
JOHNSON CONTROLS
61
SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION
FORM 161.01-OM1
ISSUE DATE: 6/8/2018
3
PROGRAMMABLE
BUTTON
ACCESS LEVEL
DESCRIPTION
Pulldown
Demand Limit
Operator
Allows the user to specify the current limit value (as a percentage of Full Load
Amps) to which the chiller will be limited during the specified pulldown limit time.
This value will override the Input Current Limit value during this time period. This
function is used to provide energy savings following chiller start-up. Pulldown de-
mand limit is ignored in BAS control source because the BAS system is expect-
ed to use its algorithms to reset current limit as required in that operating mode.
Pulldown
Demand Time
Operator
Allows the user to set a period of time for which the pulldown demand limit will
be in effect after the chiller starts.
Local Cooling
Setpoint
Operator
This value allows the user to define the Leaving Chilled Liquid Temperature that
is to be maintained by the chiller. It is programmable over the range of 36.0°F
to 72.0 °F (2.2 °C to 22.2 °C ) (water) or 10.0°F to 72.0°F (-12.2 °C to 22.2 °C)
(brine). Default = 45°F.
Leaving Chilled
Liquid
Temperature
Cycling Offset -
Shutdown
Operator
Programmable over the range of 1.0°F to 70.0°F (-17.2 °C to 21.1 °C). Default =
4°F (-15.6 °C).
Leaving Chilled
Liquid
Temperature
Cycling Offset -
Restart
Operator
Programmable over the range of 0.0°F to 37.0°F (-17.8 °C to 2.8 °C. Default =
0.0°F (-17.8°C).
Operator
Generates Setpoints print report.
NAVIGATION
NAVIGATION
BUTTON
DESCRIPTION
Home
Causes an instant return to the Home Screen.
Setup
Moves to the subscreen allowing setup of general system parameters.
Remote Control
Navigates to the subscreen allowing setup of the Remote Control BAS interface.
Summary of Contents for YZ MODEL A
Page 10: ...JOHNSON CONTROLS 10 FORM 161 01 OM1 ISSUE DATE 6 8 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 142: ...JOHNSON CONTROLS 142 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...
Page 143: ...JOHNSON CONTROLS 143 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...
Page 144: ...JOHNSON CONTROLS 144 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...
Page 145: ...JOHNSON CONTROLS 145 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...
Page 146: ...JOHNSON CONTROLS 146 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...
Page 147: ...JOHNSON CONTROLS 147 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...
Page 148: ...JOHNSON CONTROLS 148 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...
Page 149: ...JOHNSON CONTROLS 149 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...
Page 150: ...JOHNSON CONTROLS 150 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...
Page 151: ...JOHNSON CONTROLS 151 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...
Page 152: ...JOHNSON CONTROLS 152 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...
Page 153: ...JOHNSON CONTROLS 153 Appendix Material Safety Data Sheets FORM 161 01 OM1 ISSUE DATE 6 8 2018...
Page 154: ...JOHNSON CONTROLS 154 FORM 161 01 OM1 ISSUE DATE 6 8 2018 Appendix Material Safety Data Sheets...