All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” 
to 0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 
1.0” w.c. external static pressure is not recommended.

NOTE: 

At some settings, LOW COOL  airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Con-

sult the instructions for the electronic air cleaner for further details.

Blower Performance CFM - Any Position

High / Low Speed Cooling CFM

060B12 080B12 

Jumper 

Settings 

Hi Cool 

Lo Cool 

Hi Cool 

Lo Cool 

COOL Jumper 

ADJ Jumper 

1305 850 1290 840  H 

1100 715 1090 710  MH  B 

1065 690 1015 660  H 

1000 650 1000 650  MH  A 

960 625 960 625  H 

760 495 760 495  ML  B 

900 585 900 585 MH  C 

660 430 660 430  L 

690 450 680 445  ML  A 

600 400 600 400  L 

620 400 620 400  ML  C 

550 400 540 400  L 

High / Low Speed Cooling CFM

080C16 100C16 

Jumper 

Settings 

Hi Cool 

Lo Cool 

Hi Cool 

Lo Cool 

COOL Jumper 

ADJ Jumper 

1670 1085 1655 1075  H 

1295 840 1275 820  MH  B 

1385 900 1345 875  H 

1175 765 1160 755  MH  A 

1245 810 1210 785  H 

995  645 1000 650  ML  B 

1055 685 1045 680  MH  C 

935 605 955 620  L 

905 590 910 590  ML  A 

850 550 870 565  L 

815 530 815 530  ML  C 

765 500 785 510  L 

High / Low Speed Cooling CFM

100C20 120D20 

Jumper 

Settings 

Hi Cool 

Lo Cool 

Hi Cool 

Lo Cool 

COOL Jumper 

ADJ Jumper 

2215 1440 2180 1415  H 

1765 1145 1760 1140  MH 

1820 1180 1800 1170  H 

1605 1040 1595 1035  MH 

1635 1060 1620 1050  H 

1270 825 1255 815  ML  B 

1445 940 1435 935  MH  C 

1055 685 1050 680  L 

1155 750 1160 755  ML  A 

960 620 960 615  L 

1040 675 1035 670  ML  C 

860 560 840 545  L 

Summary of Contents for YP9C Series

Page 1: ...irculating blower Modulating operation from 100 to 35 input in 100 increments with nearly constant temperature rise Easily applied in upflow horizontal left or right or downflow installation with minimal conversion necessary Compact easy to install ideal height 33 tall cabinet ECM variable speed drive for cooling SEER enhancement improved comfort with optional airflow delay profiles and continuous...

Page 2: ... B 17 1 2 16 3 8 13 1 4 122 YP9C080B12MP11 1200 B 17 1 2 16 3 8 14 3 4 126 YP9C080C16MP11 1600 C 21 19 7 8 16 1 2 136 YP9C100C16MP11 1600 C 21 19 7 8 18 1 4 142 YP9C100C20MP11 2000 C 21 19 7 8 18 1 4 145 YP9C120D20MP11 2000 D 24 1 2 23 3 8 21 3 4 156 Ratings Physical Electrical Data Models Input Max Min Output Max Min AFUE Nominal Airflow Total Unit Amps Air Temp Rise Max Input Air Temp Rise Min I...

Page 3: ...BR0517 or 1BR0617 For 17 1 2 cabinets 1BR0521 or 1BR0621 For 21 cabinets 1BR0524 or 1BR0624 For 24 1 2 cabinets 1BR05xx series are galvanized steel filter racks 1BR06xx are pre painted steel filter racks to match the appearance of the fur nace cabinet COMBUSTIBLE FLOOR BASE KIT For installation of these furnaces in downflow applications directly onto combustible flooring material These kits are re...

Page 4: ...mper Settings Hi Cool Lo Cool Hi Cool Lo Cool COOL Jumper ADJ Jumper 1305 850 1290 840 H B 1100 715 1090 710 MH B 1065 690 1015 660 H A 1000 650 1000 650 MH A 960 625 960 625 H C 760 495 760 495 ML B 900 585 900 585 MH C 660 430 660 430 L B 690 450 680 445 ML A 600 400 600 400 L A 620 400 620 400 ML C 550 400 540 400 L C High Low Speed Cooling CFM 080C16 100C16 Jumper Settings Hi Cool Lo Cool Hi C...