring 10 If the thermostat and UCB are properly wired replace the UCB On a call for cooling the supply air blower motor is operating b...

Page 46: ...1 ECON terminal 13 For units with economizers If 24 volts is present at the Y1 OUT terminal check for 24 volts at the Y1 ECON terminal If 24 volts is not present check for loose wiring from the Y1 OUT...

Page 47: ...e ICB LED If it now flashes the heartbeat then the fault was a bad connection between the harness connector and the ICB connector or a broken wire exists in the harness With the harness connected to t...

Page 48: ...manual reset type If either one opens then the ICB removes power to the gas valve and the UCB energizes the indoor blower until the primary limit automatically resets or the auxiliary limit is manuall...

Page 49: ...e the motor 6 If 24 volts is not present at M2 check that 24 volts is present at the supply air blower motor terminal on the UCB If 24 volts is present at the UCB terminal check for loose wiring betwe...

Page 50: ...es for obstruction and alignment Removal procedure is described in BURNER INSTRUCTIONS on page 43 Clean or replace burner orifices and burners as needed Unit flash codes Various flash codes are utiliz...

Page 51: ...Operation 1 Flash Not Applicable 2 Flashes Control waiting ASCD1 1 These flash codes do not represent alarms 3 Flashes HPS1 Compressor Lock out 5 Flashes LPS1 Compressor Lock out 7 Flashes FS1 Compres...

Page 52: ...the UCB microprocessor connects through circuit trace to the SD 24 terminal SD 24 24 VAC hot out for factory accessory smoke detector condensate overflow and or user shutdown relay switching in serie...

Page 53: ...t indicates 24 VAC is present at C and 24V terminals FAULT Red hard lockout networking error and firmware error indicator 1 2 second on off flashing indicates one or more alarm is currently active 1 1...

Page 54: ...reading EC2 to EC2 with open circuit Used in suction line temperature safety Pinned connections on right edge of UCB RAH Return Air Humidity input from 0 10 VDC 0 100 RH sensor Input required for rehe...

Page 55: ...ut for indoor blower contactor coil indoor blower VFD enable relay coil Output with heat cool operation G input or schedule demand C1 24 VAC hot output for compressor 1 If demand is present and permis...

Page 56: ...er of the board Positive of the 15 VDC reading to C circuit for powering an optional netstat and or Multi Touch gateway C Common for SA BUS power and communication circuits Also incorporated in the J8...

Page 57: ...indicates the UCB is supplying power to the communication sub board 1 When wiring unit and other devices using the SA Bus and FC Bus see Table 29 Table 28 Smart Equipment UCB details continued Descri...

Page 58: ...5848 XIM A 0319 58 Johnson Controls Ducted Systems Typical wiring diagrams Simplicity Lite control board Figure 28 Typical ZF036 048 with Simplicity Lite control with without electric heat wiring diag...

Page 59: ...5725848 XIM A 0319 Johnson Controls Ducted Systems 59 Figure 29 Typical ZF036 048 with Simplicity Lite control with gas heat wiring diagram...

Page 60: ...5725848 XIM A 0319 60 Johnson Controls Ducted Systems Figure 30 Typical ZF060 076 with Simplicity Lite control with without electric heat wiring diagram...

Page 61: ...5725848 XIM A 0319 Johnson Controls Ducted Systems 61 Figure 31 Typical ZF060 076 with Simplicity Lite control with gas heat wiring diagram...

Page 62: ...5725848 XIM A 0319 62 Johnson Controls Ducted Systems Smart Equipment Figure 32 Typical ZF036 048 with Smart Equipment control with without electric heat wiring diagram...

Page 63: ...5725848 XIM A 0319 Johnson Controls Ducted Systems 63 Figure 33 Typical ZF036 048 with Smart Equipment control with gas heat wiring diagram...

Page 64: ...5725848 XIM A 0319 64 Johnson Controls Ducted Systems Figure 34 Typical ZF060 076 with Smart Equipment control with without electric heat wiring diagram...

Page 65: ...5725848 XIM A 0319 Johnson Controls Ducted Systems 65 Figure 35 Typical ZF060 076 with Smart Equipment control with gas heat wiring diagram...

Page 66: ...LDO VWDUW XS 7KLV FRQILGHQFH LV VXSSRUWHG E WKH GD GHDOHU SURWHFWLRQ FRYHUDJH SRUWLRQ RI RXU VWDQGDUG ZDUUDQW SROLF ZKLFK VWDWHV WKDW RKQVRQ RQWUROV XFWHG 6 VWHPV ZLOO FRYHU SDUWV DQG ODERU RQ QHZ HTX...

Page 67: ...LQ WKH IXOO RSHQ SRVLWLRQ DQG WKH IUHTXHQF GULYH LV RSHUDWLQJ DW R QRW SURFHHG ZLWK WKH HTXLSPHQW VWDUW XS ZLWKRXW WKH GHVLJQ 0 LQIRUPDWLRQ HVLJQ 6XSSO LU 0 BBBBBBBBBBBBBBBBBBBBBBBBBB HVLJQ 5HWXUQ LU...

Page 68: ...RPSOHWH LU 0RYLQJ QVSHFWLRQ RPSOHWHG 6HH 1RWHV OLJQPHQW RI GULYH FRPSRQHQWV HOW WHQVLRQ DGMXVWHG SURSHUO ORZHU SXOOH V WLJKW RQ VKDIW EHDULQJ VHW VFUHZV WLJKW ZKHHO WLJKW WR VKDIW 3UHVVXUH VZLWFK RU W...

Page 69: ...JH UHTXLUHG WR REWDLQ WKH FRUUHFW DLUIORZ DV LW QHFHVVDU WR LQFUHDVH RI GHFUHDVH WKH DLUIORZ WR PHHW WKH GHVLJQ FRQGLWLRQV I WKH PRWRU SXOOH VL H ZDV FKDQJHG PHDVXUH WKH RXWVLGH GLDPHWHUV RI WKH PRWRU...

Page 70: ...BB 5 5HWXUQ LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 0L HG LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 6XSSO LU 7HPSHUDWXUH BBBBBBBBBBBBB...

Page 71: ...BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB...

Reviews: