background image

User's Manual

New Released

YMGE36BNO--MS-X
YMGE48BNO--MS-X
YMGE60BNO--MS-X

Issue Date

R-410

Form: MMGEBNO--MS-X-170131

Rooftop Package

50HZ R-410a Heat Pump

Issue Date

Jan 31st, 2017

Summary of Contents for YMGE36BNO-MS-X

Page 1: ...User s Manual New Released YMGE36BNO MS X YMGE48BNO MS X YMGE60BNO MS X Issue Date R 410 Form MMGEBNO MS X 170131 Rooftop Package 50HZ R 410a Heat Pump Issue Date Jan 31st 2017 ...

Page 2: ...User s Manual New Released Multi Splits High Wall DC Inverter Rooftop Package Type YMGE36BNO MS X YMGE48BNO MS X YMGE60BNO MS X Issue Date Jan 1st 2017 R 410 ...

Page 3: ...flow as per installation conditions This unit is ideal for Single story and Double story houses as they offer high static With its easy installation and simple controlling system this products is suitable for Factories Shopping malls Multiplex Hotels etc At present the unit capacity range goes from 3 to 5 tons A lot of information regarding the design installation of this system is provided in thi...

Page 4: ... copper tube The appliance should not be used by children without supervision This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capcabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not p...

Page 5: ...3 DIMENSIONAL DATA Figure 1 I O manual 2 ...

Page 6: ...the roof Flashing is required The hole in the roof must be prepared in advance of installing the unit Secure the ducts to the roof Place the unit on the frame or roof curb Insulate any ductwork outside of the structure with at least two 2 inches of insulation and then weatherproof There must be a weatherproof seal where the duct enters the structure Secure the unit to the frame or roof curb Comple...

Page 7: ...ections are tight Replace and secure all electrical box covers and access doors before leaving the unit or turning on the power to the unit ELECTRICAL POWER It is important that proper electrical power be available for the unit Voltage variation should remain within the limits stamped on the unit nameplate DISCONNECT SWITCH Provide an approved weatherproof disconnect either on the side of the unit...

Page 8: ...N BROWN BLUE BLUE Y R G ROOFTOP PACKAGE UNIT ROOFTOP PACKAGE UNIT B C RED RED Y C B GREEN G Control Wiring for H P systems CAUTION If the supply cord is damaged it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard An all pole disconnection device which has at least 3mm separation distance in all pole and a residual current device R...

Page 9: ... 4 WAY VALVE BLUE BLUE BLACK BROWN BROWN RED BLUE YELLOW GREEN BROWN CN37 BLACK R S T NC COM NO POWER PROTECTOR WHITE BLUE RED Xs6 XP6 RED RED MAIN CONTROL BOARD L PRO T6 CN4 RT2 CN2 24V CN3 CN13 21 22 KM1 A1 3 1 5 A2 2 4 6 COMP RED FAN2 CAP2 FAN1 CAP1 WHITE WHITE Y G C N XT1 B A Y G POWER CN32 CN34 CN35 CN36 CN6 CN15 XP5 XS5 XP4 XS4 RT3 RT4 CN8 CN7 Y G V U Y G W RED WHITE BLUE RED BLACK BLACK BLU...

Page 10: ...ARD L PRO T6 CN4 RT2 CN2 24V CN3 CN13 21 22 KM1 A1 3 1 5 A2 2 4 6 COMP RED FAN2 CAP2 FAN1 CAP1 BROWN BROWN Y G C N XT1 B A Y G POWER CN32 CN34 CN35 CN36 CN6 CN15 XP5 XS5 XP4 XS4 RT3 RT4 CN8 CN7 Y G V U Y G W RED WHITE BLUE RED BLACK BLACK BLUE PURPLE RED BLUE BROWN CN1 RED BLACK B C R Y G XT2 BLACK BLACK WHITE BLUE WHITE BLUE T5 XS1XP1 XS2XP2 K1 K2 XS3 XP3 CT1 TRANSFORMER 24V 4 WAY TERMINAL LOW PR...

Page 11: ...fice CONDENSER FAN DAT A Quantity 1 1 1 Fan diameter mm 550 550 550 Type Drive type Prop Prop Prop Direct Direct Direct No Speeds 1 1 1 Number of motors RPM Nominal total CFM 940 1050 1050 3180 3600 3200 1 1 1 DIRECT DRIVE EVAP FAN DAT A Quantity 1 1 1 Fan diameter in 11 1 11 1 11 1 Type Drive type Direct Direct Direct No Speeds 2 3 3 Number of motors RPM Nominal total CFM 850 1090 1140 1 1 1 Leng...

