PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of intercon-

necting line tubing.

2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the Physical and Electrical 

Data Table.

4. Permanently mark the unit nameplate with the total system charge.  Total System Charge = Base Charge (as shipped) + adder for evap-

adder for line set.

Additional R-410A Charge / TXV Size for Various Matched Systems

Outdoor Unit 

YZE02411

YZE03611

YZE04811

YZE06011

Approved System Thermal Expansion Valve

1

1TVM902

1TVM902

1TVM4A1

1TVM905

1TVM906

Factory R-410A Charge, lbs-oz

8 - 14

8 - 8

14 - 8

14 - 0

Indoor Coil

2

TXV Kit

3

  - Additional Charge, Oz

FC/MC/PC/UC30A

+ 4

FC/MC/PC/UC30B

+ 4

FC/MC/PC32A

+ 6

FC/MC/PC35B

+ 6

+ 0

FC/MC/PC35C

+ 6

+ 0

FC/MC/PC/UC36A

+ 5

FC/MC/PC/UC36B

+ 5

FC/MC/PC36C

+ 5

FC/MC/PC/UC42B

+ 12

+ 0

FC/MC/PC/UC42C

+ 12

+ 0

FC/MC/PC/UC48C

+ 14

FC/MC/PC/UC48D

+ 14

FC/PC/UC60C

+ 9

+ 9

FC/MC/PC/UC60D

+ 9

+ 9

FC/MC62D

+ 17

+ 16

HC30

+  4

HC36

+  6

HC42

+ 12

HC60

+ 9

+ 9

HD24

HD36

+    6

HD48

+ 10

HD60

+ 9

+ 9

AV24

+  4

AV36

+ 12

+ 0

AV/SV48

+ 17

+ 9

AV/SV60

+ 9

+ 9

F*FV060

+ 9

+ 9

FOOTNOTES:

1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit  2FD06700224.
2. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
3.

A

 TXV kit must be used with these coils to obtain system performance.

Note: If a TXV is factory installed on the coil, it must be replaced with the listed TXV.

Summary of Contents for YZE024 THRU 060

Page 1: ...wder paint topcoat is applied over a baked on primer using a galvanized zinc coated steel base material The result is a finish that has been proven in testing to provide 33 greater durability than con...

Page 2: ...3 250 3 300 3 050 3 100 Coil Face Area Sq Ft 17 15 20 58 20 58 20 58 Rows Deep 1 1 2 2 Fins Inch 22 22 22 22 Liquid Line Set OD Field Installed 3 8 3 8 3 8 3 8 Vapor Line Set OD Field Installed 3 4 3...

Page 3: ...proved System Thermal Expansion Valve1 1TVM902 1TVM902 1TVM4A1 1TVM905 1TVM906 Factory R 410A Charge lbs oz 8 14 8 8 14 8 14 0 Indoor Coil2 TXV Kit3 Additional Charge Oz FC MC PC UC30A 4 FC MC PC UC30...

Page 4: ...75 12 70 2 1200 35 4 24 2 12 00 YZE04811 AV48 24 1 1135 33 2 23 5 15 00 13 30 2 1600 45 0 32 8 12 50 AV SV 60 24 1 1135 33 2 23 5 15 00 13 30 2 1600 45 0 32 8 12 50 F FV060 24 1 1000 33 2 23 5 15 50 1...

Page 5: ...P C V 9 B12 HC36 17 1 475 17 4 12 0 14 50 12 60 2 800 24 0 19 0 12 00 P C V 9 B12 HD36 17 1 475 17 9 12 2 14 50 12 75 2 800 24 0 19 2 12 00 YZE03611 P C V 9 B12 FC MC PC35B 17 1 770 24 2 16 2 14 50 12...

Page 6: ...8 11 50 P C V 9 D20 HC60 24 1 850 32 2 21 9 15 00 12 75 2 1610 45 5 35 2 11 50 PV8 C20 HC60 21 1 850 32 2 21 9 15 00 12 75 2 1610 45 5 35 2 11 50 P C V 9 D20 HD60 24 1 850 32 0 21 6 15 00 12 50 2 1610...

