SECTION 8 – UNIT OPERATION
FIGURE 23 -
DISCHARGE AIR TEMPERATURE CONTROL
20 sec.
30 sec.
60 sec.
control range 60 sec.
unloading
unloading
unloading
(no compressor staging) loading
51.5°F
52.5°F
53.0°F
55.0°F
57.0°
(10.8°C)
(11.4°C)
(11.7°C)
(12.8°C)
(13.9°C)
Low Limit Setpoint High limit
Discharge Air Temperature Control – Compressor Staging
Setpoint = 55.0°F (12.8°C) Range = +/- 5°F (-12.2°C)
TABLE 23 -
DISCHARGE AIR TEMPERATURE CONTROL FOR 5 AND 6 COMPRESSORS (7 AND 8 STEPS)
LEAD SYSTEM (SEQUENCE - SEE NOTE 4)
LAG SYSTEM (SEQUENCE - SEE NOTE 4)
* STEP
COMP 1
COMP 2
COMP 3
COMP 1
COMP 2
COMP 3
0
OFF
OFF
OFF
OFF
OFF
OFF
1
ON+HG
OFF
OFF
SEE NOTE 1
OFF
OFF
OFF
2
ON
OFF
OFF
OFF
OFF
OFF
3
ON
OFF
OFF
SEE NOTE 2
ON
OFF
OFF
4
ON
ON
OFF
SEE NOTE 3
OFF
OFF
OFF
5
ON
ON
OFF
ON
OFF
OFF
6
ON
ON
OFF
ON
ON
OFF
7
ON
ON
ON
ON
ON
OFF
8
ON
ON
ON
ON
ON
ON
Notes:
1. Step 1 is Hot Gas Bypass and is skipped when loading occurs. Hot Gas Bypass operation is inhibited during Pumpdown. For Discharge Air
Temperature Control the Hot Gas Bypass solenoid is energized only when the lead compressor is running and the DAT < SP, the Hot Gas
Bypass solenoid is turned off when the DAT > SP + CR/2.
2. Step 3 is skipped when loading occurs.
3. Step 4 is skipped when unloading occurs.
* STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND.
4. Each system will attempt to rotate the lead compressor start sequence to help even out the run hours in a system, therefore piping suction
risers should be sized off the smallest compressor capacity in either system.
TABLE 24 -
DISCHARGE AIR TEMPERATURE CONTROL FOR 4 COMPRESSORS (6 STEPS)
LEAD SYSTEM (SEQUENCE - SEE NOTE 4)
LAG SYSTEM (SEQUENCE - SEE NOTE 4)
* STEP
COMP 1
COMP 2
COMP 1
COMP 2
0
OFF
OFF
OFF
OFF
1
ON+HG
OFF
SEE NOTE 1
OFF
OFF
2
ON
OFF
OFF
OFF
3
ON
OFF
SEE NOTE 2
ON
OFF
4
ON
ON
SEE NOTE 3
OFF
OFF
5
ON
ON
ON
OFF
6
ON
ON
ON
ON
Notes:
1. Step 1 is Hot Gas Bypass and is skipped when loading occurs. Hot Gas Bypass operation is inhibited during Pumpdown. For Discharge Air
Temperature Control the Hot Gas Bypass solenoid is energized only when the lead compressor is running and the DAT < SP, the Hot Gas
Bypass solenoid is turned off when the DAT > SP + CR/2.
2. Step 3 is skipped when loading occurs.
3. Step 4 is skipped when unloading occurs.
* STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND.
4. Each system will attempt to rotate the lead compressor start sequence to help even out the run hours in a system, therefore piping suction
risers should be sized off the smallest compressor capacity in either system.
Summary of Contents for YLUA0078
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 42: ...JOHNSON CONTROLS 42 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 100: ...JOHNSON CONTROLS 100 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 130: ...JOHNSON CONTROLS 130 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 152: ...JOHNSON CONTROLS 152 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...