(WPEVKQPCPF%QPVTQN
'HVFULSWLRQRI(DFK&RQWURO2SHUDWLRQ
●
Indoor Unit
1Temperature Parameters
ƹ
Indoor preset temperature (Tpreset)
ƹ
Indoor ambient temperature (Tamb.)
2 Basic functions (The temperature in this manual is expressed by Centigrade. If Fahrenheit is used, the switchover between them is
Tf=TcX1.8+32.)
Once the compressor is energized, there should be a minimum interval of 3 minutes between two start-ups. But if the unit is
de-energized and then energized, the compressor can restart within 3 minutes.
2.1 Cooling mode
2.1.1 Cooling conditions and process
When Tamb. ≥Tpreset, the unit starts cooling operation. In this case, the compressor and the outdoor fan operate and the indoor fan
operates at set speed.
When Tamb. ≤Tpreset-3
ć
, the compressor and the outdoor fan stop while the indoor fan runs at set speed.
When Tpreset-3
ć˘
Tamb.
˘
Tpreset, the unit will maintain its previous running status.
In cooling mode, temperature setting range is 16
̚
30
ć
; the indoor unit displays operation icon, cooling icon and set temperature.
2.1.2 When outdoor unit has malfunction or stops for protection, indoor unit will keep previous operation status and display malfunction
code.
2.1.3 The protection status is as the same as the cooling mode.
2.2 Dry Mode
2.2.1 Dry Conditions and Process
2.3 Heating mode (not available for cooling only type)
2.3.1 Heating conditions and process
When Tamb. ≤2
ć
, the unit starts heating operation. In this case, compressor and outdoor fan operate simultaneously; the
indoor fan operates at cold-air prevention mode.
When Tamb≥5
ć
, the compressor and outdoor fan stop operation; the indoor fan blows residual heat.
When T
preset
+2
ć˘
T
amb.
˘
T
preset
+5
ć
, the unit will maintain its previous running status.
Under this mode, temperature setting range is 16
̚
30
ć
; the indoor unit displays operation icon, heating icon and set temperature.
Tpreset
Tpreset –3 ˚C
Compressor
Outdoor fan
Indoor fan
Run
Tamb.
Stop
Stop cooling
Start cooling
Previous running status
≥ 6 min.
≥ 3 min.
≥ 6 min.
Set fan speed
When Tamb.>Tpreset, the unit operates in cooling mode. Meanwhile, compressor and outdoor fan operate, and indoor fan operates at
set fan speed (low fan speed, quiet fan speed or auto quiet fan speed).When Tpreset-2
℃<
Tamb. ≤Tpreset, the unit keeps previous
operation status.When Tamb. ≤Tpreset-2
℃
, compressor, outdoor fan and indoor fan operate at set fan speed (low fan speed, quiet fan
speed or auto quiet fan speed).Under this mode, the temperature setting range is 16
~
30
℃
. Display displays operation icon, drying icon
and set temperature.
Tpreset
Tpreset –2˚C
Compressor
Outdoor fan
Indoor fan
Run
Tamb.
Stop
Stop cooling
Start cooling
Previous running status
≥ 6 min.
≥ 3 min.
≥ 6 min.
Set fan speed
Summary of Contents for YWHJXH012BAMK-FX
Page 12: ...QPUVTWEVKQP 8KGYU 8QLW PP 4 5 6 0RGHO 3DQHO 0RGHOV 4 5 6 YWHJXH009BAMK FX YWHJXH012BAMK FX...
Page 13: ...QPUVTWEVKQP 8KGYU 2XWGRRU 8QLW 8QLW PP 8QLW PP 0RGHOV YWHJYH009BAMKA X 0RGHOV YWHJYH012BAMKA X...
Page 49: ...6TQWDNGUJQQVKPI QGRRU IDQ GRHV QRW RSHUDWH DC motor interface sketch...
Page 51: ...6TQWDNGUJQQVKPI XPSHU FDS PDOIXQFWLRQ Jumper cap interface sketch...
Page 53: ...6TQWDNGUJQQVKPI RPPXQLFDWLRQ PDOIXQFWLRQ Indoor unit communication indicator sketch...