Page 12: ...817 830 848 343 331 315 1 56 1 5 1 4 1375 649 1121 659 3 0 1290 609 1140 640 3 0 736 1651 779 1601 756 1554 733 1503 709 1444 682 985 1015 1043 1073 1099 732 720 706 691 675 3 4 3 3 3 2 3 2 3 1 1689 797 1641 775 1583 747 1521 718 1088 1114 1145 1164 3 7 3 7 3 6 3 5 1767 834 1717 810 1656 782 1580 746 1160 1192 1206 1221 914 895 875 848 4 2 4 1 4 0 3 9 1786 843 1733 818 1039 1066 3 9 3 8 812 796 77...

Page 13: ...99 3 01 3 02 3 04 TC 26 3 30 1 33 7 35 3 26 8 30 7 34 4 36 0 SC 15 7 19 5 23 1 24 7 16 0 19 9 23 6 25 2 PI 2 98 3 00 3 01 3 03 3 01 3 03 3 04 3 06 TC 27 0 30 9 34 7 37 1 27 5 31 5 35 4 37 9 SC 10 9 14 8 18 6 21 1 11 1 15 1 19 0 21 5 PI 2 99 3 01 3 02 3 04 3 02 3 04 3 05 3 07 TC 21 1 24 7 28 0 30 2 21 5 25 2 28 6 30 8 SC 19 1 22 7 26 1 28 2 19 5 23 2 26 6 28 8 PI 3 24 3 25 3 27 3 29 3 27 3 29 3 30 ...

Page 14: ...33 1 38 2 43 4 46 8 33 8 39 0 44 3 47 7 SC 13 6 18 6 23 7 27 0 13 9 19 0 24 2 27 6 14 2 19 4 24 7 28 2 PI 5 09 5 12 5 14 5 17 5 14 5 17 5 19 5 22 5 19 5 22 5 25 5 27 TC 24 4 29 2 33 8 36 7 24 9 29 8 34 5 37 4 25 4 30 4 35 2 38 1 SC 24 2 29 0 33 6 36 5 24 7 29 6 34 3 37 2 25 2 30 2 35 0 37 9 PI 5 47 5 50 5 53 5 55 5 53 5 55 5 58 5 61 5 58 5 61 5 64 5 67 TC 26 6 31 6 36 6 39 8 27 1 32 2 37 3 40 6 27...

Page 15: ...39 2 45 3 51 5 55 5 40 0 46 2 52 5 56 6 SC 16 1 22 1 28 1 32 1 16 5 22 5 28 7 32 7 16 8 23 0 29 3 33 4 PI 6 00 6 03 6 07 6 10 6 07 6 10 6 13 6 16 6 13 6 16 6 19 6 22 TC 28 7 34 5 39 9 43 3 29 3 35 2 40 8 44 2 29 9 35 9 41 6 45 1 SC 28 5 34 3 39 7 43 1 29 1 35 0 40 6 44 0 29 7 35 7 41 4 44 9 PI 6 46 6 49 6 52 6 56 6 52 6 56 6 59 6 62 6 59 6 62 6 66 6 69 TC 31 4 37 3 43 3 47 0 32 0 38 1 44 2 48 0 32...

Page 16: ...g above room temperature Do not de energize the main power disconnect except when unit is to be serviced Power is required to keep the heat pump compressor warm and boil off refrigerant in the compressor 11 SYSTEM OPERATION LED DISPLAY The control would display any fault code that is currently active using the LED The control will display the fault code when the LEDS are flashing quickly there is ...

Page 17: ... To clean the coil vertically i e with the fins stroke the coil surface with a soft bristled brush Be sure to keep all vegetation away from the condenser coil area MAINTENANCE PERFORMED BY SERVICEMAN COOLING SEASON To keep your unit operating safely and efficiently the manufacturer recommends that a qualified serviceman check the entire system at least once each year and any other time that you fe...

Page 18: ...MD14IU 021EW 202000172582 ...

Page 19: ...更改内容 此页不做菲林 试产整改 更换说明书中接线铭牌 1 a版本升b版本更改说明 更换说明书中60K能力标称 2 b版本升c版本更改说明 更换说明书中变工况表及故障代码表 3 c版本升d版本更改说明 更换说明书中风量参数表 4 d版本升e版本更改说明 ...

Page 20: ...2016 Johnson Controls Inc www johnsoncontrols com Doc No MMGEBNO MS X 170131 ...

Reviews: