Section 3 - Dimensions, nozzle arrangements, and weights
Table 2 -
Approximate unit weight* (max tube count using 150 psi compact waterboxes)
Compressor
Evaporator
Condenser
Shipping weight,
lb (kg)
Operating weight,
lb (kg)
Est. refrigerant
charge, lb (kg)
M1-197FAB
EA2510
CA2110
11770 (5339)
12740 (5779)
555 (255)
EA2510
CA2510
12790 (5802)
14070 (6383)
610 (280)
EA2514
CA2514
14970 (6791)
16620 (7539)
860 (390)
M2-205FAB
EA2510
CA2110
11790 (5348)
12760 (5788)
555 (255)
EA2510
CA2510
12810 (5811)
14090 (6392)
610 (280)
EA2514
CA2514
14990 (6800)
16630 (7544)
860 (390)
Note
:
Refrigerant charge quantity and weights will vary based on tube count.
Shipping weight based on Form 1 shipment.
*
Refer to product drawings for detailed weight information.
Table 3 -
Evaporator marine waterbox weights (to be added to standard unit weights shown on
)
Evaporator
Shipping weight increase, lb (kg)
Operating weight increase, lb (kg)
1-pass
2-pass
3-pass
1-pass
2-pass
3-pass
EA2510
702 (318)
365 (170)
737 (334)
1192 (540)
561 (254)
1130 (515)
EA2514
702 (318)
365 (170)
737 (334)
1192 (540)
561 (254)
1130 (515)
Table 4 -
Condenser marine waterbox weights (to be added to standard unit weights shown on
)
Condenser
Shipping weight increase, lb (kg)
Operating weight increase, lb (kg)
1-pass
2-pass
3-pass
1-pass
2-pass
3-pass
CA2110
557 (263)
269 (122)
551 (249)
996 (452)
413 (187)
843 (382)
CA2510
797 (361)
403 (183)
805 (370)
1453 (659)
708 (321)
1400 (635)
CA2514
797 (361)
403 (183)
805 (370)
1453 (659)
708 (321)
1400 (635)
Weights