Page 7: ...3 30 2 775 24 0 15 5 8 2 3 36 2 650 23 0 14 5 8 05 3 12 YZE03611 AV36 1 775 23 6 3 60 2 1200 33 0 20 8 8 50 3 70 2 775 29 6 19 7 8 40 3 30 AV48 1 775 23 6 3 60 2 1200 33 0 20 8 8 50 3 70 2 775 29 6 1...

Page 8: ...ER MODEL COIL1 MODEL HEATING STAGE RATED CFM NET MBH HSPF COP 47 47 OD 17 OD HEATING CAPACITY With Variable Speed Furnaces UNIT MODEL VARIABLE SPEED FURNACE MODEL COIL MODEL1 W HEATING STAGE RATED CFM...

Page 9: ...C16 FC MC PC UC42C 21 1 650 23 2 3 56 2 1200 33 0 20 8 8 50 3 70 2 650 29 8 19 9 8 40 3 30 PV8 C16 FC MC PC UC42C 21 1 650 23 2 3 56 2 1200 33 0 21 0 8 50 3 70 2 650 29 8 19 9 8 40 3 30 PV8 C20 FC MC...

Page 10: ...8 C20 FC PC UC60C 21 1 1030 37 0 3 22 2 1730 54 5 32 0 8 05 3 48 2 1030 49 5 29 6 7 85 3 20 P C V 9 C20 FC PC UC60C 21 1 990 36 8 3 20 2 1640 54 5 31 6 8 00 3 46 2 990 49 5 29 2 7 80 3 18 P C V 9 D20...

Page 11: ...rmostats A wide selection of matching thermo stats is available to provide features required for any installa tion 3H 2C non programmable digital thermostat 3H 2C auto manual changeover electronic pro...

Page 12: ...14 0 14 2 11 3 K W 1 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 105 T C 16 1 16 0 15 2 17 1 18 6 16 8 16 4 15 5 17 4 18 8 17 5 16 8 15 9 17 6 19 0 S C 14 6 14 8 12 1 12 5 9 9 15 2 15 5...

Page 13: ...23 8 19 7 19 9 15 7 K W 1 9 1 9 1 9 2 0 2 0 1 9 2 0 1 9 2 0 2 0 2 0 2 0 1 9 2 0 2 0 105 T C 21 3 21 1 20 0 22 5 24 1 22 4 22 0 20 5 23 2 24 7 23 4 22 8 21 0 23 8 25 3 S C 20 2 20 0 16 4 16 8 13 2 21 0...

Page 14: ...3 14 2 20 4 20 4 17 4 18 0 14 5 K W 2 3 2 3 2 3 2 3 2 2 2 3 2 3 2 3 2 3 2 2 2 3 2 3 2 3 2 3 2 2 115 T C 18 7 19 5 19 4 21 5 24 2 19 1 19 8 19 6 21 7 24 3 19 5 20 2 19 9 21 9 24 5 S C 18 4 18 3 15 4 16...

Page 15: ...24 3 19 4 29 7 29 7 24 6 25 3 19 7 K W 3 2 3 2 3 2 3 3 3 3 3 2 3 3 3 2 3 3 3 4 3 3 3 3 3 2 3 3 3 4 115 T C 26 7 27 9 27 7 30 2 33 5 27 7 28 5 28 0 30 7 33 8 28 6 29 1 28 3 31 2 34 2 S C 26 6 26 0 22 3...

Page 16: ...2 2 2 2 2 2 2 2 95 T C 28 0 28 7 29 1 32 9 37 3 28 4 29 0 29 4 33 2 37 7 28 7 29 2 29 6 33 5 38 0 S C 27 9 25 9 22 5 22 8 18 3 28 3 26 5 23 1 23 5 18 7 28 7 27 1 23 6 24 2 19 2 K W 2 6 2 6 2 6 2 5 2 5...

Page 17: ...4 3 4 3 4 3 5 3 6 95 T C 39 0 40 2 40 8 45 6 50 8 39 6 40 7 41 2 46 0 51 2 40 2 41 1 41 6 46 3 51 5 S C 39 7 38 4 33 3 33 3 26 1 40 3 39 4 34 3 34 4 26 8 40 8 40 3 35 3 35 5 27 4 K W 3 6 3 7 3 7 3 7 3...

