SECTION 7 – UNIT CONTROLS
FORM 150.73-NM2
ISSUE DATE: 09/07/2020
7
SETPOINTS KEYS
00069VIP
Programming of the cooling setpoints, daily schedule,
and safeties is accomplished by using the keys located
under the SETPOINTS section.
The three keys involved are labeled COOLING
SETPOINTS, SCHEDULE/ADVANCE DAY, and
PROGRAM.
Following are instructions for programming the respec-
tive setpoints. The same instruction should be used to
view the setpoints with the exception that the setpoint
will not be changed.
Cooling Setpoints
The Cooling setpoint and Range can be programmed
by pressing the COOLING SETPOINTS key. After
pressing the COOLING SETPOINTS key, the Cooling
Mode (Discharge Air Temperature or Suction Pressure
Control) will be displayed for a few seconds, and then
the setpoint entry screen will be displayed.
Unit must first be checked for "Unit
Type - Condensing Unit" under the
Option Key to allow programming of
appropriate setpoints. This is accom-
plished by the jumper between J11-7
and J11-12 on the I/O Board.
Following are the four possible messages that can be
displayed after pressing the COOLING SETPOINT
key, indicating the cooling mode:
L O C A L D I S C H A R G E
A I R T E M P C O N T R O L
This message indicates that the cooling setpoint is un-
der LOCAL control. That is, the cooling setpoint is
controlling to the
locally
programmed setpoint. The
message also indicates that the control point is based
on Discharge Air temperature leaving the evaporator
coil.
L O C A L S U C T I O N
P R E S S U R E C O N T R O L
This message indicates that the cooling setpoint is un-
der LOCAL control (the cooling setpoint is controlling
to the
locally
programmed cooling setpoint). However,
unlike the previous message, it is now indicating that
the control point is based on Suction Pressure.
R E M O T E D I S C H A R G E
A I R T E M P C O N T R O L
This message indicates that the cooling setpoint is un-
der REMOTE control. When under remote control, the
Summary of Contents for YLUA0248 Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...