SECTION 9 – SERVICE AND TROUBLESHOOTING
FORM 150.73-NM1
ISSUE DATE: 09/04/2020
9
TABLE 37 -
PRESSURE TRANSDUCERS
0-400 PSIG SUCTION
PRESSURE TRANS-
DUCER
0-600 PSIG DISCHARGE
PRESSURE TRANS-
DUCER
PRESSURE
PSIG
VOLTAGE
VDC
PRESSURE
PSIG
VOLTAGE
VDC
0
0.5
0
0.5
50
1.0
75
1.0
100
1.5
150
1.5
150
2.0
225
2.0
200
2.5
300
2.5
250
3.0
375
3.0
300
3.5
450
3.5
350
4.0
525
4.0
400
4.5
600
4.5
Red Wire = 5V, Black wire = 0V, White/Green Wire = signal
TEST POINTS:
Suction Pressure:
System 1: ....................................Microboard J7-10 to J7-9
System 2: ....................................Microboard J9-10 to J9-9
DISCHARGE PRESSURE:
System 1: ....................................Microboard J7-11 to J7-7
System 2: ....................................Microboard J9-11 to J9-7
V = (Pressure in psig x .01) + .5
or
V = (Pressure in BARG x .145) + .5
where V = dc voltage output
Pressure = pressure sensed by transducer
The I/O board connections for the Discharge Transduc-
ers:
System 1 Discharge Transducer
J7-6 = +5 VDC regulated supply to transducer.
J7-11 = VDC input signal to the microboard.
See the formula above for voltage readings that
correspond to specific discharge pressures.
J7-7 = +5 VDC return
J7-2 = drain (shield connection = 0 VDC)
System 2 Discharge Transducer
J9-6 = +5 VDC regulated supply to transducer.
J9-11 = VDC input signal to the microboard.
See the formula above for voltage readings that
correspond to specific discharge pressures.
J9-7 = +5 VDC return
J9-2 = drain (shield connection = 0 VDC)
The suction transducers have a range from 0 psig to
400 psig (27.5 barg). The output will be linear from 0.5
VDC to 4.5 VDC over the 400 psig (27.5 barg) range.
Following is a formula that can be used to verify the
voltage output of the transducer. All voltage reading
are in reference to ground (unit case).
V = (Pressure in psig x .02) + .5
or
V = (Pressure in barg x .29) + .5
where V = dc voltage input to micro
Pressure = pressure sensed by transducer
Following are the I/O board connections for the Suc-
tion Transducer:
System 1 Suction Transducer
J7-5 = +5 VDC regulated supply to transducer.
J7-10 = VDC input signal to the microboard.
See the formula above for voltage readings that
correspond to specific suction pressures.
J7-9 = +5 VDC return
J7-1 = drain (shield connection = 0VDC)
System 2 Suction Transducer
J9-5 = +5 VDC regulated supply to transducer.
J9-10 = VDC input signal to the microboard.
See the formula above for voltage readings that
correspond to specific suction pressures.
J7-9 = +5 VDC return
J7-11 = drain (shield connection = 0 VDC)
Summary of Contents for YLUA0078
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 42: ...JOHNSON CONTROLS 42 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 100: ...JOHNSON CONTROLS 100 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 130: ...JOHNSON CONTROLS 130 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 152: ...JOHNSON CONTROLS 152 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...