Page 18: ...2 9 2 9 2 9 2 9 2 9 2 9 95 T C 32 5 33 7 33 9 38 0 42 3 33 0 34 1 34 2 38 5 42 5 33 5 34 5 34 5 39 0 42 7 S C 33 3 31 4 26 6 26 8 20 8 33 8 32 1 27 2 27 4 21 4 34 3 32 7 27 8 28 0 22 1 K W 3 3 3 3 3...

Page 19: ...6 4 7 4 6 4 6 4 6 4 7 4 7 95 T C 47 2 48 6 48 7 53 6 58 7 47 8 49 0 49 1 54 0 58 9 48 4 49 5 49 4 54 4 59 1 S C 47 8 45 3 38 4 38 0 29 5 48 3 46 0 39 4 38 9 29 8 48 8 46 7 40 4 39 7 30 1 K W 4 9 4 9 4...

Page 20: ...3 1 4 2 6 12 4 1 4 2 7 70 10 7 1 6 1 9 10 9 1 6 2 0 11 1 1 6 2 1 80 9 2 1 8 1 5 9 5 1 8 1 5 9 8 1 8 1 6 10 60 10 5 1 4 2 2 10 7 1 4 2 3 10 8 1 3 2 4 70 9 4 1 5 1 8 9 6 1 5 1 9 9 8 1 5 2 0 80 8 3 1 6 1...

Page 21: ...8 2 7 16 3 1 7 2 8 70 15 6 2 0 2 3 15 6 1 9 2 4 15 6 1 9 2 4 80 14 3 2 1 2 0 14 6 2 1 2 1 15 0 2 1 2 1 10 60 13 6 1 7 2 3 13 4 1 7 2 3 13 3 1 7 2 3 70 13 3 2 1 1 9 13 3 2 0 1 9 13 3 2 0 2 0 80 13 1 2...

Page 22: ...2 0 1 7 11 8 2 0 1 7 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil MBH KW COP AV36 1 00 1 00 1 00 AV48 1 00 1 00 1 00 MV12B FC MC35B 1 00 1 00 1 00 MV12B FC MC42B...

Page 23: ...2 6 2 1 20 5 2 6 2 3 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil MBH KW COP AV36 1 00 1 00 1 00 AV48 1 01 1 00 1 01 MV12B FC MC35B 1 00 1 00 1 00 MV12B FC MC42B...

Page 24: ...2 8 30 60 25 6 2 2 3 4 25 5 2 2 3 4 25 5 2 2 3 4 70 24 3 2 6 2 8 24 3 2 6 2 8 24 3 2 6 2 8 80 23 0 2 9 2 3 23 0 2 9 2 3 23 1 2 9 2 3 17 60 19 7 2 3 2 6 19 6 2 2 2 6 19 4 2 2 2 6 70 17 3 2 6 2 0 17 2 2...

Page 25: ...3 2 30 60 35 5 3 0 3 5 34 4 2 9 3 5 33 3 2 9 3 4 70 33 9 3 2 3 1 33 6 3 2 3 0 33 3 3 3 3 0 80 32 3 3 5 2 7 32 8 3 6 2 7 33 2 3 7 2 7 17 60 28 5 2 9 2 9 28 6 2 8 3 0 28 8 2 8 3 0 70 27 3 3 3 2 5 27 6...

Page 26: ...8 3 6 2 7 30 60 24 7 2 9 2 5 23 3 2 8 2 4 21 9 2 8 2 3 70 25 8 3 3 2 3 24 9 3 3 2 2 23 9 3 2 2 2 80 26 8 3 7 2 1 26 4 3 7 2 1 26 0 3 6 2 1 17 60 22 6 2 8 2 4 22 4 2 8 2 4 22 1 2 7 2 4 70 20 5 3 1 2 0...

Page 27: ...7 5 4 9 2 9 30 60 42 5 3 8 3 3 39 9 3 7 3 1 37 3 3 7 2 9 70 38 8 4 0 2 8 39 1 4 1 2 8 39 4 4 2 2 8 80 35 0 4 3 2 4 38 3 4 5 2 5 41 6 4 6 2 6 17 60 34 3 3 6 2 8 32 3 3 5 2 7 30 4 3 4 2 6 70 34 2 4 1 2...

Page 28: ...nge without notice Printed in U S A 246750 YTG L 0408 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 246750 YTG K 0108 Johnson Controls Unitary Products 5005 York Drive Norman O...

Reviews: